background image

035-14520-001 Rev.  B (0803)

Unitary Products Group

3

LOCATION

Location is usually predetermined. Check with owner's or
dealer's installation plans. If location has not been decided,
consider the following in choosing a suitable location:

1.

Select a location with adequate structural support, space 
for service access, clearance for air return and supply 
duct connections.

2.

Use hanging brackets to wall mount unit as shown 
below.

3.

Normal operating sound levels may be objectionable if 
the air handler is placed directly over some rooms such 
as bedrooms, study, etc.

4.

Precautions should be taken to locate the unit and duct-
work so that supply air does not short circuit to the return 
air.

5.

Select a location that will permit installation of a trapped 
condensate line to an open drain.

6.

When an evaporator coil is installed in an attic or above a 
finished ceiling, an auxiliary drain pan should be pro-
vided under the coil as is specified by most local building 
codes.

The coil is provided with a secondary drain. It should be
trapped and piped to a location that will give the occu-
pant a visual warning that the primary drain is clogged. If
the secondary drain is not used it must be capped.

7.

Proper electrical supply must be available.

8.

Clearances must also be taken into consideration, and 
provided for as follows:

a.

Refrigerant piping and connections are located in
the front.

b.

Maintenance and servicing through the front or
access side of unit with both sides and rear of unit
having zero inch clearance.

c.

Condensate drain lines are connected in the front
(clear of filter).

d.

Filter removal.

e.

When no electric heat is used, the unit as well as all
duct work and plenum are designed for zero clear-
ance to combustible materials.

If Electric Heat is used, a minimum clearance of one
inch must be maintained on all sides of the supply
air duct and/or plenum continuously for up to 3 feet.
See Figure 2.

 FIGURE 2 : 

Plenum Clearances

MINIMUM CLEARANCE

OF 1” ALL SIDES

FLEXIBLE

DUCT COLLAR

3’

 FIGURE 3 : 

Typical Installation

POWER WIRING

TO MAIN

POWER SOURCE

SUPPLY

AIR

POWER WIRING

CONTROL

WIRING

THERMOSTAT

FILTER

ACCESS

LOUVERED

TO

CONDENSATE

DRAIN

REFRIGERANT

LINES

ELECTRIC HOT WATER HEATER

(Must comply with water heater installation instructions)

Содержание F2FC018

Страница 1: ...S GENERAL INFORMATION 2 INSPECTION 2 REFERENCE 2 LIMITATIONS 2 LOCATION 3 HORIZONTAL DRAIN PAN INSTALLATION CONVERSION 4 DIMENSIONS DUCT CONNECTORS 5 AIR FILTERS 6 SUSPENSION KITS 6 COIL METERING DEVI...

Страница 2: ...butor for more information Also check to be sure all accessories such as heater kits or suspension kits are available Installation of these accesso ries or field conversion of the unit should be accom...

Страница 3: ...trapped and piped to a location that will give the occu pant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 7 Proper electrical supply must be...

Страница 4: ...fe if not previously cut out 8 Re position and replace access panels DO NOT TRY TO KNOCK OUT Models F 2 3 FP045 048 060 have a coil baffle and support bracket factory installed for right hand hori zon...

Страница 5: ...s unit is not designed for non ducted freeblow applications Size outlet plenum or transition to discharge opening sizes shown in Figure 5 Duct work should be fabricated and installed in accordance wit...

Страница 6: ...is a valid system match for the AC or HP unit installed The TXV is fully brazed into the coil assembly of this Air Han dler unit at the factory The temperature sensing bulb will need to be attached t...

Страница 7: ...orifice with a small diameter wire or paper clip 2 Remove the new orifice from the packet and verify that it is the correct number required Install this orifice with the rounded end toward the coil a...

Страница 8: ...igure 10 LOW VOLTAGE CONTROL CONNECTION The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models However if the unit is connected to a 208 vo...

Страница 9: ...OWER SUPPLY 3 GND LUG POWER SUPPLY GND LUG POWER WIRING 208 230 1 60 NOTE USE ONLY COPPER CONDUCTORS FIGURE 12 Control Board FIGURE 13 Blower Speed Connections R Y G W2 W1 O C 2 4 V A C BREAK TAB FOR...

Страница 10: ...085 1100 Voltage 208 230 Amps Full Load 208 230 2 5 2 2 4 4 3 8 3 0 2 7 3 4 3 3 50 Hz 2 4 4 5 4 4 50 Hz 5 7 Locked Rotor 208 230 6 2 5 5 11 9 10 3 4 8 4 1 4 6 4 0 8 4 7 3 Filter1 Type DISPOSABLE OR PE...

Страница 11: ...0 2HK 6500806B LO 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 042 N H 06 2HK 6...

Страница 12: ...95 2 90 100 3 3 040H06 2HK 6500506B 20 8 25 8 28 7 30 30 10 10 2HK 6500806B 31 3 36 7 41 7 40 45 8 8 2HK 6501006B 41 7 48 1 54 7 50 60 8 6 2HK16501506B 62 5 70 9 80 8 80 90 4 3 042 N H 06 2HK 6500506...

Страница 13: ...5 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 030 N H 06 2HK06501025B 0 5 LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK06501525B 0 5 HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 036 N H 06 2HK06501025...

Страница 14: ...25 0 71 7 85 3 4 2 5 0 12 6 15 0 21 0 25 0 F2RP060N93 2HK 6500506B 0 5 LO 4 2 5 0 14 3 17 1 4 2 5 0 4 2 5 0 4 2 5 0 2HK 6500806B LO 6 3 7 5 21 5 25 6 4 2 5 0 6 3 7 5 6 3 7 5 2HK 6501006B LO 8 4 10 0...

Страница 15: ...E PHASE HEATERS Model Heater Model Min CFM Max Static Total Heat1 KW Staging KW MBH W1 Only W2 Only W1 W2 Static Tap 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V F2RP024N93 2HK06501025B 0 5 LO 8...

Страница 16: ...gh 1575 1535 1475 1390 1310 1418 1382 1328 1251 1179 Med high 1375 1315 1255 1185 1110 1238 1184 1130 1067 999 Med low 1210 1160 1110 1050 980 1089 1044 999 945 882 Low 1035 990 940 890 825 932 891 84...

Страница 17: ...64 Med 2125 3613 2020 3434 1910 3247 1805 3069 1705 2899 Low 1655 2814 1605 2729 1550 2635 1500 2550 1450 2465 MODEL Blower Motor Speed 220 Volt 50 HZ CFM or M3 H External Static Pressure IWG or PA 0...

Страница 18: ...T PUMP FIELD INSTALLED JUMPER TERMINAL NOT AVAILABLE ON ALL THERMOSTATS FAN COIL UNIT R Y G W2 W1 O C O R Y G T E W O X R B Y W NOTE TO CHANGE HEAT QUANTITY DURING DEFROST REVERSE CONNECTIONS AT W1 W2...

Страница 19: ...s to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Soluti...

Страница 20: ...without notice Printed in U S A 035 14520 001 Rev B 0803 Copyright by York International Corp 2003 All rights reserved Supersedes 035 14520 001 Rev A 0902 Unitary 5005 Norman Products York OK Group D...

Отзывы: