*** SERVICE ***
AMS#1 Controller
Measured Air
ß
ow
at balance =9000cfm
*** SERVICE ***
Application
Revision # = 1.63
This display shows the entry made by the Air Balancer
if a man u al air balance is done.
Line 2 AMS #1 Controller
Line 3 Measured Air
ß
ow
Line 4 at balance= XXXXX cfm
The Line 4 value is entered as a part of the air
ß
ow
balancer’s calibration of the Air
ß
ow Mea sure ment Sta-
tion #1. A default value will be shown whether or not
this function is used. Editing the value requires the en try
of a pass word of the ap pro pri ate level. This func tion
is described under Units Se quence and Operation and
PA RAM E TER DESCRIPTION AND OP TIONS.
This display indicates the software revision
Line 2 Application
Line 3 Revision #= X.X
Line 4 Blank
*** SERVICE ***
Economizer Tunins
Prop Band = 40°F
Intes Time = 45 sec
Line 2 Economizer Tunis
Line 3 Prop Band = XX°F
Line 4 Intes Time = XX sec