Johnson Controls Unitary Products

7

277805-YTG-A-1106

APPLYING FILTER PRESSURE DROP TO 
DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in
place, follow the steps below:

1.

Select the filter type.

2.

Select the number of return air openings or calculate the 
return opening size in square inches to determine the 
proper filter pressure drop.

3.

Determine the External System Static Pressure (ESP) 
without the filter.

4.

Select a filter pressure drop from the table based upon 
the number of return air openings or return air opening 
size and add to the ESP from Step 3 to determine the 
total system static.

5.

If total system static matches a ESP value in the airflow 
table (i.e. 0.20, 0.60, etc,) the system airflow corre-
sponds to the intersection of the ESP column and Model/
Blower Speed row.

6.

If the total system static falls between ESP values in the 
table (i.e. 0.58, 0.75, etc.), the static pressure may be 
rounded to the nearest value in the table determining the 
airflow using Step 5 or calculate the airflow by using the 
following example.

Example:  For a 120,000 Btuh furnace with 2 return openings
and operating on high speed blower, it is found that total sys-
tem static is 0.58" w.c. To determine the system airflow, com-
plete the following steps:

1.

Obtain the airflow values at 0.50" & 0.60" ESP.

Airflow @ 0.50":  2285 CFM

Airflow @ 0.60":  2175 CFM

2.

Subtract the airflow @ 0.50" from the airflow @ 0.60" to 
obtain airflow difference.

2175 - 2285 = -110 CFM

3.

Subtract the total system static from 0.50" and divide this 
difference by the difference in ESP values in the table, 
0.60" - 0.50", to obtain a percentage.

(0.58 - 0.50) / (0.60 - 0.50) = 0.8

4.

Multiply percentage by airflow difference to obtain airflow 
reduction.

(0.8) x (-110) = -88

5.

Subtract airflow reduction value to airflow @ 0.50" to 
obtain actual airflow @ 0.58" ESP.

2288 - 88 = 2197

ACCESSORIES

PROPANE (LP) CONVERSION KIT - 

1NP0347 - All Models

This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation. Conversions must be
made by qualified distributor or dealer personnel.

CONCENTRIC VENT TERMINATION - 

1CT0302 (2")

1CT0303 (3")

For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole.

SIDEWALL VENT TERMINATION KIT - 
1HT0901 (3”) and  1HT0902 (2”)
For use on sidewall, two-pipe installations only. Provides a
more attractive termination for locations where the terminal is
visible on the side of the home.

CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for instal-
lation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).

EXTERNAL SIDE RETURN FILTER RACK -

1SF0101 - Fits all cabinet sizes
Attaches to side of furnace cabinet in side return applications.
Holds any 16x25x1 permanent or disposable filter.

SIDE RETURN FILTER - 

1SR0302 - All Models

1SR0200 - All Models

BOTTOM RETURN FILTER - 

1BR0114 or 1BR0214 - For 14-1/2” cabinets

1BR0117 or 1BR0217 - For 17-1/2” cabinets

1BR0121 or 1BR0221 - For 21” cabinets

1BR0124 or 1BR0224 - For 24-1/2” cabinets

INTERNAL FILTER WITH FIBER FILTER - 

1HF0801 - All Models

HIGH ALTITUDE PRESSURE SWITCHES - 

For installation where the altitude is less than 8,000 feet it is
not required that the pressure switch be changed. For alti-
tudes above 8,000 feet see kits below. Conversion must be
made by qualified distributor or dealer personnel.

1PS0307 - 080, 100 MBH
1PS0309 - 060, 120 MBH
1PS0322 - 040, 135 MBH

ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.

1H/1C, manual change-over electronic non-programmable 
thermostat.

1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

* For the most current accessory information, refer to the
price book or consult factory.

Содержание GY9S-UP

Страница 1: ...aser 10 year warranty on the heat exchanger in commercial appli cations 5 year limited parts warranty FEATURES Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improve...

Страница 2: ...MAGE RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in GY9...

Страница 3: ...12UP11 60 B 56 1200 17 1 2 9 92 0 40 70 GY9S080B12UP11 80 B 74 1200 17 1 2 9 92 0 45 75 GY9S080C16UP11 80 C 75 1600 21 12 92 0 45 75 GY9S080C20UP11 80 C 75 2000 21 14 92 0 40 70 GY9S100C16UP11 100 C 9...

Страница 4: ...680 1595 1500 1390 1270 1155 M LO 1610 1545 1490 1440 1390 1315 1230 1155 1050 920 LOW 1325 1270 1225 1175 1105 1045 990 905 890 790 GY9S080C16UP11 GY9S100C16UP11 HIGH 1960 1955 1925 1890 1830 1765 16...

Страница 5: ...ers 2 Air flows above 1800 CFM require either return from two sides or one side plus bottom RECOMMENDED FILTER SIZES Nominal CFM Cabinet Size Side Return Filter in Bottom Return Filter in cm 1200 A 16...

Страница 6: ...tage Cool Y Y2 Single Second Stage Cool Y Single Stage Cool DN11C00124 C 24 Volt Common C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN...

Страница 7: ...ACCESSORIES PROPANE LP CONVERSION KIT 1NP0347 All Models This accessory conversion kit may be used to convert natural gas units for propane LP operation Conversions must be made by qualified distribut...

Страница 8: ...change without notice Printed in U S A 277805 YTG A 1106 Copyright by York International Corp 2006 All rights reserved Supersedes 246716 YTG B 0806 Unitary 5005 Norman Products York OK Group Drive 73...

Отзывы: