404912-UIM-A-0508
10
Johnson Controls Unitary Products
*
May be 0 (no breaker) or 1 (with breaker).
TABLE 7:
Electrical Data - (For
Single Source
Power Supply) - Copper Wire 1 Ø - 208/230-1-60
1
Models F*FP
Heater*
Model
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
2
Amps/Type
75
°
C Wire Size - AWG
208V
240V
208V
240V
208V
240V
024
2HK*6500506B
20.8
24.7
27.7
25
30
10
10
2HK*6500806B
31.3
35.5
40.7
40
45
8
8
2HK*6501006B
41.7
46.9
53.7
50
60
8
6
030
2HK*6500506B
20.8
25.8
28.7
30
30
10
10
2HK*6500806B
31.3
36.7
41.7
40
45
8
8
2HK*6501006B
41.7
48.1
54.7
50
60
8
6
2HK16501506B
62.5
70.9
80.8
80
90
4
3
036
2HK*6500506B
20.8
26.8
29.5
30
30
10
10
2HK*6500806B
31.3
37.7
42.6
40
45
8
8
2HK*6501006B
41.7
49.1
55.6
50
60
8
6
2HK16501506B
62.5
71.9
81.6
80
90
4
3
2HK16501906B
3
73.3
83.3
95.2
90
100
3
3
040
2HK*6500506B
20.8
25.8
28.7
30
30
10
10
2HK*6500806B
31.3
36.7
41.7
40
45
8
8
2HK*6501006B
41.7
48.1
54.7
50
60
8
6
2HK16501506B
62.5
70.9
80.8
80
90
4
3
042
2HK*6500506B
20.8
28.1
30.5
30
35
10
8
2HK*6500806B
31.3
38.9
43.6
40
45
8
8
2HK*6501006B
41.7
50.3
56.6
60
60
6
6
2HK16501506B
62.5
73.2
82.6
80
90
4
3
045
2HK*6500506B
20.8
26.6
29.3
30
30
10
10
2HK*6500806B
31.3
37.4
42.3
40
45
8
8
2HK*6501006B
41.7
48.8
55.3
50
60
8
6
2HK16501506B
62.5
71.7
81.4
80
90
4
3
048
2HK*6500506B
20.8
32.8
35.6
35
40
8
8
2HK16500806B
31.3
43.0
48.4
45
50
8
8
2HK16501006B
41.7
55.3
61.5
60
70
6
4
2HK16501506B
62.5
77.3
87.8
80
90
4
3
2HK16502006B
83.3
101.0
113.8
110
125
2
1
2HK16502506B
104.2
124.3
139.9
125
150
1
1/0
060
2HK*6500506B
20.8
32.8
35.6
35
40
8
8
2HK16500806B
31.3
42.9
48.3
45
50
8
8
2HK16501006B
41.7
55.3
61.6
60
70
6
4
2HK16501506B
62.5
78.5
87.8
80
90
4
3
2HK16502006B
83.3
101.0
113.8
110
125
2
1
2HK16502506B
104.2
122.2
139.5
125
150
1
1/0
1. Heat amps shown at 240V represents maximum heater rating.
2. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
3. 2HK16501906B only applies to F4FP036 model.
TABLE 8:
Electrical Data - (For
Multi-Source
Power Supply) - Copper Wire 1 Ø - 208/230-1-60
1
Models F*FP
Heater
Model
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75
°
C Wire Size - AWG
Circuit
Circuit
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/240
208/240
208/240
208/240
208/240
208/240
208/240
208/240
208/240
030
2HK16501506B
25.8/28.7 45.1/52.1
—
30/30
50/60
—
10/10
8/6
—
036
2HK16501506B
26.8/29.5 45.1/52.1
—
30/30
50/60
—
10/10
8/6
—
2HK16501906B
2
38.3/42.6 45.7/52.6
—
40/45
50/60
—
8/8
8/6
—
040
2HK16501506B
25.8/28.7 45.1/52.1
—
30/30
50/60
—
10/10
8/6
—
042
2HK16501506B
28.1/30.5 45.1/52.1
—
30/35
50/60
—
10/8
8/6
—
045
2HK16501506B
26.6/29.3 45.1/52.1
—
30/30
50/60
—
10/10
8/6
—
048
2HK16501506B
32.8/35.6 45.1/52.1
—
35/40
50/60
—
8/8
8/6
—
2HK16502006B
55.3/61.6 45.1/52.1
—
60/70
50/60
—
6/4
8/6
—
2HK16502506B
32.8/35.6 45.1/52.1 45.1/52.1
35/40
50/60
50/60
8/8
8/6
8/6
060
2HK16501506B
32.8/35.6 45.1/52.1
—
35/40
50/60
—
8/8
8/6
—
2HK16502006B
55.3/61.6 45.1/52.1
—
60/70
50/60
—
6/4
8/6
—
2HK16502506B
33.8/35.6 45.1/52.1 45.1/52.1
35/40
50/60
50/60
8/8
8/6
8/6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
2. 2HK16501906B only applies to F4FP036 model.