GENERAL
This instruction covers the installation of the following outdoor
units: E1FD018A(S)06, E9FD018S06, E1FD024A(S)06,
E 9 F D0 24 S 06 , E 1F D0 30 A (S )06 , E 9F D 03 0S 06 ,
E 1F D 03 6A (S )06 , E9 FD0 36S 06, E 1FD 036 S(25 ,4 6),
E1FD042A(S)06, E1FD048A(S)06 E1FD048S(25, 46),
E1FD060A(S)06, E1FD060S06(25, 46).
The outdoor units are designed to be connected to a matching
indoor coil with either quick or sweat connect lines. Quick
connect units are factory charged with refrigerant for a match-
ing indoor coil and factory charged line sets are available in
various lengths. Sweat connect units are factory charged with
refrigerant for a matching indoor coil plus 15 feet of field
supplied lines.
Matching indoor coils are available with a thermal expansion
valve or an orifice liquid feed (YORKMATE flow control device)
sized for the most common usage. The orifice size and/or
refrigerant charge may need to be changed for some indoor-
outdoor unit combinations, elevation differences or total line
lengths. Refer to Application Data covering “General Piping
Recommendations and Refrigerant Line Length” (Form
690.01-AD1V).
THIS UNIT IS NOT EQUIPPED WITH A FILTER DRIER. A
SOLID CORE BI-FLOW DIRECTIONAL FILTER IS RE-
QUIRED FOR INSTALLATION AND ANY TIME THE REFRIG-
ERANT CIRCUIT IS OPENED.
INSPECTION
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier’s delivery receipt. A
separate request for inspection by the carrier’s agent should
be made in writing. See Local Distributor for more information.
REFERENCE
Use this instruction in conjunction with the instructions for the
appropriate indoor unit, air moving system and accessories.
Installer should pay particular attention to the words:
NOTE,
CAUTION and WARNING.
NOTES are intended to clarify or make the installation easier.
CAUTIONS identifies procedure which, if not followed carefully,
could result in personal injury, property damage or product
damage.
WARNINGS are given to alert the installer that severe personal
injury, death or equipment damage may result if installation
procedures are not handled properly.
NOMENCLATURE
LIMITATIONS
The unit should be installed in accordance with all national and
local safety codes.
Limitations for the indoor unit, coil and appropriate accessories
must also be observed.
The outdoor unit must not be installed with any ductwork in the
air stream. The outdoor fan is the propeller type and is not
designed to operate against any additional external static pres-
sure.
OUTDOOR
SPLIT-SYSTEM HEAT PUMPS
Supersedes:
Supersedes: 515.26-N5Y (995)
MODELS E1(9)FD018, 024, 030 and 036
E1FD042, 048 and 060
(See Detail Listing Below)
515.26-N5Y (296)
035- 13682
AIR TEMPERATURE
°
DB
ON OUTDOOR COIL
AIR TEMPERATURE
ON INDOOR COIL
Min.
Max.
Min.
Max.
Cool
Heat
Cool
Heat
°
WB
Cool
°
DB
Heat
°
WB
Cool
°
DB
Heat
50
-10*
115
75
57
50**
72
80
* If ambient will be below this, Accessory Kit 2LT06700224 must be installed to
cutoff heat pump.
** Operation below this temperature is permissible for a short period of time,
during morning warm-up.
TABLE 1 - APPLICATION LIMITATIONS
Voltage Code
Refrigerant Line Connections
Nominal Cooling Capacity
Product Category
Product Generation
Product Identifier
E = Outdoor Split System Heat Pump
1 = Design Level
9 = Canada
FDs = 10 SEER Heat Pump
018 = 1.5 Tons
024 = 2Tons
030 = 2.5Tons
036 = 3 Tons
042 = 3.5 Tons
048 = 4 Tons
060 = 5 Tons
A = Quick-Connect Fittings
S = Sweat Fittings
06 = 208/230-1-60
25 =208/230-3-60
46 = 460-3-60
E
1
FD 036
A
06
®
INSTALLATION INSTRUCTION