DRAIN CONNECTIONS

All drain lines should be trapped a minimum of three inches,
should be pitched away from unit drain pan and should be no
smaller than the coil drain connection.

Route the drain line so that it does not interfere with accessi-
bility to the coil, air handling system or filter and will not be
exposed to freezing temperatures. See Figures 2, 3 and 4.

NOTE: 

When the coil is installed in an attic or above a fin-

ished ceiling, an auxiliary drain pan should be provided under
the coil as is specified by most local building codes.

Coils should be installed level or pitched slightly toward the
drain end. Suggested pitch should not exceed 1/4 inch per
foot of coil.

The coil is provided with a secondary drain that should be
trapped and piped to a location that will give the occupant a
visual warning that the primary drain is clogged. If the sec-
ondary drain is not used it must be capped.

The drain pan connections are designed to ASTM Standard D
2466 Schedule 40. Use 3/4" PVC or steel threaded pipe.
Since the drains are not subject to any pressure it is not nec-
essary to use Schedule 40 pipe for drain lines.

It is recommended that all drain connections be sealed with
teflon tape or equivalent.

MAINTENANCE

Filters must be cleaned or replaced when they become dirty.
Inspect at least once per month. The frequency of cleaning
depends upon the hours of operation and the local atmo-
spheric conditions. Clean filters keep unit efficiency high.

COIL CLEANING

If the coil needs to be cleaned or replaced, it should be
washed with Calgon coilclean (mix one part Coilclean to
seven parts water). Allow solution to remain on coil for 30
minutes before rinsing with clean water. Solution should not
be permitted to come in contact with painted surfaces.

LUBRICATION

The bearings of the blower motor are permanently lubricated.

CONDENSATE DRAINS

During the cooling season check the condensate drain lines
to be sure that condensate is flowing from the primary drain
but not from the secondary drain. If condensate ever flows
from the secondary drain the unit should be promptly shut off
and the condensate pan and drains cleaned to insure a free
flowing primary drain.

TROUBLESHOOTING GUIDE

Threaded drain connection should be hand-tight-
ened, plus no more than 1/16 turn.

Horizontal drain cutout in the center access panel
should be removed by using a utility knife. DO NOT
TRY TO KNOCK OUT.

PROBLEM

POSSIBLE CAUSE

Blower Runs all of the time

1. No heat units do not have 6-pin connector installed.
2. Limit open or not connected.
3. Variable speed break-out tab broken out.
4. Blower OFF delay (approx. 1 min).
5. Thermostat fan switch in “ON” position.

Blown Fuse

1. Low voltage short to C or ground from R, Y, G, W, or O.

No 24V

1. 4-pin connector loose.
2. Loose wire from control to transformer (24V and 230V).
3. Blown fuse on control board.

No 2nd stage heat

1. Check 6-pin connector and connections to panel mount relays.
2. Verify that both W

1

 & W

2

 are connected at the terminal strip.

No Heat or Limited Heating

1. Check filter.
2. Closed registers.
3. Restricted airflow (supply registers or return registers)
4. Check blower motor operation.
5. If the safety limit opens 4 times, the control will not permit the heating element to operate for 1 hour.

Содержание F2FC018

Страница 1: ...S GENERAL INFORMATION 2 INSPECTION 2 REFERENCE 2 LIMITATIONS 2 LOCATION 3 HORIZONTAL DRAIN PAN INSTALLATION CONVERSION 4 DIMENSIONS DUCT CONNECTORS 5 AIR FILTERS 6 SUSPENSION KITS 6 COIL METERING DEVI...

Страница 2: ...butor for more information Also check to be sure all accessories such as heater kits or suspension kits are available Installation of these accesso ries or field conversion of the unit should be accom...

Страница 3: ...trapped and piped to a location that will give the occu pant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 7 Proper electrical supply must be...

Страница 4: ...fe if not previously cut out 8 Re position and replace access panels DO NOT TRY TO KNOCK OUT Models F 2 3 FP045 048 060 have a coil baffle and support bracket factory installed for right hand hori zon...

Страница 5: ...s unit is not designed for non ducted freeblow applications Size outlet plenum or transition to discharge opening sizes shown in Figure 5 Duct work should be fabricated and installed in accordance wit...

Страница 6: ...is a valid system match for the AC or HP unit installed The TXV is fully brazed into the coil assembly of this Air Han dler unit at the factory The temperature sensing bulb will need to be attached t...

Страница 7: ...orifice with a small diameter wire or paper clip 2 Remove the new orifice from the packet and verify that it is the correct number required Install this orifice with the rounded end toward the coil a...

Страница 8: ...igure 10 LOW VOLTAGE CONTROL CONNECTION The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models However if the unit is connected to a 208 vo...

Страница 9: ...OWER SUPPLY 3 GND LUG POWER SUPPLY GND LUG POWER WIRING 208 230 1 60 NOTE USE ONLY COPPER CONDUCTORS FIGURE 12 Control Board FIGURE 13 Blower Speed Connections R Y G W2 W1 O C 2 4 V A C BREAK TAB FOR...

Страница 10: ...085 1100 Voltage 208 230 Amps Full Load 208 230 2 5 2 2 4 4 3 8 3 0 2 7 3 4 3 3 50 Hz 2 4 4 5 4 4 50 Hz 5 7 Locked Rotor 208 230 6 2 5 5 11 9 10 3 4 8 4 1 4 6 4 0 8 4 7 3 Filter1 Type DISPOSABLE OR PE...

Страница 11: ...0 2HK 6500806B LO 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 042 N H 06 2HK 6...

Страница 12: ...95 2 90 100 3 3 040H06 2HK 6500506B 20 8 25 8 28 7 30 30 10 10 2HK 6500806B 31 3 36 7 41 7 40 45 8 8 2HK 6501006B 41 7 48 1 54 7 50 60 8 6 2HK16501506B 62 5 70 9 80 8 80 90 4 3 042 N H 06 2HK 6500506...

Страница 13: ...5 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 030 N H 06 2HK06501025B 0 5 LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK06501525B 0 5 HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 036 N H 06 2HK06501025...

Страница 14: ...25 0 71 7 85 3 4 2 5 0 12 6 15 0 21 0 25 0 F2RP060N93 2HK 6500506B 0 5 LO 4 2 5 0 14 3 17 1 4 2 5 0 4 2 5 0 4 2 5 0 2HK 6500806B LO 6 3 7 5 21 5 25 6 4 2 5 0 6 3 7 5 6 3 7 5 2HK 6501006B LO 8 4 10 0...

Страница 15: ...E PHASE HEATERS Model Heater Model Min CFM Max Static Total Heat1 KW Staging KW MBH W1 Only W2 Only W1 W2 Static Tap 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V F2RP024N93 2HK06501025B 0 5 LO 8...

Страница 16: ...gh 1575 1535 1475 1390 1310 1418 1382 1328 1251 1179 Med high 1375 1315 1255 1185 1110 1238 1184 1130 1067 999 Med low 1210 1160 1110 1050 980 1089 1044 999 945 882 Low 1035 990 940 890 825 932 891 84...

Страница 17: ...64 Med 2125 3613 2020 3434 1910 3247 1805 3069 1705 2899 Low 1655 2814 1605 2729 1550 2635 1500 2550 1450 2465 MODEL Blower Motor Speed 220 Volt 50 HZ CFM or M3 H External Static Pressure IWG or PA 0...

Страница 18: ...T PUMP FIELD INSTALLED JUMPER TERMINAL NOT AVAILABLE ON ALL THERMOSTATS FAN COIL UNIT R Y G W2 W1 O C O R Y G T E W O X R B Y W NOTE TO CHANGE HEAT QUANTITY DURING DEFROST REVERSE CONNECTIONS AT W1 W2...

Страница 19: ...s to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Soluti...

Страница 20: ...without notice Printed in U S A 035 14520 001 Rev B 0803 Copyright by York International Corp 2003 All rights reserved Supersedes 035 14520 001 Rev A 0902 Unitary 5005 Norman Products York OK Group D...

Отзывы: