5-28
SM-16005-rev.2
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(45) Not Prepared (E9)
(46) Not Prepared (EA)
(47) Fan Operation Control during Cooling Thermo-OFF (Eb)
This function is utilized to prevent diffusion of odor and high humidity by reducing the indoor fan speed
during cooling Thermo-OFF.
Setting Condition
Fan Operation during Thermo-OFF
00
LOW
01
SLOW
Setting Condition
Fan Operation during Thermo-OFF
00
Operation at Set Fan Speed
01
LOW
02
SLOW
(38) Enthalpy Sensor (E2)
This function selects the enthalpy sensor input.
(39) Not Prepared (E3)
(40) CO
2
Gas Sensor (E4)
This function selects the CO
2
gas sensor input.
(41) Not Prepared (E5)
(42) Indoor Fan Operation Time After Cooling Operation Stoppage (E6)
This function is utilized to prevent condensation upon cooling operation stoppage by “SLOW” indoor
fan operation to dry. “SLOW” operation (for 60 minutes or 120 minutes by setting) continues even
when the cooling operation is stopped.
(43) Not Prepared (E7)
(44) Fan Operation Control during Heating Thermo-OFF (E8)
This function is utilized to prevent the perception of cold draft by reducing the indoor fan speed during
heating Thermo-OFF.
(48) Forced Thermo-ON Stoppage during Cooling (EC)
This function is utilized to force Thermo-ON and then stop the operation when cooling operation is
stopped.
This is effective to prevent abnormal odor because the heat exchanger is rinsed with drain water to
keep in the clean condition.
(49) Not Prepared (Ed)
(50) Not Prepared (EE)
(51) Automatic Fan Speed Control (Corresponding to HIGH2) (EF)
This function is utilized to increase the maximum fan speed to "HIGH2" setting condition when the
maximum fan speed remain "HIGH" by default.
The fan speed setting (EF) by Wired Controller are shown below.
Function
Selection
EF Setting
Wired Controller Setting
AUTO
HIGH2
HIGH
MED
LOW
00
HIGH - LOW
HIGH2
HIGH
MED
LOW
01
HIGH2 - LOW
HIGH2
HIGH
MED
LOW
NOTE:
This function is not available when the auxiliary heater is enabled. Fan speed is either "HIGH" or
"HIGH2" during this time.
Содержание IDM030B21E Series
Страница 2: ......
Страница 10: ...viii SM 16005 rev 2...
Страница 14: ......
Страница 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Страница 20: ...2 2 SM 16005 rev 2 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Ducted Medium Static EconoFresh...
Страница 22: ......
Страница 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 70: ......
Страница 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Страница 72: ...4 2 SM 16005 rev 2 MAINTENANCE 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 89: ...SM 16005 rev 2 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 130: ......
Страница 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Страница 142: ...SERVICE PARTS LIST 7 2 SM 16005 rev 2 Refer to the Service Parts List for Ducted Medium Static EconoFresh...
Страница 143: ......
Страница 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...