PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.

2. Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.

3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for 

evap adder for line set.

5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.

G1NA036S17L

63

63 + 15

73 + 12

701 + 15

702 + 12

G1NA048S21D

78

73 + 12

78 + 0

87 + 0

702 + 12

702 + 0

703 + 0

G1NA048S24P

63

73 + 13

78 + 2

87 + 1

702 + 13

702 + 2

703 + 1

G1NA060S24T

78

703  +  0

G1NF024SOF

63

G1NF036SOF

67

59 + 12

63 + 0

73 + 7

701 + 12

701 + 0

702 + 7

G1NF048SOF

78

78 + 21

87 + 6

702 + 21

703 + 6

G1NF060SOF

87

87 + 18

703 + 18

F(2,3)RP024N,H06(T)

61

53 + 4

59 + 4

701 + 4

701 + 4

F(2,3)RP030N06(T)

65

59 + 6

63 + 4

701 + 6

701 + 4

F(2,3)RP036N06(T)

75

63 + 4

73 + 8

701 + 4

702 + 8

F(2,3)RP042N06(T)

78

73 + 13

78 + 0

702 + 13

702 + 0

F(2,3)FP048N06(T)

84

73 + 16

78 + 10

87 + 11

702 + 16

702 + 10

703 + 11

F(2,3)FP060N06(T)

90

87 + 15

703 + 15

703

5

 + 5

F(2,3)FV060N06(T)

90

87 + 15

703 + 15

703 + 5

MDD30MSD

90

53 + 6

59 + 6

63 + 4

701 + 6

107 + 6

701 + 4

MDD48DSD

90

73 + 12

81 + 0

87 + 0

702 + 12

702 + 0

703 + 0

FOOTNOTES:

1. These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.

2. A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).

3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.

4. These orifices are factory mounted in the flow control device of each indoor coil.  A TXV is factory mounted if the model number has a (T) suffix.

5. This TXV is factory mounted in indoor coils, if the model number has a (T) suffix.

Additional R-22 Charge / Orifice Size for Various Matched Systems (Continued)- 1 Phase

Outdoor Unit

DRCS0181BE DRCS0241BE DRCS0301BE DRCS0361BE DRCS0421BE DRCS0481BE DRCS0601CE

Unit Orifice (s)

1

53

59

63

73

78

87

Factory R-22 Charge, lbs-oz.

4 - 9

4 - 7

5 - 8

5 - 3

6 - 13

7 - 7

8 - 15

Indoor Coil

5

Coil Orifice

4

Orifice or TXV Kit 

2

 - Additional Charge, Oz.

3

Содержание DRCS0181BE

Страница 1: ...high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur A liquid line filter drier further protects the compressor DURABLE FINISH The cabinet is made of pre painted steel The pre treated galvanized steel provides a better paint to steel bond which...

Страница 2: ...036S HABC W048S HABC W060S Unit Supply Voltage 208 230 3 60 460 3 60 Normal Voltage Range 1 187 to 252 432 to 504 Minimum Circuit Ampacity 13 3 18 9 22 9 7 6 9 6 12 0 Max Overcurrent Device Amps 2 20 30 40 15 15 20 Compressor Type Inertia Inertia Scroll Inertia Inertia Scroll Compressor Amps Rated Load 9 6 14 1 17 3 5 4 7 0 9 0 Locked Rotor 78 0 130 0 123 0 40 0 64 0 62 0 Crankcase Heater No No No...

Страница 3: ...60 S H 24 90 87 15 703 15 703 5 G2FD061H24 90 87 19 703 19 703 11 G1HA024H14 61 053 03 059 03 G1HA024H14 T TXV 701 03 03 G1HA036H14 75 59 12 63 11 73 08 G1HA036H14 T TXV 702 11 08 G1HA036H17 78 63 14 73 12 G1HA036H17 T TXV 702 14 12 G1HA048H21 84 73 09 78 07 87 08 G1HA048H21 T TXV 703 09 07 08 G1HA060H24 90 87 15 G1HA060H24 T TXV 703 87 15 703 5 G1HD024 59 53 5 59 4 701 5 701 4 G1HD036 69 59 13 63...

Страница 4: ...2 3 RP030N06 T 65 59 6 63 4 701 6 701 4 F 2 3 RP036N06 T 75 63 4 73 8 701 4 702 8 F 2 3 RP042N06 T 78 73 13 78 0 702 13 702 0 F 2 3 FP048N06 T 84 73 16 78 10 87 11 702 16 702 10 703 11 F 2 3 FP060N06 T 90 87 15 703 15 7035 5 F 2 3 FV060N06 T 90 87 15 703 15 703 5 MDD30MSD 90 53 6 59 6 63 4 701 6 107 6 701 4 MDD48DSD 90 73 12 81 0 87 0 702 12 702 0 703 0 FOOTNOTES 1 These orifices are factory mount...

Страница 5: ... HABC T W060S Unit Orifice s 1 Factory R 22 Charge lbs oz 6 2 7 10 9 3 Indoor Coil Coil Orifice TVX Kit2 Additional Charge Oz3 G2FD035 S H 14 65 702 0 G2FD036 S H 17 21 75 702 3 G2FD042 S H 21 78 702 0 G2FD046 S H 17 78 702 9 703 0 G2FD048 S H 21 24 84 702 17 703 9 G2FD060 S H 24 90 703 0 703 20 G2FD061H24 90 703 6 703 25 G1FA G1UA036S14 73 702 1 G1FA G1UA036S17 21 73 702 0 G1FA G1UA048S17 84 703 ...

Страница 6: ...5 18 21 G2FD048 S H 21 1400 43 0 30 6 13 00 11 55 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 30 6 12 80 11 40 DRCS0481BE N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 34 9 12 80 12 80 11 40 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1560 48 5 36 0 13 25 13 25 11 75 N1VSD20 10 15 18 30 24 G2FD061H24 1560 49 0 36 4 13 30 13 30 11 90 DRCS0601CE N1VSD20 10 15 18 30 24 G2FD060 S H 24 1780 56 0 42 3 12 10 1...

Страница 7: ...0 14 G1UA036S14 750 24 2 17 6 12 00 12 00 11 25 17 21 G1UA036S17 21 750 24 0 17 3 12 00 12 00 11 10 14 17 G2FD024 S H 14 17 750 23 6 16 9 12 00 12 00 11 00 17 G2FD030 S H 17 750 24 0 17 3 12 00 12 00 11 10 14 G2FD035 S H 14 750 24 0 17 3 12 10 12 10 11 10 17 G2FD036 S H 17 750 24 6 17 8 12 15 12 15 11 35 19 MDD30MSD 750 24 0 17 2 12 00 12 00 11 15 DRCS0301BE 875 1125 14 G1FA030S14 1000 29 2 20 7 1...

Страница 8: ... 14 G1FA036S14 1235 33 4 25 0 11 50 10 65 17 21 G1FA036S17 21 1235 33 0 24 4 11 50 10 55 21 G1FA048S21 1235 35 0 25 9 12 00 10 70 G1HD036 1235 33 4 24 7 11 80 10 70 G1HD048 1235 35 0 25 8 12 00 11 05 17 G1NA036S17L 1200 35 0 24 4 12 00 10 90 21 G1NA048S21D 1200 35 0 24 4 12 00 10 90 14 G1UA036S14 1200 33 4 25 0 11 50 10 65 17 21 G1UA036S17 21 1235 33 0 24 4 11 50 10 55 21 G1UA048S21 1235 35 0 25 9...

Страница 9: ...5 33 7 12 00 11 00 21 24 G1FA060S21 24 1600 47 0 34 8 12 50 11 45 G1HD048 1600 45 0 33 3 12 00 11 15 G1HD060 1600 46 5 36 1 12 40 11 40 21 G1NA048S21D 1400 46 0 34 0 12 00 11 20 17 G1UA048S17 1500 44 5 32 9 12 00 10 50 21 G1UA048S21 1600 45 5 33 7 12 00 11 00 21 24 G1UA060S21 24 1600 47 0 34 8 12 50 11 45 17 G2FD046 S H 17 1500 44 5 32 9 12 00 10 50 21 24 G2FD048 S H 21 24 1600 45 5 33 7 12 20 11 ...

Страница 10: ...1 15 G8V 16UHB F L C8V B16UH G2FD036 S H 17 17 1200 34 4 24 2 12 25 11 40 G8V 20UHC F L C8V C20UH G1FA036S21 21 1200 33 6 23 6 12 00 11 30 G8V 20UHC F L C8V C20UH G2FD036 S H 21 21 1200 34 8 24 4 13 00 11 60 G9V 12DHB G2FD036 S H 17 17 1130 34 4 24 4 12 00 11 15 G9V 12UPB G1FA036S17 17 1220 33 2 23 2 11 50 10 80 G9V 12UPB G2FD036 S H 17 17 1200 34 0 23 8 12 00 11 05 G9V 16UPC G1FA036S21 21 1200 33...

Страница 11: ... G1UA060S21 T 21 1640 56 0 41 8 12 10 10 10 G9V 20UPC G2FD060 S H 24 T 24 1640 56 0 41 8 12 10 10 10 G9V 20UPC G2FD061H24 24 1640 56 5 42 0 12 10 10 25 G9V 20UPD G1FA G1UA060S24 T 24 1620 56 0 41 6 12 10 10 30 G9V 20UPD G2FD060 S H 24 T 24 1620 56 0 41 6 12 10 10 30 G9V 20UPD G2FD061H24 24 1620 56 5 41 9 12 25 10 40 G9V 20DHC G2FD060 S H 24 T 24 1575 55 5 40 9 12 10 10 20 G9V 20DHC G2FD061H24 24 1...

Страница 12: ...tat Add sub base for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermostat 1H 1C auto manual changeover electronic programmable For the most current accessory information refer to the price book or consult factory SOUND POWER RATINGS Rated in accordance with ARI 270 95 Standards DIMENSIONS 1 Phase Unit Mod...

Страница 13: ...230 1 60 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM THERMOSTAT CONDENSING UNIT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE N...

Страница 14: ... 47 1 45 1 43 1 48 1 47 1 45 1 49 1 48 1 46 105 T C 18 1 16 3 14 2 18 7 17 1 15 0 19 4 17 8 15 8 S C 11 3 10 6 9 7 13 0 12 2 11 3 14 7 13 8 12 9 KW 1 58 1 55 1 52 1 59 1 57 2 53 1 61 1 58 3 54 115 T C 16 6 14 5 12 7 17 5 15 3 13 2 18 3 16 1 13 8 S C 10 8 9 8 9 1 12 7 11 6 10 6 14 7 13 4 12 1 KW 1 69 1 65 1 61 1 71 1 67 3 62 1 73 1 69 5 62 125 T C 15 2 12 7 11 1 16 2 13 6 11 5 17 3 14 5 11 9 S C 10...

Страница 15: ... 98 2 09 2 04 2 00 115 T C 21 3 18 6 16 2 22 0 19 5 17 0 22 8 20 5 17 7 S C 14 0 12 9 12 0 16 3 15 3 14 2 18 6 17 8 16 4 KW 2 19 2 13 2 08 2 22 2 16 2 10 2 25 2 18 2 12 125 T C 19 8 16 4 14 2 20 7 17 6 14 9 21 8 19 0 15 4 S C 13 5 12 0 11 1 16 3 14 6 13 4 19 1 17 5 15 6 KW 2 34 2 25 2 20 2 37 2 30 2 22 2 41 2 32 2 24 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 10...

Страница 16: ...2 61 2 55 2 74 2 64 2 57 2 77 2 68 2 59 125 T C 24 0 20 4 17 0 26 7 21 7 16 8 29 4 23 2 16 7 S C 17 1 15 6 14 1 20 2 17 9 16 0 23 3 20 5 17 8 KW 2 88 2 76 2 70 2 94 2 79 2 70 3 00 2 84 2 69 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW F2RP F2FP030 1 01 1 08 0 99 F2RP F2FP036 1 03 1 10 1 01 F2RC F2FC030 0 99 1 01 0 99 F2RC F2FC0...

Страница 17: ...2 9 S C 21 4 20 0 19 0 23 8 22 3 21 1 26 2 24 6 23 2 KW 3 36 3 29 3 19 3 38 3 31 3 23 3 39 3 33 3 26 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW F2RC F2FC036 1 02 1 04 1 00 F2RP F2FP036 1 02 1 03 1 00 F2RP F2FP042 1 02 1 04 1 02 F2FP048 1 04 1 06 1 02 N1VSB12 G2FD036 S H 17 1 02 1 03 0 96 N1VSB12 G2FD046 S H 17 1 05 1 08 0 97 ...

Страница 18: ...0 8 27 2 33 6 31 3 27 7 S C 23 7 22 5 20 7 24 5 23 6 21 9 25 4 24 6 23 0 KW 4 01 3 88 3 75 4 02 3 91 3 77 4 03 3 93 3 78 125 T C 31 0 27 6 23 5 31 1 28 1 24 1 31 3 28 5 24 4 S C 23 1 21 3 19 6 23 7 22 3 20 2 24 8 23 7 21 6 KW 4 26 4 10 3 94 4 28 4 12 3 95 4 30 4 15 3 97 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB1246 G2F...

Страница 19: ...5 38 1 44 2 42 0 38 9 S C 28 4 27 6 25 9 30 0 29 7 28 2 31 6 31 8 30 5 KW 3 39 3 38 3 36 3 39 3 38 3 36 3 40 3 39 3 37 115 T C 41 2 38 1 34 1 41 6 38 7 34 9 42 0 39 3 35 7 S C 27 8 26 7 24 8 29 8 28 9 27 0 31 8 31 0 29 2 KW 3 80 3 77 3 73 3 81 3 78 3 74 3 81 3 79 3 75 125 T C 38 7 35 3 30 9 39 3 35 9 31 8 39 9 36 5 32 6 S C 27 1 25 7 23 7 29 5 28 0 25 8 31 9 30 3 27 9 KW 4 21 4 16 4 11 4 22 4 18 4...

Страница 20: ... 1 S C 30 5 28 3 26 3 33 1 30 5 28 4 35 7 32 8 30 5 KW 4 28 4 15 4 02 4 32 4 17 4 05 4 35 4 19 4 08 125 T C 36 3 31 3 28 5 36 9 31 9 28 8 37 6 32 5 29 1 S C 29 2 26 8 24 8 31 8 28 9 26 8 34 4 31 0 28 8 KW 4 55 4 42 4 25 4 60 4 43 4 29 4 64 4 44 4 33 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW F2FP048 1 00 1 00 1 02 F2FP060 1 0...

Страница 21: ...42 5 39 3 36 2 S C 30 5 30 6 29 5 30 9 32 6 32 8 31 5 32 8 34 1 34 2 32 7 34 5 KW 4 67 4 45 4 25 4 03 4 72 4 49 4 30 4 09 4 74 7 53 4 34 4 18 115 T C 41 8 38 3 35 3 31 7 42 3 38 8 35 8 33 0 42 5 39 0 36 2 33 5 S C 29 3 29 5 28 2 29 6 31 6 31 4 30 1 31 5 33 0 32 9 31 5 32 0 KW 4 91 4 67 4 47 4 25 4 94 4 73 4 52 4 36 4 98 4 76 4 56 4 41 125 T C 38 0 35 0 32 3 29 1 38 6 35 4 32 7 31 0 38 8 35 5 33 2 ...

Страница 22: ... 7 50 4 53 7 57 9 S C 40 6 38 6 39 8 39 6 43 1 40 6 41 9 41 6 44 6 42 4 43 5 43 2 KW 7 5 8 1 8 6 9 3 7 5 8 1 8 6 9 2 7 4 8 1 8 5 9 1 115 T C 42 3 46 7 50 1 53 9 42 9 47 4 50 4 54 4 43 4 47 8 50 9 54 6 S C 39 4 37 5 38 8 38 2 41 8 39 7 40 6 40 4 43 3 41 2 42 6 42 1 KW 6 3 6 9 7 3 7 8 6 3 6 9 7 3 7 8 6 3 6 9 7 3 7 7 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 ...

Страница 23: ...3 1 42 6 41 6 KW 5 24 5 10 5 06 5 25 5 11 5 07 5 26 5 12 5 08 105 T C 58 1 54 6 50 0 58 9 55 7 51 3 59 7 56 8 52 7 S C 36 9 36 0 34 4 39 8 39 0 37 3 42 7 41 9 40 2 KW 5 86 5 72 5 63 5 87 5 74 5 64 5 88 5 77 5 66 115 T C 56 2 51 8 46 3 57 1 53 2 47 9 57 9 54 5 49 5 S C 36 2 34 9 32 9 39 3 38 1 35 9 42 3 41 2 38 8 KW 6 47 6 33 6 19 6 49 6 38 6 22 6 50 6 42 6 24 125 T C 54 3 49 0 42 6 55 2 50 6 44 5 ...

Страница 24: ...HING INDOOR COMPONENTS G1UA 1 2 CASED UPFLOW G1HD HORIZONTAL DUCT G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICATIONS N1AH OR N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F2RC F2FC OR F2RP F2FP F2FV FAN COIL UNITS UPFL...

Отзывы: