background image

035-16399-001 Rev. B (101)

6

Unitary Products Group

ELECTRICAL CONNECTIONS

GENERAL INFORMATION & GROUNDING

Check the electrical supply to be sure that it meets the values
specified on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect
switches and over current protection to be supplied by the
installer. Wire size should be sized per NEC requirements

The complete connection diagram and schematic wiring label
is located on the inside surface of the unit electrical box cover
and this instruction.

POWER WIRING

1.

Install the proper size weatherproof disconnect switch
outdoors and within sight of the unit.

2.

Run power wiring from the disconnect switch to the unit.

3.

Remove the control box cover to gain access to the unit
wiring. Route wires from disconnect through power wir-
ing opening provided and into the unit control box as
shown in Figure 3.

4.

Install the proper size time-delay fuses or circuit breaker,
and make the power supply connections. 

5.

Energize the crankcase heater to save time by preheat-
ing the compressor oil while the remaining installation is
completed.

ACCESSORY WIRING

The electrical accessories available for this unit are a two
stage cooling thermostat and an optional De-humidification
Control. Refer to the individual instructions packaged with the
accessories for installation.

THERMOSTAT MOUNTING / WIRING

This condensing unit must be installed with the factory rec-
ommended thermostat, 2ET04700224 or any conventional
two-stage cooling thermostat. The difference between the
two stages of a typical two-stage thermostat is 2 - 2.5 °F.

The thermostat should be located about 5 ft. above the floor,
where it will be exposed to normal room air circulation. Do not
place it on an outside wall or where it is exposed to the radi-
ant effect from exposed glass or appliances, drafts from out-
side doors or supply air grilles.

After the thermostat is mounted, route the 24-volt control wir-
ing (NEC Class 2) from the thermostat to the indoor unit and
outdoor unit. Route the control wiring into the grommeted
hole in the bottom of control box of the outdoor unit. Using
wire nuts connect to leads inside the low voltage box shown
in Figure 3 and wiring diagrams shown in Figures 4 -7.

Interconnecting control wiring must be a minimum of No. 18
AWG color coded insulated wires. If wire lengths increase
more than 90 feet, use No. 16 AWG wires, to prevent exces-
sive voltage drop.

NOTE:  

To eliminate erratic operation, seal the hole in the

wall at the thermostat with permagum or equivalent
to prevent air drafts affecting the anticipators in the
thermostat.

DE-HUMIDIFICATION CONTROL

A de-humidification control accessory 2HU06700124 may be
required in high humidity areas that apply to varible speed air
handler/furnaces. This control provides cooling at a reduced
air flow, lowering evaporator temperature and increasing
latent capacity. To install, refer to instructions packaged with
the accessory and per Figure 4. Prior to the installation of the
de-humidistat control, the jumper across the de-humidistat
control terminals on the indoor variable speed air handler/fur-
nace terminal board must be removed.

During first or second stage cooling, if the relative humidity in
the space is higher than the desired set point of the de-humi-
distat control, the variable speed blower motor will operate at
a lower speed until the de-humidification control is satisfied.
A 40 - 60% relative humidity level is recommended to achieve
optimum comfort.

NOTE:  

If a de-humidification control is installed, it is recom-

mended that a minimum air flow of 325 cfm/ton be
supplied at all times.

Never attempt to repair any brazed connections
while the system is under pressure. Personal
injury could result.

All field wiring must USE COPPER CONDUC-
TORS ONLY and be in accordance with Local,
National Fire, Safety & Electrical Codes. This unit
must be grounded with a separate ground wire in
accordance with the above codes.

 FIGURE 3 : 

OUTDOOR UNIT CONTROL BOX

START
RELAY

START
CAPACITOR

RUN
CAPACITOR

POWER
WIRING

LOW
VOLTAGE
BOX

COMFORT
ENHANCER
CONTROL

CONTACTOR

Содержание HATC-F024S

Страница 1: ...NFORMATION GROUNDING 6 POWER WIRING 6 ACCESSORY WIRING 6 THERMOSTAT MOUNTING WIRING 6 DE HUMIDIFICATION CONTROL 7 FIELD CONNECTIONS CONTROL WIRING 7 INDOOR BLOWER SPEED SETTINGS 7 WIRING DIAGRAMS 8 SY...

Страница 2: ...en to alert the installer that severe per sonal injury death or equipment damage may result if instal lation procedures are not followed properly LIMITATIONS The unit should be installed in accordance...

Страница 3: ...ined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided 5 Make a hole s in the structure...

Страница 4: ...nstalled only with the tubing sizes for approved system com binations as specified in Tabular Data Sheet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Form...

Страница 5: ...ng the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum NOTE Do not use the system refrigerant in the outdoor unit to purge or leak test 9 D...

Страница 6: ...r ing NEC Class 2 from the thermostat to the indoor unit and outdoor unit Route the control wiring into the grommeted hole in the bottom of control box of the outdoor unit Using wire nuts connect to l...

Страница 7: ...y to Y1 on the outdoor unit Do not connect to Y at the indoor control The first stage blower operation is controlled by the G signal It is critical the Y2 OUT signal is connected to Y at the air handl...

Страница 8: ...TROL CLASS 2 WIRING POWER WIRING 208 230 1 60 GND LUG T2 T1 L2 L1 M1 BLK RED BRN YEL ORG PUR C R Y2 Y1 R Y2 Y1 G W1 W2 X L W2 W1 G Y C R 1 2 Y2 OUT X L C LOW HIGH FIGURE 6 WIRING FOR USE WITH SINGLE S...

Страница 9: ...T USED 2 OUTDOOR UNIT WIRE NUT CONTACTOR THERMOSTAT P DU P XU 2 STAGE FURNACE TYPICAL TWO STAGE COOLING THERMOSTAT MUST BE USED DEHUMIDISTAT OPTIONAL POWER CONTROL FACTORY CLASS 1 WIRING TS CONTROL CL...

Страница 10: ...ed with the matching thermostatic expansion valve kit listed in the tabular data sheet The best way to check the system charge is by check ing the system subcooling during the second stage of opera ti...

Страница 11: ...15 of the pro grammed speed during the dehumidification mode This lower airflow reduces the evaporator temperature increasing the latent capacity The humidistat for these variable speed systems opens...

Страница 12: ...maintenance Instruct the owner or the opera tor how to start stop and adjust temperature setting The installer should also instruct the owner on proper opera tion and maintenance of all other system...

Отзывы: