5803641-JIM-B-0620
8
Johnson Controls Ducted Systems
Figure 5: Unit 4 Point Load Weight
Figure 6: Unit 6 Point Load Weight
Figure 7: Center of Gravity
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
D
A
C
B
LEFT
FRONT
D
A
C
B
E
F
LEFT
FRONT
X
Y
LEFT
FRONT
Table 2: Weights and Dimensions
Size
(Tons)
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
6 Point Load Location (lbs.)
Shipping Operating
X
Y
A
B
C
D
A
B
C
D
E
F
JA3
(3)
ZJ
745
740
40
26
180
147
186
228
124
108
95
120
137
157
JA4
(4)
ZJ
767
762
40
24
171
139
203
249
118
102
90
131
149
172
JA5
(5)
ZJ
780
775
40
24
174
142
207
253
120
104
91
133
152
175
Table 3: JA3 thru A5ZJ Unit Accessory Weights
Unit Accessory
Weight (lbs.)
Shipping
Operating
Economizer
90
85
Power Exhaust
40
35
Electric Heat
1
49
49
Gas Heat
2
110
110
1. Weight given is for the maximum heater size available (24KW).
2. Weight given is for the maximum number of tube heat exchangers
available (8 tube).