13
•
Optional CO
2
Space Sensor Kit Part #
2AQ04700324
•
Optional CO
2
Unit Sensor Kit Part # 2AQ04700424
Replace the economizer access panel.
OPTIONAL BAS-READY ECONOMIZER POWER
EXHAUST DAMPER SET POINT ADJUSTMENT
Remove the economizer access panel from the unit.
Loosen, but do not remove the two panel latches.
Locate the economizer actuator, where the following
adjustment can be made.
With power exhaust option, each building pressuriza-
tion requirement will be different. The point at which the
power exhaust comes on is determined by the econo-
mizer's outdoor damper position. The actuator's auxil-
iary switch adjustment screw should be set at the
damper position at which the power exhaust is needed.
The adjustment screw can be set between 25 to 85
degrees open.
Replace the economizer access panel.
FIGURE 6 - ENTHALPY SETPOINT ADJUSTMENT