background image

FIRST STAGE OF COOLING

A call for cooling at terminal Y1 energizes relay RY1.  Relay
RY1 closes contacts RY1-1, energizing time delay relay 3TR.
If time delay relay 3TR is satisfied as described below, it will
energize its output terminal Y2, which is connected to compres-
sor 1 control module terminal M1.

If the compressor 1 control module is satisfied as described
below, it will apply power to terminal 7 of low or high pressure
lock out relay (LOR) contacts.  See a description of the LOR
operation below.  If the LOR coil is not energized (not locked
out), the LOR contacts will be closed,  energizing contactor 1M,
which powers compressor 1 and condenser fan motor 1.  

When 1M is energized on H3CE240 units, auxiliary contact
1M-AC2 is closed, powering terminal 1 for opening the stage 1
solenoid in air handlers which feature a stage 1 solenoid.

If the low ambient temperature switch TLA is closed, it will allow
condenser fan 2 contactor 3M to energize.  TLA opens as the
temperature falls below 50 F and closes as the ambient rises
above 60 F.  TLA is used on the H3CE180, not the H3CE240.

Anti-short Cycle Time Delay Relays 3TR and 4TR

Relay 3TR, which serves compressor 1 control, has an adjust-
able low voltage lock out which is set at 20V in the factory.  The
voltage applied to 3TR must be above its lock out setting and
5 minutes must elapse since the relay was last energized
before it will energize its output terminal Y2.  Relay 4TR is
identical but it serves compressor 2 control.

Compressor Control Module

If  the compressor control module terminals L1 (or T1) and L2
(or T2) have 24 V applied and the internal compressor tempera-
ture lock out is inactive, the internal switch connecting M1 and

M2 will be closed.  M1 to M2 will open if one of the compressor’s
internal temperature sensors exceeds its limit.  M1 to M2 stays
open for 30 minutes after a internal temperature limit is ex-
ceeded.  The 30 minute lock out may be reset prior to the 30
minutes expiring by removing power to the control module
terminals L1 and L2.  During normal operation, each compres-
sor control module should always be powered at the L1 and L2
terminals, whether there is a call for cooling or not.

Low or High Pressure Lock Out Operation 

If the lock out circuit path is opened during a call for cooling,
the lock out relay (LOR) coil will energize, opening LOR-1
contacts and disabling all compressor operation.  The lock out
circuit path is open if:

 the lock out relay contacts LOR-1 are open, OR

 the low pressure switch LP is open AND the low
 pressure switch bypass timer contacts 1TR-1 are open
OR

 the high pressure switch HP is open.

 Once the LOR coil has been energized, it remains energized,
locking out cooling operation until the call for cooling has been
removed.  When Y1 is returned to 0 volts, the LOR coil is no
longer energized, closing the LOR-1 contacts and removing the
lock out.

 The low pressure bypass timer 1TR leaves the 1TR-1 contacts
closed upon the start of a call for cooling until its 90 second
(nominal) timer has expired.  This bypasses the low pressure
switch during start up.  After the time delay has elapsed, 1TR-1
contacts are opened, once again allowing low pressure to
trigger the lock out circuit if the low pressure switch opens.

START-UP

CRANKCASE HEATER

The crankcase heater must be energized at least 8 hours before
starting the compressor. To energize the crankcase heater, the
main disconnect switch must be closed. During this 8 hour
period, the system switch on the room thermostat must be
“OFF” to prevent the compressor from starting.

CAUTION: DO NOT ATTEMPT TO START THE COMPRES-

SOR WITHOUT AT LEAST 8 HOURS OF CRANK-
CASE HEAT OR COMPRESSOR DAMAGE CAN
OCCUR.

Make sure that the bottom of the compressor is warm to the
touch to prove crankcase heater operation.

PRE-START CHECK

Before starting the unit, complete the following check list:

1. Have sufficient clearances been provided?

2. Has all foreign matter been removed from the interior of the

unit (tools, construction or shipping materials, etc.)?

3. Have the condenser fans been rotated manually to check

for free rotation?

4. Are all wiring connections tight?

5. Does the available power supply agree with the nameplate

data on the unit?

6. Is the control circuit transformer set for the proper voltage?

7. Have the fuses, disconnect switch and power wire been

sized properly?

8. Are all compressor hold-down nuts properly secured?

9. Are any refrigerant lines touching each other or any sheet

metal surface? Rubbing due to vibration could cause a
refrigerant leak.

10. Are there any visible signs of a refrigerant leak, such as oil

residue?

11. Is any electrical wire laying against a hot refrigerant line?

INITIAL START-UP

1. Supply power to the unit through the disconnect switch at

least 8 hours prior to starting the compressor.

2. Move the system switch on the thermostat to the AUTO or

COOL position.

3. Reduce the setting of the room thermostat to energize the

compressor.

4. Check the operation of the evaporator unit per the manufac-

turer’s recommendations.

5. With an ammeter, check the compressor amps against the

unit data plate.

6. Check for refrigerant leaks.

7. Check for any abnormal noises and/or vibrations, and make

the necessary adjustments to correct (e.g. fan blade(s)
touching shroud, refrigerant lines hitting on sheet metal,
etc.)

8. After the unit has been operating for several minutes, shut

off the main power supply at the disconnect switch and
inspect all factory wiring connections and bolted surfaces for
tightness.

OPERATION

550.23-N6Y

12

Unitary Products Group

Содержание H3CE180

Страница 1: ...f the evaporator blower units refer to instruction Form 550 23 N4Y All accessories come with a separate Installation Manual Refer to Parts Manual for complete listing of replacement parts on this equi...

Страница 2: ...Secure Owner s Approval 12 Maintenance 12 Cleaning Condenser Surface 13 Lubrication 12 Compressor Replacement 12 TABLES No Description Page 1 Unit Application Data 3 2 Physical Data 4 3 Electrical Dat...

Страница 3: ...4 Footers under the slab that extend below the frost line are recom mended Anystrainontherefrigerantlinesmaycausearefrigerant leak Theslabshouldnotbetiedtothebuildingfoundationbecause noise and vibra...

Страница 4: ...r general installation procedure Refer to Figure 3 for typical field wiring COMPRESSOR CRANKCASE HEATER The compressor is equipped with a crankcase heater to prevent refrigerant from mixing with crank...

Страница 5: ...R S H 3 C E 1 8 0 K 1 E U 1 8 0 H 3 C E 2 4 0 L 3 E U 2 4 0 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T...

Страница 6: ...A C C E S S E X T E R N A L P R E S S U R E G A U G E F I T T I N G S C O N T R O L B O X A C C E S S 9 1 3 2 7 6 7 8 7 1 3 2 3 9 7 8 1 3 1 4 3 0 3 4 2 4 1 2 1 2 1 8 C D F E F E F A B All dimensions a...

Страница 7: ...on line must be sized for both pressure drop and for oil return For certain piping arrangements different suction line sizes may have to be used The velocity of the suction gas must always be great en...

Страница 8: ...oor system performance but could also damage the expansion valve TABLE 5 LIQUID LINES Liquid Line2 Inches O D 5 8 0 113 lb ft 7 8 0 237 lb ft Suction Line2 Inches O D 1 5 8 0 018 lb ft 2 1 8 0 031 lb...

Страница 9: ...rom the access port on the liquid line service valve of the condensing unit to the hole through the suction disc on the evaporator coil 3 Unbraze the coil s liquid line disc while maintaining a flow o...

Страница 10: ...f the refrigerant for the total system by adding the required charge for the outdoor unit the indoor unit and the refrigerant lines using information in Tables 2 Physical Data and 6 Refrigerant Line C...

Страница 11: ...F Ambient 95 F Ambient 85 F Ambient 75 F Ambient Charging Curve H CE240 200 250 300 350 400 57 62 67 72 77 82 87 92 97 Suction Pressure Discharge Pressure 115 F Ambient 105 F Ambient 95 F Ambient 85...

Страница 12: ...rgized locking out cooling operation until the call for cooling has been removed When Y1 is returned to 0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out...

Страница 13: ...ration to 0 F SAFETY FEATURES 1 The compressor is protected against over current and excessive temperature as described in the Sequence of Operation 2 The compressor is equipped with a crankcase heate...

Отзывы: