262259-YTG-B-0107

38

Unitary Products Group

bearings, internally protected against overload conditions and 
staged independently. 

REFRIGERANT COMPONENTS

Compressors:

a.

Shall be Scroll (25T only) compressors internally
protected with internal high-pressure relief and over
temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting. 

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.

b.

Evaporator and Condenser coils shall be of the 
direct expansion, draw-thru, design. 

Refrigerant Circuit and Refrigerant Safety Components shall 
include:

a.

Balance-port thermostatic expansion valve with
independent circuit feed system.

b.

Filter drier/strainer to eliminate any moisture or for-
eign matter.

c.

Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge. 

d.

The refrigeration system shall provide at least 15° F
of sub-cooling at design conditions.

e.

All models shall have two independent circuits.

f.

Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in
low-load applications. HGBP shall be a standard
feature on VAV models and an optional feature on
CV models.

UNIT CONTROLS

a.

Unit shall be complete with self-contained low-volt-
age control circuit protected by a resettable circuit
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.

1.

High-pressure switch.

2.

Freeze-protection thermostat, evaporator coil. If 
any of the above safety devices trip, a LED 
(light-emitting diode) indicator shall flash a 

diagnostic code that indicates which safety 
switch has tripped.

d.

Unit shall incorporate "AUTO RESET" compressor
over temperature, over current protection.

e.

Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.

f.

Unit control board shall have on-board diagnostics
and fault code display.

g.

Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0 °F.

h.

Control board shall monitor each refrigerant safety
switch independently.

i.

Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.

GAS HEATING SECTION (DM***N MODELS) 

Shall be designed with induced draft combustion with post 
purge logic and energy saving direct spark ignition, redun-
dant main gas valve. Ventor wheel shall be constructed of 
stainless steel for corrosion resistance. The heat exchanger 
shall be of the tubular type, constructed of T1-40 aluminized 
steel for corrosion resistance and allowing minimum mixed 
air entering temperature of 25° F. Burners shall be of the in-
shot type, constructed of aluminum coated steel and contain 
air mixture adjustments. All gas piping shall enter the unit 
cabinet at a single location through either the side or curb, 
without any field modifications. An integrated control board 
shall provide timed control of evaporator fan functioning and 
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:

a.

Primary and auxiliary high-temperature limit
switches.

b.

Induced draft motor speed sensor.

c.

Flame roll out switch (automatic reset).

d.

Flame proving controls. Unit shall have two inde-
pendent stages of capacity. 

ELECTRIC HEATING (DM***C/E MODELS) 

Nickel chromium electric heating elements shall be provided 
as required by the application with 1 or 2 stage control, as 
required, from 13.5 KW to 72 KW capacities. The heating 
section shall have a primary limit control(s) and automatic 
reset to prevent the heating element system from operating 
at an excessive temperature. Units with Electric Heating shall 
be wired for a single point power supply with branch circuit 
fusing (where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125° F 
outdoor temperature, exceeding maximum load criteria of 
ARI Standard 340/360. The compressor, with standard 
controls, shall be capable of operation down to 0° F outdoor 

Содержание DM 180

Страница 1: ...sure loss of charge switches and freezestats Scroll compressors 25T model only Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft logic Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Belt Drive Blower Motor with high static drive option Constant supp...

Страница 2: ... 15 TON COOLING ONLY 180 MBH BOTTOM DUCT CONNECTIONS 18 9 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 19 10 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 MBH BOTTOM DUCT CONNECTIONS 20 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON GAS HEAT 240 MBH BOTTOM DUCT CONNECTIONS 21 12 SUPPLY AIR BLOWER PERFORMANCE 25 TON GAS HEAT 300 MBH BOTTOM DUCT CONNECTIONS 22 13 BL...

Страница 3: ...roller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w ModLinc Hot Gas Bypass Standard on VAV Optional on CV Variable Air Volume VFD Not Available with Factory Installed BAS Options Variable Air Volume VFD With Manual Bypass Not Available with Factory Installed BAS Options Variable Air Volume VFD Ready for Cu...

Страница 4: ...is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing additional controls Low Ambient An integrated low ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis tance Optionally the control board can be pro gr...

Страница 5: ... the outdoor air intake dampers are opened for free cooling the exhaust fan will be energized to prevent the conditioned space from being over pressurized during economizer operation The exhaust fan motor and controls are installed and wired at the factory The rain hood must be assembled and installed in the field The power exhaust option can only be used on bot tom duct configurations MOTORIZED O...

Страница 6: ...0 volt outlet can be powered by the unit with a stepdown transformer or you may order the unit with a non powered conve nience outlet that can be wired in the field DISCONNECT SWITCH For gas heat units and cooling units with electric heat a HACR breaker sized to the unit is provided For cooling only units a switch sized to the largest electric heat available for the particular unit is provided Fac...

Страница 7: ...ncludes a slide in plug in damper assembly with a 2 position spring return motor actuator which opens to some pre set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down The rain hood is painted to match the basic unit and must be field assembled before installing ROOF CURBS Fourteen inch high roof curbs provide a water tight seal betwee...

Страница 8: ...re with proper exhausting of furnace combustion products this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes WOOD SKID Allows unit to be handled with 90 forks CO2 SENSOR Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits COIL GUARD Customers can purchase a coil guard kit to protect the condenser coil from ...

Страница 9: ...itary Large Equip ment certification program which is based on ARI Stan dard 340 360 MODEL MBH EER2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated Part Load Value COOLING ONLY DM180C E00 176 8 7 9 2 DM240C E00 234 8 6 8 05 DM300C E00 272 8 5 9 2 COOLING WITH GAS ...

Страница 10: ... 7 121 4 84 2 184 1 16 4 184 1 184 1 184 1 146 9 109 6 72 3 57 195 9 15 5 195 9 195 9 195 9 158 7 121 4 84 2 184 1 16 3 184 1 184 1 184 1 146 9 109 6 72 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 95 F 105 F TOTAL CAP 1 MBH POWER INPUT2 KW SENSIBLE CAPACITY MBH TOTAL CAP 1 MBH POWER INPUT2 KW SENSIBLE CAPACITY MBH ENTERING DRY BULB F ENTERING DRY BULB F CFM WB F 90 85 80 75 70 65...

Страница 11: ...0 0 20 7 154 6 96 3 67 0 72 174 0 19 8 156 3 127 2 98 0 68 8 67 158 0 18 9 158 0 158 0 129 0 99 8 70 7 62 146 0 18 4 146 0 146 0 146 0 116 8 87 7 58 5 57 146 0 18 5 146 0 146 0 146 0 116 8 87 7 58 5 6750 72 178 4 20 1 169 6 140 7 107 5 74 3 67 162 0 19 2 162 0 162 0 141 5 108 3 75 1 62 149 7 18 6 149 7 149 7 149 7 116 5 83 3 50 1 57 149 7 18 7 149 7 149 7 149 7 116 5 83 3 50 1 7500 72 182 8 20 3 1...

Страница 12: ...148 6 99 0 239 1 22 2 239 1 239 1 239 1 189 4 139 8 90 1 57 248 0 20 5 248 0 248 0 248 0 198 3 148 6 99 0 239 1 21 7 239 1 239 1 239 1 189 4 139 8 90 1 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 95 F 105 F TOTAL CAP 1 MBH POWER INPUT2 KW SENSIBLE CAPACITY MBH TOTAL CAP 1 MBH POWER INPUT2 KW SENSIBLE CAPACITY MBH ENTERING DRY BULB F ENTERING DRY BULB F CFM WB F 90 85 80 75 70 65 90...

Страница 13: ... 0 28 6 200 5 129 9 91 0 72 238 0 27 1 209 8 170 9 132 0 93 1 67 219 0 25 6 219 0 211 9 173 0 134 1 95 2 62 199 0 24 8 199 0 199 0 192 0 153 1 114 2 75 4 57 199 0 24 3 199 0 199 0 199 0 160 1 121 2 82 4 9000 72 240 4 27 5 226 3 190 8 146 5 102 2 67 221 3 26 0 221 3 217 7 192 0 147 7 103 4 62 201 0 25 1 201 0 201 0 197 5 153 3 109 0 64 7 57 201 0 24 6 201 0 201 0 201 0 156 8 112 5 68 2 10000 72 242...

Страница 14: ...8 9 297 7 25 6 297 7 297 7 297 7 235 6 173 5 111 4 57 295 3 22 4 295 3 295 3 299 6 237 5 175 4 113 3 294 6 25 6 294 6 294 6 294 6 232 5 170 4 108 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 95 F 105 F TOTAL CAP 1 MBH POWER INPUT2 KW SENSIBLE CAPACITY MBH TOTAL CAP 1 MBH POWER INPUT2 KW SENSIBLE CAPACITY MBH ENTERING DRY BULB F ENTERING DRY BULB F CFM WB F 90 85 80 75 70 65 90 85 ...

Страница 15: ...000 77 306 1 36 3 222 2 131 9 83 3 72 284 5 35 7 242 6 194 0 145 4 96 8 67 263 0 35 1 263 0 256 1 207 5 158 9 110 3 62 242 8 34 2 242 8 242 8 228 2 179 6 131 0 82 4 57 240 5 34 8 240 5 240 5 230 4 181 8 133 2 84 6 11250 72 287 9 35 9 258 4 203 1 147 7 92 4 67 266 1 35 3 266 1 262 7 210 8 155 4 100 1 62 245 7 34 5 245 7 245 7 231 8 176 5 121 1 65 8 57 243 3 35 0 243 3 243 3 234 0 178 7 123 3 68 0 1...

Страница 16: ...static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 7 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC Corrected BHP 4 0 x 0 832 3 328 Example 2 A system located at 5 000 feet of elevation is to deliver 6 000 CFM at a static pressure of 1 5 Use the unit blower tables to select the blower speed and the BHP...

Страница 17: ...262259 YTG B 0107 Unitary Products Group 17 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR ...

Страница 18: ...9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH SPEED DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4 5 1 5 3 2 2 9 1 3 3 9 3 5 1 1 4 5 4 0 0 8 5 1 4 6 0 7 5 6 5 0 1065 3 5 1 6 3 4 3 0 1 4 4 0 3 6 1 2 4 7 4 2 1 0 5 5 4 9 1095 3 0 1 7 3 5 3 1 1 5 4 2 3 8 1 3 4 9 4 4 1 2 5 7 5 1 1130 2 0 1 9 3 7 3 3 1 7 4 5 ...

Страница 19: ... 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9 6 8 5 7 1 7 7 4 6 2 1 2 8 1 6 8 0 7 8 6 7 3 1050 2 5 2 1 6 4 5 4 2 0 7 0 5 9 1 8 7 6 6 4 1 3 8 3 7 0 1075 2 0 2 3 6 6 5 5 2 1 7 2 6 0 1 9 7 8 6 6 1 5 8 6 7 2 1100 1 0 2 4 6 7 5 6 2 2 7 3 6 1 2 1 7 9 6 7 2...

Страница 20: ...4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH SPEED DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3 5 1 4 6 1025 4 5 1 4 3 1 2 8 1 2 3 6 3 2 0 9 4 1 3 7 0 7 4 8 4 3 0 4 5 5 4 9 1065 3 5 1 6 3 4 3 0 1 4 3 9 3 5 1 1 4 5 4 0 0 9 5 1 4 6 1125 2 0 1 9 3 6 3 2 1 7 4 4 3 9 1 4 5 0 4 5 1 2 5 8 5 2 1170 1 0 2 1 ...

Страница 21: ...5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5 1 4 3 2 0 6 1 5 1 1 4 7 1 6 0 0 9 8 4 7 0 1065 2 0 2 6 5 3 4 4 2 1 6 3 5 3 1 5 7 3 6 2 1 0 8 6 7 2 1100 1 0 2 9 5 6 4 7 2 3 6 8 5 7 1 8 7 9 6 6 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 3 3 6 ...

Страница 22: ...2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1 0 3 5 10 0 8 2 3 0 12 0 9 9 2 3 14 1 11 6 1 5 16 4 13 4 1365 0 0 3 7 10 5 8 6 3 2 12 6 10 3 2 6 14 7 12 1 1 8 17 0 13 9 230 460 575 VOLT AND STANDARD DRIVE 975 6 0 1 4 5 9 4 9 1 0 7 3 6 0 0 5 8 8 7 2 1005 ...

Страница 23: ...pulley below 1 turn open TABLE 14 STATIC RESISTANCES1 DESCRIPTION RESISTANCE IWG CFM 15 TON 20 TON 25 TON 4500 6000 7200 6000 8000 9400 7500 10000 12500 WET INDOOR COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS 18 KW 0 3 0 4 0 4 0 4 0 4 0 5 0 4 0 5 0 6 36 KW 0 3 0 4 0 5 0 4 0 5 0 5 0 5 0 5 0 6 54 KW 0 4 0 5 0 5 0 5 0 5 0 6 0 5 0 6 0 7 72 KW 0 4 0 5 0 5 0 5 0 5 0 6 0 5 0 6 0 7 ECONO...

Страница 24: ...9 6 62 2 2 7 0 0 0 None 0 0 42 6 50 E18 18 0 1 21 7 42 6 50 E36 36 0 2 43 3 62 9 70 E54 54 0 2 65 0 73 7 90 E72 72 0 2 86 6 95 4 110 575 7 7 50 1 7 5 3 0 0 None 0 0 33 7 40 E18 18 0 1 17 3 33 7 40 E36 36 0 2 34 6 49 9 50 E54 54 0 2 52 0 58 6 70 E72 72 0 2 69 3 75 9 90 240 20 208 19 2 124 4 5 19 6 0 0 None 0 0 110 3 125 E18 13 5 1 37 5 110 3 125 E36 27 0 2 75 1 118 2 125 E54 40 6 2 112 6 165 4 175 ...

Страница 25: ... 102 9 110 575 17 3 102 1 7 10 0 0 0 None 52 3 60 E18 18 0 1 17 3 52 3 60 E36 36 0 2 34 6 55 8 60 E54 54 0 2 52 0 64 5 70 E72 72 0 2 69 3 81 8 90 TABLE 18 DM 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET MODEL TON NAGE VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN CIRCUIT AMPACITY AMPS MAX FUSE BRKR1 SIZE AMPS RLA EACH ...

Страница 26: ... 62 2 2 7 0 5 0 None 0 0 47 6 50 E18 18 0 1 21 7 47 6 50 E36 36 0 2 43 3 69 1 70 E54 54 0 2 65 0 80 0 90 E72 72 0 2 86 6 101 6 110 575 7 7 50 1 7 5 3 4 0 None 0 0 37 7 45 E18 18 0 1 17 3 37 7 45 E36 36 0 2 34 6 54 9 60 E54 54 0 2 52 0 63 6 70 E72 72 0 2 69 3 80 9 90 240 20 208 19 2 124 4 5 19 6 10 0 None 0 0 120 3 125 E18 13 5 1 37 5 120 3 125 E36 27 0 2 75 1 130 7 150 E54 40 6 2 112 6 177 9 200 E...

Страница 27: ... 109 1 110 575 17 3 102 1 7 10 0 4 0 None 56 3 70 E18 18 0 1 17 3 56 3 70 E36 36 0 2 34 6 60 8 70 E54 54 0 2 52 0 69 5 70 E72 72 0 2 69 3 86 8 90 TABLE 21 DM 300 ELECTRICAL DATA HIGH STATIC MOTOR WITH POWERED CONVENIENCE OUTLET MODEL TON NAGE VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN CIRCUIT AMPACITY AMPS MAX FUSE BRKR1 SIZE AMPS RLA EACH LRA...

Страница 28: ...REA Sq Ft 36 43 3 43 3 COMPRESSOR Qty Per Unit 5 TON HERMETIC RECIP 1 10 TON TANDEM RECIP 11 2 12 5 TON SCROLL 2 FILTERS QUANTITY PER UNIT 12 X 24 X 2 or 4 QUANTITY PER UNIT 16 X 20 X 2 or 4 4 4 QUANTITY PER UNIT 16 X 25 X 2 or 4 4 4 QUANTITY PER UNIT 18 X 24 X 2 or 4 5 TOTAL FACE AREA Sq Ft 15 20 24 CHARGE REFRIGERANT 22 Lb Oz SYSTEM No 1 17 8 18 0 18 0 SYSTEM No 2 8 8 18 0 18 0 OPERATING WEIGHTS...

Страница 29: ...t control box 3Second stage heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back position NOTE Fans switch must be in ON position for minimum ventilation during heater operation LINE VOLTAGE TERMINAL BLOCK 2TB IN CONTROL BOX GROUND LUG Refer to the ELECTR...

Страница 30: ...ions UNIT BASE WITH RAILS Shown separately to illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY 92 CONDENSER COILS COIL GUARD COMPRESSOR ACCESS ECONOMIZER MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS See detail Y FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER COMPARTMENT A...

Страница 31: ... The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air compartments with the side duct flange accessory kit panels 2 Connect ductwork to the flanges on those panels SUPPLY AIR RETURN AIR OUTDOOR AIR 5 1 8 18 5 8 27 3 4 28 5 8 15 TON 39 5 8 20 25 TON 40 1 ...

Страница 32: ...NCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 0 Above Unit2 2 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air disch...

Страница 33: ...262259 YTG B 0107 Unitary Products Group 33 FIGURE 7 CENTER OF GRAVITY FIGURE 8 TYPICAL UNIT APPLICATIONS ...

Страница 34: ...86 240 Gas 2500 538 563 715 684 300 Gas 2531 593 645 674 619 180 Elec 2100 492 514 558 536 240 Elec 2300 295 517 658 630 300 Elec 2331 546 594 621 570 Unit Size Total Shipping Weight 6 Point Loads lbs A B C D E F 180 Gas 2300 351 367 392 416 399 375 240 Gas 2500 334 350 426 502 481 407 300 Gas 2531 390 412 436 456 430 407 180 Elec 2100 320 335 358 380 364 343 240 Elec 2300 307 322 392 462 442 375 ...

Страница 35: ...URE 10 UNIT ROOF CURB DIMENSIONS SUPPLY AIR BACK OF UNIT RETURN AIR DUCT SUPPORT RAILS MIN ROOF OPENING 39 7 8 WIDE X 61 7 8 Long OUTDOOR COIL END OF UNIT 4 33 1 8 2 22 3 4 4 4 84 35 7 8 14 1 4 15 Ton 25 1 4 20 25 Ton 115 5 16 15 Ton 126 1 4 20 25 Ton 2 Supply and Return Air including duct support rails as shown are typical for bottom duct applications For location of horizontal duct applications ...

Страница 36: ... TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage cooling units Jumper is required if there is no Smoke Detector circuit Jumper is required for any combination of R RC or RH 6 5 5 6 OCC is an output from the thermostat to indicate the Occupied condition X is an input to the...

Страница 37: ...alled options or field installed accessories The units shall be factory wired piped charged with R 22 refrigerant and factory tested prior to ship ment All unit wiring shall be both numbered and color coded All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be CGA listed...

Страница 38: ...all incorporate AUTO RESET compressor over temperature over current protection e Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook up f Unit control board shall have on board diagnostics and fault code display g Standard controls shall include anti short cycle and low voltage protection and permit cooling operation down to 0 F h Control boa...

Страница 39: ...ntial of 0 5 IWG A unit mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation Whenever the indoor fan motor is energized the dampers open up to one of two pre selected posi tions regardless of the outdoor air enthalpy Dampers return t...

Страница 40: ...ry Products All rights reserved Supersedes 262259 YTG A 0706 Unitary 5005 Norman Products York OK Group Drive 73069 HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS HIGH SPEED DRIVE 2 THROW AWAY FILTERS 4 PLEATED FILTERS DISCONNECT SWITCH SUPPLY AIR SMOKE DETECTOR RETURN AIR SMOKE DETECTOR ...

Отзывы: