background image

404912-UIM-A-0508

10

Johnson Controls Unitary Products

*

May be 0 (no breaker) or 1 (with breaker).

TABLE 7: 

Electrical Data - (For 

Single Source 

Power Supply) - Copper Wire 1 Ø - 208/230-1-60

1

Models F*FP

Heater*

Model

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

75

°

C Wire Size - AWG

208V

240V

208V

240V

208V

240V

024

2HK*6500506B

20.8

24.7

27.7

25

30

10

10

2HK*6500806B

31.3

35.5

40.7

40

45

8

8

2HK*6501006B

41.7

46.9

53.7

50

60

8

6

030

2HK*6500506B

20.8

25.8

28.7

30

30

10

10

2HK*6500806B

31.3

36.7

41.7

40

45

8

8

2HK*6501006B

41.7

48.1

54.7

50

60

8

6

2HK16501506B

62.5

70.9

80.8

80

90

4

3

036

2HK*6500506B

20.8

26.8

29.5

30

30

10

10

2HK*6500806B

31.3

37.7

42.6

40

45

8

8

2HK*6501006B

41.7

49.1

55.6

50

60

8

6

2HK16501506B

62.5

71.9

81.6

80

90

4

3

2HK16501906B

3

73.3

83.3

95.2

90

100

3

3

040

2HK*6500506B

20.8

25.8

28.7

30

30

10

10

2HK*6500806B

31.3

36.7

41.7

40

45

8

8

2HK*6501006B

41.7

48.1

54.7

50

60

8

6

2HK16501506B

62.5

70.9

80.8

80

90

4

3

042

2HK*6500506B

20.8

28.1

30.5

30

35

10

8

2HK*6500806B

31.3

38.9

43.6

40

45

8

8

2HK*6501006B

41.7

50.3

56.6

60

60

6

6

2HK16501506B

62.5

73.2

82.6

80

90

4

3

045

2HK*6500506B

20.8

26.6

29.3

30

30

10

10

2HK*6500806B

31.3

37.4

42.3

40

45

8

8

2HK*6501006B

41.7

48.8

55.3

50

60

8

6

2HK16501506B

62.5

71.7

81.4

80

90

4

3

048

2HK*6500506B

20.8

32.8

35.6

35

40

8

8

2HK16500806B

31.3

43.0

48.4

45

50

8

8

2HK16501006B

41.7

55.3

61.5

60

70

6

4

2HK16501506B

62.5

77.3

87.8

80

90

4

3

2HK16502006B

83.3

101.0

113.8

110

125

2

1

2HK16502506B

104.2

124.3

139.9

125

150

1

1/0

060

2HK*6500506B

20.8

32.8

35.6

35

40

8

8

2HK16500806B

31.3

42.9

48.3

45

50

8

8

2HK16501006B

41.7

55.3

61.6

60

70

6

4

2HK16501506B

62.5

78.5

87.8

80

90

4

3

2HK16502006B

83.3

101.0

113.8

110

125

2

1

2HK16502506B

104.2

122.2

139.5

125

150

1

1/0

1. Heat amps shown at 240V represents maximum heater rating.
2. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
3. 2HK16501906B only applies to F4FP036 model.

TABLE 8: 

Electrical Data - (For 

Multi-Source 

Power Supply) - Copper Wire 1 Ø - 208/230-1-60

1

Models F*FP

Heater

Model

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

75

°

C Wire Size - AWG

Circuit

Circuit

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

030

2HK16501506B

25.8/28.7 45.1/52.1

30/30

50/60

10/10

8/6

036

2HK16501506B

26.8/29.5 45.1/52.1

30/30

50/60

10/10

8/6

2HK16501906B

2

38.3/42.6 45.7/52.6

40/45

50/60

8/8

8/6

040

2HK16501506B

25.8/28.7 45.1/52.1

30/30

50/60

10/10

8/6

042

2HK16501506B

28.1/30.5 45.1/52.1

30/35

50/60

10/8

8/6

045

2HK16501506B

26.6/29.3 45.1/52.1

30/30

50/60

10/10

8/6

048

2HK16501506B

32.8/35.6 45.1/52.1

35/40

50/60

8/8

8/6

2HK16502006B

55.3/61.6 45.1/52.1

60/70

50/60

6/4

8/6

2HK16502506B

32.8/35.6 45.1/52.1 45.1/52.1

35/40

50/60

50/60

8/8

8/6

8/6

060

2HK16501506B

32.8/35.6 45.1/52.1

35/40

50/60

8/8

8/6

2HK16502006B

55.3/61.6 45.1/52.1

60/70

50/60

6/4

8/6

2HK16502506B

33.8/35.6 45.1/52.1 45.1/52.1

35/40

50/60

50/60

8/8

8/6

8/6

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
2. 2HK16501906B only applies to F4FP036 model.

Содержание F4FP024H06T3X

Страница 1: ...ectrical Data For Multi Source Power Supply Copper Wire 1 208 230 1 601 10 Electrical Data 3 208 230 3 60 11 Electrical Data For Single Source Power Supply Copper Wire 3 208 230 3 60 11 Airflow Data f...

Страница 2: ...used for cooling or heat pump operation with or without electric heat BRAND LABEL available from Distribution can be applied to center of the blower access panel The unit can be positioned for bottom...

Страница 3: ...ed with the unit Ensure that the drain pan is lying flat against the insulation of the cabinet 7 Horizontal drain cutout in the center access panel should be removed by using a utility knife if not pr...

Страница 4: ...Sizes SHIPPING BRACKET REMOVE PRIOR TO INSTALLATION 2 SCREWS 10 3 8 J DRAIN CONNECTIONS FOR HORIZONTAL APPLICATIONS 4 D VAPOR OPENING LIQUID OPENING 2 B FILTER ACCESS DRAIN CONNECTIONS FOR UPFLOW APP...

Страница 5: ...model num bers 1PF0601 602 603BK See Table 3 for filter size SUSPENSION KITS A suspension kit is available Models 1BH0601 unit sizes 018 060 is designed specifically for the units contained in this i...

Страница 6: ...d be sound isolated by using the appropriate hangers or strapping When field supplied lines are used be sure to insulate the suction line only ELECTRIC HEATERS AND OPERATING CONTROLS The low voltage t...

Страница 7: ...orator coil electric heat and outdoor unit Speed tap adjustments are made at the motor terminal block See Figure 11 Airflow data is shown in Tables 6 and 11 Higher efficiencies will be obtained if the...

Страница 8: ...08 230 4 4 3 8 3 0 2 7 7 6 7 6 Locked Rotor 208 230 11 9 10 3 4 8 4 1 NA NA Filter1 Type DISPOSABLE OR PERMANENT Size 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1 Permanent Type Kit 1PF0602BK 1PF06...

Страница 9: ...5 0 042 2HK 6500506B 0 5 Low 3 8 5 0 13 0 17 1 3 8 5 0 3 8 5 0 3 8 5 0 2HK 6500806B Low 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B Low 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501...

Страница 10: ...13 8 110 125 2 1 2HK16502506B 104 2 124 3 139 9 125 150 1 1 0 060 2HK 6500506B 20 8 32 8 35 6 35 40 8 8 2HK16500806B 31 3 42 9 48 3 45 50 8 8 2HK16501006B 41 7 55 3 61 6 60 70 6 4 2HK16501506B 62 5 78...

Страница 11: ...6501525B 0 5 Med Low 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 060 2HK06501025B 0 5 Med 7 5 10 0 25 6 34 1 3 8 5 0 7 5 5 0 7 5 10 0 2HK06501525B 0 5 Med 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3...

Страница 12: ...1 575 1 500 1 420 1 350 1 273 1 192 1 102 996 871 Med 1 460 1 395 1 330 1 260 1 190 1 125 1 052 960 842 695 Low 1 250 1 200 1 155 1 100 1 050 1 001 931 851 751 631 F4FP045H06T High 1 575 1 535 1 475...

Страница 13: ...T High 1400 1418 1350 1278 1215 1145 1073 991 897 784 Med 1314 1266 1197 1135 1071 1012 947 864 758 625 Low 1125 1080 1040 990 945 901 838 766 676 568 F4FP045H06T High 1418 1382 1328 1251 1179 1120 10...

Страница 14: ...trol Wiring Typical A C Cooling only Applications Y Y G G W1 O C HUM X Y1 Y2 CFM selection board only on F4FV model 1 Air Handler Control Wiring Typical A C with Electric Heat Applications THERMOSTAT...

Страница 15: ...ced it should be washed with Calgon CalClean mix one part CalClean to ten parts water or other non acidic cleaners Allow solution to remain on coil for 30 minutes before rinsing with clean water Solut...

Страница 16: ...nge without notice Printed in U S A 404912 UIM A 0508 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 292043 UIM B 0707 Johnson Controls Unitary Products 5005 York Drive Norman O...

Отзывы: