Johnson Controls Unitary Products
INSTALLATION
INSTALLATION SAFETY INFORMATION:
Read these instructions before continuing this appli-
ance installation. This is an outdoor combination heat-
ing and cooling unit. The installer must assure that
these instructions are made available to the consumer
and with instructions to retain them for future reference.
1. Install this furnace only in a location and position
as specified on Page 6 of these instructions.
2. This equipment is not to be used for temporary
heating of buildings or structures under construc-
tion.
LIMITATIONS
These units must be installed in accordance with the
following national and local safety codes:
In U.S.A.:
•
National Electrical Code ANSI/NFPA No. 70.
•
Local gas utility requirements.
In Canada:
•
Current Canadian Electrical Code C22.1.
•
Local plumbing and waste water codes.
•
Other applicable local codes.
Refer to the Unit Application Data table and to the Elec-
tric Heat Application Data table.
If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or
the customer's expense.
Size of unit for proposed installation should be based
on heat loss/heat gain calculation made according to
the methods of the Air Conditioning Contractors of
America (ACCA).
This furnace is not to be used for temporary heating of
buildings or structures under construction.
LOCATION
Use the following guidelines to select a suitable loca-
tion for these units.
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of
air.
3. Where a choice of location is possible, position the
unit on either north or east side of building.
4. For ground level installation, use a level concrete
slab with a minimum thickness of 4 inches. The
length and width should be at least 6 inches
greater than the unit base rails. Do not tie slab to
the building foundation.
5. Roof structures must be able to support the weight
of the unit and its options and/or accessories. Unit
must be installed on a solid level roof curb or
appropriate angle iron frame.
The
Simplicity
® control board used in this
product will effectively operate the cooling
system down to 0°F when this product is applied
in a comfort cooling application for people. An
economizer is typically included in this type of
application. When applying this product for
process cooling applications (computer rooms,
switchgear, etc.), please reference applications
bulletin AE-011-07 or call the applications
department for Unitary Products @ 1-877-UPG-
SERV for guidance. Additional accessories may
be needed for stable operation at temperatures
below 30°F.
TABLE 1: UNIT APPLICATION DATA
UNIT MODEL NUMBER
BQ240
Voltage Variation,
Min. / Max.
1
1.
Utilization range “A” in accordance with ARI Standard
110.
208/230-3-60
187 / 253
460-3-60
414 / 506
575-3-60
518 / 630
Supply Air CFM, Min. / Max.
6,000 / 9,300
Wet Bulb Temperature (
°
F) of Air on
Evaporator Coil, Min. / Max.
57 / 72
Dry Bulb Temperature (
°
F) of Air on
Condenser Coil, Min. / Max.
0 / 120