YORK INTERNATIONAL
86
FORM 100.50-NOM1 (604)
Menu Navigation and Display Description
*** UNIT STATUS ***
General Unit Status
Unit Type = VAV
Status = NORMAL
*** UNIT STATUS ***
Current Unit Mode
Unoccupied Standby
*** UNIT STATUS ***
Date = 25-Feb-2000
Time = 12:28:05a
Day = WED
*** UNIT STATUS ***
Unit Controlled By
Thermostat
FUNCTION KEY FIRST LINE TEXT
UNIT STATUS
*** UNIT STATUS ***
OPERATION DATA
** OPERATION DATA **
SETPOINTS
*** SETPOINTS ***
UNIT SETUP
*** UNIT SETUP ***
CONFIGURATION
** CONFIGURATION **
SERVICE
*** SERVICE ***
HISTORY
*** HISTORY ***
Starting with the
Þ
rst display item, the Unit Status dis-
play items are shown below. The values in parentheses
are the possible displays.
Line 2 General Unit Status
Line 3
Unit Type = VAV (CV, VAV, Flexsys)
Line 4 Status = NORMAL (TROUBLE, ALARM)
Unit Type will be determined from the “Unit Type”
con
Þ
g u ra tion setting un der the Con
Þ
guration menu and
can be programmed for either VAV (variable air volume
unit), CV (constant volume unit), or Flexsys.
Status is determined by:
• NORMAL - no faults have been detected
• TROUBLE - a fault that does not cause unit shut-
down has been
detected
• ALARM - a fault that causes the unit to be shut
down has been detected
Refer to the section on Service and Troubleshooting for
fault, alarm and trou ble description.
Line 2 Date = dd-mon-year
Line 3 Time = hh:mm:ss a (p)
Line 4 Day = DDD (day abbreviation)
The Date and Time are displayed and, if required,
changed in this display by pressing Enter/Change and
using cursor control and the Enter button to up date the
Date and Time parameters. A Level 1 password is re-
quired to change these parameters.
Line 2 Current Unit Mode
Line 3 (Current unit operating mode)
Line 4 (Blank)
Line 3 displays the one of the following operating
modes:
Occupied Standby
Occupied Cooling Warm-up
Occupied Heating Sys. Start Delay
Unoccupied Standby Preoccupancy Purge
Unoccupied Cooling Smoke Purge
Unoccupied Heating Emergency Shut Down
Manual Override Fault Shutdown
Line 2 Unit Controlled By
Line 3
(Determined by inputs and Setup settings)
Line 4
(Blank)
Line 3 displays one of the following four space tem-
per a ture control sources or method:
Thermostat
Zone Sensor
BAS Network
Stand Alone Control