146
a.
Under AUTO mode, if T
amb
.
≥
T
preset
is detected, the unit will select to run under cooling mode, in which case implicit
preset temperature is 25
ć
; if T
amb
.
≤
T
preset
-2
ć
, the compressor will stop, the outdoor fan will stop with a time lag of 1
minute, and the indoor fan will run at preset speed; and if T
preset
–(-2
ć
)< T
amb
.< T
preset
, the unit will remain at its original
state.
b.
Under AUTO mode, if T
amb
.
≤
T
preset
+2
ć
is detected, the unit will select to run under heating mode, in which case
implicit preset temperature is 18
ć
; if T
amb
.
≥
T
preset
+5
ć
, the compressor will stop, the outdoor fan will stop with a time lag
of 1 minute, and the indoor fan will run under the mode of residue heat blowing; and if T
preset
+2
ć
< T
amb
.< T
preset
+5
ć
, the
unit will remain at its original state. The cooling-only unit will run under fan mode.
c.
Under AUTO mode, if 20
ć
< T
amb
.< 25
ć
, the unit will remain at its original state.
2.Protection
a.
In cooling operation, protection is the same as that under the cooling mode;
b.
In heating operation, protection is the same as that under the heating mode;
c.
When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will
remain unchanged for at least 6 minutes.
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
ķ
Overload protection
T
tube
: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat
exchanger under heating mode.
1) Cooling overload
a. If T
tube
≤
52
ć
, the unit will return to its original operation state.
b. If T
tube
≥
55
ć
, frequency rise is not allowed.
c. If T
tube
≥
58
ć
, the compressor will run at reduced frequency.
d. If T
tube
≥
62
ć
, the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a. If T
tube
≤
52
ć
, the unit will return to its original operation state.
b. If T
tube
≥
55
ć
, frequency rise is not allowed.
c. If T
tube
≥
58
ć
, the compressor will run at reduced frequency.
d. If T
tube
≥
62
ć
, the compressor will stop and the indoor fan will blow residue heat and then stop.
ĸ
Exhaust temperature protection of compressor
If exhaust temperature
≥
98
ć
, frequency is not allowed to rise.
If exhaust temperature
≥
103
ć
, the compressor will run at reduced frequency.
If exhaust temperature
≥
110
ć
, the compressor will stop.
If exhaust temperature
≤
90
ć
and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its
operation.
Ĺ
Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system
will stop.
ĺ
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the
compressor will resume its operation. If module protection occurs six times in succession, the compressor will not be started
again.
Ļ
Overload protection
If temperature sensed by the overload sensor is over 115
ć
, the compressor will stop and the outdoor fan will stop with a
time lag of 30 seconds. If temperature is below 95
ć
, the overload protection will be relieved.
ļ
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time
lag of 30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least
3 minutes, the compressor will resume its operation.
Ľ
Faults of temperature sensors
Operation
24
Содержание EVJC 12
Страница 2: ...74 74...
Страница 30: ...102...
Страница 32: ...104 www johnsoncontrols com...
Страница 34: ...106 by johnson controls 2...
Страница 35: ...107 by johnson controls 3 Fig 1 Fig 2 Fig 3 15 cm 15 cm 70 cm 15 cm 15 cm 200 cm 5 6 7 30 cm 50 cm 2 3 4 1 5...
Страница 46: ...118...
Страница 48: ...120 www johnsoncontrols com...
Страница 49: ...121 High Wall EVHC 09 to 12 DSAAAR SERVICE MANUAL SM EVHC D 09 12GB 05 10 EVHC 09 EVHC 12...
Страница 65: ...137 LULQJ LDJUDP Schematic Diagram Indoor Unit Schematic Diagram...
Страница 66: ...138 Schematic Diagram Outdoor Unit...
Страница 69: ...141 TOP VIEW Schematic Diagram BOTTOM VIEW 1 3 4 5 6 2 7 8 9 10 11 12 Outdoor Unit...
Страница 113: ...185 Exploded View Exploded View Indoor Unit...
Страница 114: ...186 Exploded View Outdoor Unit...
Страница 118: ...190 High Wall EVHC 18 to 24 DSAAAR SERVICE MANUAL SM EVHC D 18 24GB 05 10 EVHC 18 EVHC 24...
Страница 132: ...204 LPHQVLRQV Dimensions QGRRU 8QLW Tube exit Air inlet Right Left Ceiling W D H 02 18K 24K...
Страница 133: ...205 890 340 955 560 380 424 700 60cm 60cm 60cm 60cm LPHQVLRQV Outdoor Unit Bolt Nut Spanner...
Страница 140: ...212 TOP VIEW Schematic Diagram BOTTOM VIEW 1 2 3 4 5 6 7 8 9 7 8 9 10 11 12 13 1 2 3 4 5 6 10...
Страница 142: ...214 Schematic Diagram Key testing spot bottom...
Страница 197: ...269 Exploded View Exploded View Indoor Unit 78 Model EVKC 18 DS...
Страница 198: ...270 Exploded View Model EVKC 24 DS 79...
Страница 199: ...271 Exploded View Outdoor Unit 80...