• The drain hose can be connected to the left or the
right side.
Verification of condensate water drainage:
Fill the drain pan with water and observe evacuation.
Drain hose
For right connection
Drain cap
■
Indoor Unit Fixing
• Thread the indoor unit piping and cable through the hole.
• Hang the top of the unit onto the upper ridge of them in mounting plate.
• Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.
• Press the bottom left and bottom right hand corners of the unit against the mounting plate until the fixing prongs click
into place in the retainers provided to that effect.
Drainage line
Interconnection cable
Note: The condensate evacuation line should be taped to the re-
frigerant lines with vinyl tape.
a) Access plate for the
condensate drainage
pump detection
(condensate pump is
available as an
accessory).
Condensate
drainage line
Vinyl tape
a
■
Drain hose
• Drain hose is flexible and can be routed to suit various
piping arrangements. The drain line must include elbow
trap (U bend). Connect a plastic condensate pipe with
an internal diameter of 12 mm.
Note: Do not put the drain hose end into water.
Drain cap
For left and left rear piping (Factory standard)
Drain hose
J222