background image

1083292-UIM-A-0114

Johnson Controls Unitary Products

21

ACCESSORY CONNECTIONS

The furnace control will allow power-switching control of various acces-
sories.

ELECTRONIC AIR CLEANER CONNECTION

Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic
air cleaner connections are located on the control board. The terminals
provide 115 VAC (1.0 amp maximum) during circulating blower opera-
tion.

HUMIDIFIER CONNECTION

Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier
connections are located on the control board. The terminals provide 115
VAC (1.0 amp maximum) during heating system operation.

A mounting hole is provided on the control panel next to the furnace
control board for mounting a humidifier transformer if read.

HUMIDISTAT CONNECTION

For better humidity control during cooling operation, an external humidi-
stat may be used. When using a external humidistat, put the HUMIDI-
STAT jumper in the YES position. Connect the low voltage wiring as
shown in Figures 22-27.

ZONING OPERATION

This furnace may be used in zoning systems, using a separate after-
market zoning control. For use in zoned systems, put the ZONE CON-
TROL jumper on the furnace control board in the “YES” position.

If the Zone jumper is put in the “Yes” position, the heating load logic
switches to a special algorithm for multi-zone homes. 

1.

This algorithm operates at the “low demand” firing rate for 10 min-
utes and then ramps to high fire within 20 minutes (30 minutes
maximum to get to 100% firing rate).

2.

The special zoning algorithm does not have the Run 2 function, so
the burners will stop firing as soon as there is no call for heating.

HEAT PUMP OPERATION

This furnace may be used in conjunction with a heat pump in dual fuel
applications. For heat pump applications, put the HEAT PUMP jumper
on the furnace control board in the “YES” position. Connect the low volt-
age wiring as shown in Figures 25-27, Thermostat Charts. If a two-
stage heat pump is to be used, a two-stage thermostat is required.

If the Heat Pump jumper is in the “YES” position, it indicates that there
is a heat pump present and the furnace is used as a secondary heat
source. In addition, the “YES” Heat Pump jumper allows the system to
read the presence of the “O” terminal signal. In heat pump operation,
the following special algorithm logic applies:

1.

Supplemental Heating

 -

 When both a “W” signal and a “Y1” signal

are present, the modulating firing rate will operate as normal,
except there will be no Run 2 function, so the burners will stop fir-
ing as soon as the “W” signal is removed.

2.

Defrost Cycle - When both a “W” signal and a “Y2” signal are pres-
ent, the modulating firing rate will operate at a constant 80% firing
rate and there will be no Run 2 function, so the burners will stop fir-
ing as soon as the “W” signal is removed.

3.

Hot Heat Pump - The “hot” heat pump feature will work when the
control is wired to a 2-stage thermostat and a 2-stage heat pump.

4.

Hot Heat Pump - The “hot” heat pump feature will not work when
the control is wired to a single-stage thermostat and a 2-stage heat
pump.

TWINNING

These furnaces are not to be twinned. If more than one furnace is
needed in an application, each furnace must have its own complete
duct system and its own wall thermostat.

SECTION VI: CONDENSATE PIPING AND 

FURNACE VENTING CONFIGURATION

CONDENSATE DRAIN LOCATION

As shipped from the factory:

For all 060 & 080K input furnaces the main drain is plumbed
through the casing right-side opening when viewed from the front
of the furnace.

For all 100, 120K input furnaces the main drain is plumbed
through the casing left-side opening when viewed from the front
of the furnace.

The Figures 29-32 show the condensate drain arrangement for the var-
ious possible furnace and vent blower positions.

The condensate hoses must slope downwards at all points.

The condensate water will flow to the drain better if an open tee, or
short length of pipe is installed in the drain line.

When drain hose routing changes are required (shown in Figures 29-
32), be sure to cap all un-used openings.

If rerouting hoses - excess length should be cut off so that no sagging
loops will collect and hold condensate - which will cause the furnace to
not operate.

No hose clamps are needed for connecting the condensate pan.

The furnace condensate pan is self priming and contains
an internal trap to prevent flue gas leaking. Do not install an
external condensate trap.

The furnace, evaporator coil, and humidifier drains may be com-
bined and drained together. The evaporator coil drain may have an
external, field-supplied trap prior to the furnace drain connection to
prevent conditioned air leakage. All drain connections (furnace,
evaporator coil, or humidifier) must be terminated into an open or
vented drain as close to the respective equipment as possible.
Regular maintenance is required on condensate drainage system.

Condensate must be disposed of properly. Follow local plumbing 
or wastewater codes. The drain line must maintain a 1/4" per foot
(21 mm/m) downward slope to the drain.

If an external vent tee is being installed, then it must have its own
condensate trap before it is disposed into an open or vented drain.
This is not to be considered as a second trap as referenced
elsewhere in this document.

Содержание CP9C Series

Страница 1: ...rmostat Chart Two Stage Air Conditioner with Single Stage Thermostat Variable Speed Modulating Furnace 17 Thermostat Chart Single Stage Heat Pump Variable Speed Modulating Furnace 18 Thermostat Chart...

Страница 2: ...marking Means for providing outdoor air required for combustion Return air temperature maintained between 55 F 13 C and 80 F 27 C The air filter must be replaced upon substantial completion of the co...

Страница 3: ...g jurisdiction In the United States and Canada follow all codes and standards for the following using the latest edition available STEP 1 Safety US National Fuel Gas Code NFGC NFPA 54 ANSI Z223 1 and...

Страница 4: ...nstalled in every dwelling building or structure used in whole or in part for resi dential purposes including those owned or operated by the Com monwealth and where the side wall exhaust vent terminat...

Страница 5: ...ed down for shipment In order to use the flanges remove the screw holding an individual flange rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flan...

Страница 6: ...t exchang ers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lifting points as the tubes may shift out of position or their location brackets baffles SU...

Страница 7: ...il casing over or under the furnace opening as shown in Figure 7 after configuring coil flanges as required see Coil Flange sec tion below COIL FLANGE INSTALLATION The coil cabinet includes four remov...

Страница 8: ...t such that a minimum dis tance is maintained between the top of the coil and the top of the duct Refer to Table 2 COIL FURNACE ASSEMBLY HD SERIES COILS Horizontal duct coils are referred to as HD ser...

Страница 9: ...trical Entry Condensate Drain Optional Return Air Cutout Either side 29 5 For Cladded door add appoximately an additional 75 C SUPPLY END 56 56 20 B 3 23 8 56 Combustion Air Inlet RETURN END B 24 25 2...

Страница 10: ...from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace Refer to Figures 13 and 16 All filters and mounting provision must be field supplied All installa...

Страница 11: ...es to larger 43 orifices which will bring the input rate back up to approxi mately 76 000 BTU H which is what it should be for that furnace at 6 000 feet SECTION V ELECTRICAL POWER ELECTRICAL POWER CO...

Страница 12: ...bushing where the wires pass through the furnace panel After making the wiring connections replace the wiring box cover and screws Refer to Figure 17 3 The furnace s control system requires correct p...

Страница 13: ...or heat pump with a fully communicating control This furnace may also be used along with the Communicating Thermo stat Control and a non communicating outdoor air conditioner through the addition of...

Страница 14: ...tage wiring as shown in Figure 24 This furnace control board can control a two stage A C using only a sin gle stage thermostat In this case the furnace control switches between high cool and low cool...

Страница 15: ...Heat Clipping Jumper W914 for electric heat on thermostat is not necessary C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER C 24 Volt Com...

Страница 16: ...Volt Hot Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidity Rise W Modulating Heat Move HUMIDIST...

Страница 17: ...ssary C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidity Rise W M...

Страница 18: ...CONTROL X L Malfunction Light W Auxiliary Heat SINGLE STAGE HEAT PUMP Y2 Second Stage Compressor Step 9 of Thermostat Installer Configuration Menu must be set to Pump OFF Step 1 of Thermostat Installe...

Страница 19: ...Energized in Cool C 24 Volt Common R 24 Volt Hot W1 OUT First Stage Heat W2 OUT Second Stage Heat Y2 OUT Second Stage Compressor Y1 Single Stage Compressor X L Malfunction Light Y2 Second Stage Compre...

Страница 20: ...at XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Step 1 of Thermostat Installer Configuration Menu must be set to HP2 Selection of GAS ELEC switch on thermostat not necessary Thermostat Installer S...

Страница 21: ...the W signal is removed 2 Defrost Cycle When both a W signal and a Y2 signal are pres ent the modulating firing rate will operate at a constant 80 firing rate and there will be no Run 2 function so th...

Страница 22: ...and drain hose located in the loose parts bag The intake drain hose is to be installed by connecting it to the inlet pipe coupling and to the collec tor box as shown in Figures 29 31 and 32 The drain...

Страница 23: ...ff so that no sagging loops will collect and hold condensate which will cause the furnace to not operate Shorten pressure switch hose Re route and shorten pressure switch hose Shorten rain gutter hose...

Страница 24: ...tch hose to this position NOTE May require the longer hose that is provided with wider cabinets Move condensate drain hose to this position May exit either side of the cabinet Move rain gutter hose to...

Страница 25: ...ose to this position NOTE May require the longer hose that is provided with wider cabinets Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this position Mov...

Страница 26: ...tting provided Move condensate drain hose to this position Move rain gutter hose to this position Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this posit...

Страница 27: ...to American National Standards Institute ANSI and American Society for Test ing and Materials ASTM standards D1785 Schedule 40 PVC D2665 PVC DWV F891 PVC DWV Cellular Core D2261 ABS DWV or F628 Schedu...

Страница 28: ...5 80 000 4 125 100 000 2 20 100 000 2 NA 100 000 3 80 100 000 3 60 100 000 4 145 100 000 4 125 120 000 3 80 120 000 3 60 120 000 4 145 120 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input...

Страница 29: ...VENTING FIGURE 33 Dimensions TABLE 8 Elbow Dimensions Elbow A Dimension Illustrated in Figure 33 2 Standard 2 5 16 3 Standard 3 1 16 2 Sweep 3 1 4 3 Sweep 4 1 16 TABLE 9 Equivalent Length of Fittings...

Страница 30: ...equirements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 30 5 cm or in accordance with local...

Страница 31: ...Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 36 and 37 can be insta...

Страница 32: ...ipes are not termi nated in the same atmospheric zone Refer to Figure 44 for attic and crawl space termination Only the combustion air intake may terminate in the attic The vent must terminate outside...

Страница 33: ...as an exhaust fan kitchen ventilation system clothes dryer or fireplace may cre ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances A venting problem or a l...

Страница 34: ...Refer to Table 7 for intake pipe sizing allowable length and elbow usage Follow all notes procedures and required materials in the COMBUSTION AIR VENT PIPE SIZING section in these instructions when i...

Страница 35: ...no thermostat calls no call for heating cooling or continuous fan push and hold the TEST but ton on the board for one second The LED on the board will glow red 2 Release the TEST button The LED on the...

Страница 36: ...ifice hole is essential for proper flame characteristics DO NOT bottom out gas valve regulator adjusting screw This can result in unregulated manifold pressure and result in excess over fire and heat...

Страница 37: ...R jumper on the furnace control board The jumper is factory set to deliver an air temperature rise near the midpoint of the nameplate temperature rise range If more air is desired lower temper ature r...

Страница 38: ...e southern part of the country On a call for cooling the blower will ramp up to 50 of full capacity and will stay there for two minutes then will ramp up to 82 of full capacity and will stay there for...

Страница 39: ...90 840 H B 1100 715 1090 710 MH B 1065 690 1015 660 H A 1000 650 1000 650 MH A 960 625 960 625 H C 760 495 760 495 ML B 900 585 900 585 MH C 660 430 660 430 L B 690 450 680 445 ML A 600 400 600 400 L...

Страница 40: ...e is equipped with a high temperature limit control mounted to the left side of the furnace vestibule panel This limit switch will open and shut off gas to the burners if it detects excessive air temp...

Страница 41: ...ating airflow an open fuse on the control board Five Red Flashes Rollout switch or condensate pressure switch open Check the rollout switch es on the burner assembly It is a man ual reset switch To re...

Страница 42: ...GHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d PAN CONDENSATE BRACKET DOOR HARNESS WIRING FERRULE 3 Req d GROMMET 3 Req d MOTOR MOUNT TUBING SILICON HOSE RAIN GUTTER HOSE CONDENSATE PLUG SEAL 7...

Страница 43: ...und neutral Gas valve shorted ON Check blower motor wiring ID plug missing OR not connected properly None Slow Green Rapid Green Slow Amber Rapid Amber 2 Amber 3 Amber 4 Amber 5 Amber 6 Amber Steady R...

Страница 44: ...1083292 UIM A 0114 44 Johnson Controls Unitary Products NOTES...

Страница 45: ...neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control board volts AC Thermostat Type Other System Equipment and Accessories Owne...

Страница 46: ...Calculated input in btuh clock the gas meter Nat Gas Only Manifold Gas Pressure in w c furnace must be in TEST mode for setup Inlet Gas Pressure in w c LP Gas Conversion Kit Part Used Burner flame in...

Отзывы: