Johnson Controls Unitary Products

Table 6:

Physical Data  

Component

Models

JP024

JP030

JP036

JP042

JP048

JP060

Nominal Tonnage

2.0

2.5

3.0

3.5

4.0

5.0

ARI COOLING PERFORMANCE

Gross Capacity @ ARI A point (Btu)

25160

29700

37000

45800

50600

55700

ARI net capacity (Btu)

24660

29000

36000

44700

49300

53600

EER

11.95

11.5

11.3

11.9

12.2

11.15

SEER

13

13

13

13

13

13

Nominal CFM

900

1000

1150

1400

1500

1750

System power (KW)

2060

2500

3200

3740

4030

4820

Refrigerant type

R-22

R-22

R-22

R-22

R-22

R-22

Refrigerant charge (lb-oz)

System 1

10-4

10-8

10-8

11-8

11-8

11-8

ARI HEATING PERFORMANCE

47°F Capacity Rating (MBH)

22400

25900

32100

39600

43900

50000

System Power KW/COP

1760/3.70

2100/3.60

2780/3.40

3420/3.40

3750/3.45

4580/3.25

17°F Capacity Rating (MBH)

10500

12900

17300

19900

23600

29000

System Power KW/COP

1490/2.10

1770/2.15

2410/2.10

2835/2.05

3400/2.05

3980/2.10

HSPF BTU/Watts-hr

7.7

7.7

7.7

7.7

7.7

7.7

DIMENSIONS (inches)

Length

47-1/4

47-1/4

47-1/4

57-9/16

57-9/16

57-9/16

Width

32-13/16

32-13/16

32-13/16

32-13/16

32-13/16

32-13/16

Height

30-11/16

30-11/16

30-11/16

34-11/16

34-11/16

34-11/16

OPERATING WT. (lbs.)

342

347

350

372

382

390

COMPRESSORS

Type

Recip

Recip

Recip

Recip

Scroll

Scroll

Quantity

1

1

1

1

1

1

CONDENSER COIL DATA

Face area (Sq. Ft.)

11.28

11.28

11.28

16

16

16

Rows

2

2

2

2

2

2

Fins per inch

15

15

15

15

15

15

Tube diameter (in.)

3/8

3/8

3/8

3/8

3/8

3/8

Circuitry Type

Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined

Refrigerant Control

TXV

TXV

TXV

TXV

TXV

TXV

EVAPORATOR COIL DATA

Face area (Sq. Ft.)

4.67

4.67

4.67

5.44

5.44

5.44

Rows

4

4

4

4

4

4

Fins per inch

13

13

13

13

13

13

Tube diameter

3/8

3/8

3/8

3/8

3/8

3/8

Circuitry Type

Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined

Refrigerant control

Orifice

Orifice

Orifice

Orifice

Orifice

Orifice

CONDENSER FAN DATA

Quantity

1

1

1

1

1

1

Fan diameter (Inch)

20

20

20

22

22

22

Type

Prop

Prop

Prop

Prop

Prop

Prop

Drive type

Direct

Direct

Direct

Direct

Direct

Direct

No. speeds

1

1

1

1

1

1

Number  of  motors

1

1

1

1

1

1

Motor HP each

1/4

1/4

1/4

1/3

1/3

1/3

RPM

850

850

1100

1100

1100

1100

Nominal total CFM

2500

2500

2850

3200

3200

3200

DIRECT DRIVE EVAP FAN DATA

Quantity

1

1

1

1

1

1

Fan diameter (Inch)

10 x 7

10 x 7

10 x 7

11 x 10

11 x 10

11 x 10

Type

Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal

Drive type

Direct

Direct

Direct

Direct

Direct

Direct

No. speeds

5

5

5

5

5

5

Number  of  motors

1

1

1

1

1

1

Motor HP each

1/2

1/2

1/2

1

1

1

RPM

1100

1100

1100

1100

1100

1100

Frame size

48

48

48

48

48

48

Содержание LATITUDE JP024-060

Страница 1: ...tion 11 13 Defrost Operation Curves 12 14 Demand Defrost Curve Selection Jumper 12 General YORK Model JP units are factory assembled heat pump designed to be installed along side the home or building Field installed electric heater accessories are available to provide supplemental electric heat The units are completely assembled on rigid base rails All piping refrigerant charge and electrical wiri...

Страница 2: ...NSI NFPS No 70 or Canadian Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other applicable local codes Refer to Table 6 for unit physical data and to Table 5 for electrical data This product must be installed in strict compliance with the installation instructions and any applicable local state and national codes including but not limited to building electr...

Страница 3: ...nce and routing of electrical service to connect the unit Try to select a site for the unit that it is as close as possible to the proposed return grille location Unit may be positioned to draw air from underneath structure Direct Drive Condenser Fan Motor Decorative Protective Coil Guard Heavy Gauge Base Rails Control Box Service Access Panel Refrigerant Connections X13 Direct Drive Blower Motor ...

Страница 4: ...grade away from the unit will improve drainage 10 Average Winter Snow Depth The heat pump must be installed above the average snow depth to allow the outdoor coil to drain properly Cinder blocks if permitted by local codes or a metal frame may be used to support the unit above the snow Insure that the support does not obstruct drainage holes in the base pan of the unit Metal frame legs must be sup...

Страница 5: ... E F D CONDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 036 3 0 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 042 3 5 32 13 16 34 11 16 57 9 16 11 9 16 10 5 16 28 7 8 14 2 3 4 048 4 0 32 13 16 34 11 16 57 9 16 11 9 16 10 5 ...

Страница 6: ...d be installed first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting connects to the bottom of the return air box so it will be necessary to provide an opening beneath the box See Figure 5 Figure 5 Return Air Box and Grille After determining the location of the return ...

Страница 7: ...ace 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with the stub collar to the air conditioner return air flange with screws and duct tape sealing the duct cover securely Wye Insulation It is necessary to field fabricate and install an insulation jacket for the Wye Insulation will prevent loss of capacity especiall...

Страница 8: ...ound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locating the duct center increase the hole in the fiber board to approximately the size of the duct connector Figure 8 Duct Connector With Damper Figure 9 Duct Connector No Damper May use duct connector without damper if no interior furnace or air handler is connect...

Страница 9: ...in hose to the drain tube Service Access Access to all serviceable components is provided at the following locations Blower compartment access panel Control box access panel Refer to Figure 1 for location of these access locations and minimum clearances in Table 3 Power And Control Wiring Field wiring to the unit must conform to provisions of the current N E C ANSI NFPA No 70 or C E C and or local...

Страница 10: ...tall on a partitioning wall not on an outside wall 3 Never expose it to direct light from lamps sun fireplaces etc 4 Avoid locations close to doors that lead outside to windows or to adjoining outside walls 5 Avoid locations close to radiators warm air registers or in the direct path of heat or cold air from them 6 Make sure that there are no pipes or ductwork in that part of the wall chosen for t...

Страница 11: ...at temperature selection lever high enough to close the second stage of the thermostat if it is not already closed The indoor blower will turn on when the heating elements stage on If accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setting Record the following ...

Страница 12: ...ature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while the compressor is on During the defrost mode the defrost control will provide a 24 volt signal from terminal W1 66 to the fan control terminal W1 This signal will energize electric heat stage 1 if the unit is so equipped Fo...

Страница 13: ...44 0 47 3 50 50 2PH08510706 4 9 6 5 1 23 5 27 1 51 8 56 3 60 60 2PH08511006 7 2 9 6 1 34 5 39 8 65 6 72 2 70 80 2PH08511506 10 8 14 3 1 51 7 59 7 87 1 97 1 90 100 208 230 3 60 8 2 72 0 16 0 1 6 4 1 None 18 5 25 042 3 5 208 230 1 60 17 1 86 0 26 5 1 8 7 6 None 30 8 40 2PH08510506 3 6 4 8 1 17 2 19 9 52 3 55 7 60 60 2PH08510706 4 9 6 5 1 23 5 27 1 60 1 64 6 70 70 2PH08511006 7 2 9 6 1 34 5 39 8 73 9...

Страница 14: ... Recip Recip Recip Recip Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 28 11 28 11 28 16 16 16 Rows 2 2 2 2 2 2 Fins per inch 15 15 15 15 15 15 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined Refrigerant Control TXV TXV TXV TXV TXV TXV EVAPORATOR COIL DATA Face area Sq Ft 4 67 4 67 4 67 5 44...

Страница 15: ...136 1090 535 1161 High 2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016 Medium 1546 394 865 1391 439 975 1187 479 1080 1062 501 1088 892 347 1034 Medium High 1597 434 893 1460 476 989 1277 518 995 1079 515 1050 High 2227 978 1086 1976 889 1129 1677 757 11...

Страница 16: ...0 19 0 20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0 33 0 33 0 33 0 34 0 37 1900 0 35 0 35 0 35 0 36 0 39 2000 0 37 0 37 0 37 0 38 0 41 2100 0 39 0 39 0 39 0 40 0 43 2200 0 41 0 41 0 41 0 42 0 45 060 5 0 JP 500 0 09 0 09 0 09 0 10 0 12 600 0 1 0 10 0 ...

Страница 17: ... CFM Heater kW 5 0 6 5 10 0 15 0 024 2 0 208 230 1 60 800 800 800 750 030 2 5 208 230 1 60 800 800 800 750 036 3 0 208 230 1 60 800 800 800 750 042 3 5 208 230 1 60 1300 1300 1270 1270 048 4 0 208 230 1 60 1300 1300 1270 1270 060 5 0 208 230 1 60 1300 1300 1270 1270 Table 10 Indoor Blower Specifications Size Tons Motor HP RPM Eff SF Frame 024 2 0 1 2 1100 0 8 1 0 48 030 2 5 1 2 1100 0 8 1 0 48 036...

Страница 18: ...161036 YIM E 1008 18 Johnson Controls Unitary Products Typical Wiring Diagrams JP024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram ...

Страница 19: ...161036 YIM E 1008 Johnson Controls Unitary Products 19 JP036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram ...

Страница 20: ...nted in U S A 161036 YIM E 1008 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 161036 YIM D 1206 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 JP060 Typical Heat Pump 460 3 60 volt Wiring Diagram ...

Отзывы: