TABLE 4: DM 180 COOLING CAPACITIES (15 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
115°F
TOTAL
CAP.
1
MBH
POWER
INPUT
2
KW
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
CFM
WB
°F
90
85
80
75
70
65
4500
77
176.8
20.4
98.3
77.0
55.6
-
-
-
72
161.9
19.5
124.1
102.7
81.3
59.9
-
-
67
147.0
18.6
147.0
128.4
107.0
85.6
64.2
-
62
135.8
18.1
135.8
135.8
121.1
99.7
78.3
56.9
57
135.8
18.2
135.8
135.8
121.1
99.7
78.3
56.9
5250
77
183.4
20.5
126.5
86.6
61.3
-
-
-
72
167.9
19.6
140.2
114.9
89.6
64.4
-
-
67
152.5
18.8
152.5
143.2
118.0
92.7
67.5
-
62
140.9
18.3
140.9
140.9
133.6
108.3
83.0
57.7
57
140.9
18.4
140.9
140.9
133.6
108.3
83.0
57.7
6000
77
190.0
20.7
154.6
96.3
67.0
-
-
-
72
174.0
19.8
156.3
127.2
98.0
68.8
-
-
67
158.0
18.9
158.0
158.0
129.0
99.8
70.7
-
62
146.0
18.4
146.0
146.0
146.0
116.8
87.7
58.5
57
146.0
18.5
146.0
146.0
146.0
116.8
87.7
58.5
6750
72
178.4
20.1
169.6
140.7
107.5
74.3
-
-
67
162.0
19.2
162.0
162.0
141.5
108.3
75.1
-
62
149.7
18.6
149.7
149.7
149.7
116.5
83.3
50.1
57
149.7
18.7
149.7
149.7
149.7
116.5
83.3
50.1
7500
72
182.8
20.3
182.8
154.3
117.0
79.7
-
-
67
166.0
19.4
166.0
166.0
154.0
116.7
79.5
-
62
153.4
18.9
153.4
153.4
153.4
116.1
78.9
41.6
57
153.4
19.0
153.4
153.4
153.4
116.1
78.9
41.6