SM-16005-rev.2
5-41
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.5.4 Comfort Function
Following functions are not available depending on connected outdoor unit.
(1) Quick Function
Do not use the Quick Function when using the Ducted (EconoFresh). When it is used, the thermal
load of heat source in the room may significantly increase depending on the outdoor temperature
conditions. Configure according to the outdoor temperature condition.
(2) Power Up Setting
If the cooling/heating capacity seems insufficient during the normal operation, set this function.
By setting this function, the target frequency and upper limit of the compressor are set higher as
follows.
Setting Condition
Power Up Mode
Compressor Frequency for Cooling Operation Compressor Frequency for Heating Operation
Upper Limit
Target Frequency
Upper Limit
Target Frequency
0 (Default Setting)
-
-
-
-
1
Default S20% Default S20%
-
-
2
-
-
Default S20% Default S20%
3
Default S20% Default S20% Default S20% Default S20%
NOTE:
The upper limit and target frequency of the compressor are same as Function Setting “Hc” or “Hh”.
Содержание IDM030B21E Series
Страница 2: ......
Страница 10: ...viii SM 16005 rev 2...
Страница 14: ......
Страница 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Страница 20: ...2 2 SM 16005 rev 2 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Ducted Medium Static EconoFresh...
Страница 22: ......
Страница 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 70: ......
Страница 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Страница 72: ...4 2 SM 16005 rev 2 MAINTENANCE 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 89: ...SM 16005 rev 2 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 130: ......
Страница 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Страница 142: ...SERVICE PARTS LIST 7 2 SM 16005 rev 2 Refer to the Service Parts List for Ducted Medium Static EconoFresh...
Страница 143: ......
Страница 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...