MECHANICAL SPECIFICATIONS

GENERAL DESCRIPTION

Units shall be factory-assembled, single packaged, 

Heat Pumps, designed for outdoor mounted installa-

tion. Units shall have minimum SEER ratings of 13.0. 

They shall have built in, equal size, field convertible 

duct connections for down discharge supply/return or 

horizontal discharge supply/return.
The units shall be factory wired, piped, charged with R-

22 refrigerant and factory tested prior to shipment. All 

unit wiring shall be both numbered and color coded.
All units shall be manufactured in a facility certified to 

ISO 9001 standards, and the cooling performance shall 

be rated in accordance with DOE and ARI test proce-

dures. Units shall be classified to UL 1995/CAN/CSA 

No. 236-M90 conditions.

UNIT CABINET

1. Unit cabinet shall be constructed of G90 galva-

nized steel, with exterior surfaces coated with a

non-chalking, powered paint finish, certified at 750

hours salt spray test per ASTM-B117 standards.

2. The unit top shall be a single piece ìWater Shedî

design, with drip edges and no-seam corners to

provide optimum water integrity.

3. Unit shall have a rigidly mounted condenser coil

guard to provide protection from objects and per-

sonnel after installation.

4. Indoor blower section shall be insulated with up to

3/4î  thick, aluminum, foil faced insulation, fastened

to prevent insulation from entering the air stream.

5. Cabinet panels shall be ìlargeî size, easily remov-

able for servicing and maintenance, with built-in lift

handles.

6. Unit shall be built on a formed, ìSuper-Structureî

design base pan, with embossments at critical

points to add strength, rigidity and aid in minimizing

sound.

7. Full perimeter base rails shall be provided to

assure reliable transit of equipment, overhead rig-

ging, fork truck access and proper sealing on roof

curb applications. Base rails shall be removable,

when required, to lower unit height.

8. Filters shall be furnished and be accessible

through a removable access door, sealed air tight.

(Single phase models - accessory kit available.

Three phase models - standard from factory.)

9. Units vertical discharge and return duct configura-

tion shall be designed to fit between standard 24î

O.C. beams without modification to building struc-

ture, duct work and base unit.

10. Condensate pan shall be internally sloped and

conform to ASHARE 62-89 self-draining standards,

with " NPTI copper, ridged mount connection.

INDOOR (SUPPLY) FAN ASSEMBLY

1. Fan shall be direct drive, constant CFM, ECM

design. Job site selected (BHP) brake horse power

shall not exceed the motors nameplate horse

power rating.

2. Fan wheel shall be double-inlet type with forward-

curved blades, dynamically balanced to operate

smoothly throughout the entire range of operation.

Airflow design shall be constant air volume.

3. Bearings shall be sealed and permanently lubri-

cated for longer life and no maintenance.

4. Fan assembly shall be ìSlip Trackî (slide-out)

design for easy removal and cleaning.

OUTDOOR FAN ASSEMBLY

1. The outdoor fan shall be of the direct-driven propel-

ler type, discharge air vertically, have aluminum

blades riveted to corrosion resistant steel spider

bracket and shall be statically balanced for smooth

operation.

2. The outdoor fan motor shall be totally enclosed

with permanently lubricated bearings and internally

protected against overload conditions.

REFRIGERANT COMPONENTS

1. Compressors:

A. Shall be fully hermetic type, direct drive, internally

protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.

Содержание B1HP024 THRU 048

Страница 1: ...aller can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique test sta...

Страница 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Страница 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Страница 4: ...provide single phase models from factory furnished 40 VA trans former capability to 75 VA transformer capability ELECTRIC HEATERS Each heater package provides easy installation of elec tric heat strip...

Страница 5: ...RIC HEAT NOMINAL CAPACITY KW 47 F 17 F MBH SEER EER MBH COP MBH COP SINGLE PHASE THREE PHASE 024 24 4 13 0 11 3 7 6 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 6 77 28 2 3 40 16 5 2 2...

Страница 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Страница 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Страница 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Страница 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Страница 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Страница 11: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 9 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TEM...

Страница 12: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 11 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Страница 13: ...KW 2 408 2 634 2 861 3 088 3 315 3 542 3 769 3 996 70 MBH 13 702 16 887 20 812 25 650 31 612 38 961 48 017 59 179 KW 2 792 3 018 3 245 3 472 3 699 3 926 4 153 4 380 80 MBH 12 114 15 299 19 224 24 062...

Страница 14: ...CFM 273 324 392 480 541 B1HP042 Electric Heat 1225 CFM 306 341 412 494 577 B1HP042 Cooling TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B 1400 CFM 393 466 544 642 734 B1HP042 Heating TB2 A...

Страница 15: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Страница 16: ...15 0 96 75 036 208 230 1 60 187 253 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60...

Страница 17: ...06 7 5 10 0 36 1 41 7 83 2 90 1 90 100 90 100 2NP04501506 11 3 15 0 54 2 62 5 105 8 116 2 110 125 110 125 2NP04502006 15 0 20 0 72 2 83 3 128 3 142 2 150 150 150 150 2NP04502506 18 8 25 0 90 3 104 2 1...

Страница 18: ...102 89 92 042 440 435 120 115 101 104 048 485 480 132 127 111 115 FIGURE 4 UNIT CLEARANCES CLEARANCES NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1 2...

Страница 19: ...036 21528 001 A 0303 Unitary Products Group 19 FIGURE 5 UNIT DIMENSIONS...

Страница 20: ...036 21528 001 A 0303 20 Unitary Products Group FIGURE 6 TYPICAL APPLICATIONS...

Страница 21: ...036 21528 001 A 0303 Unitary Products Group 21 FIGURE 7 ROOF CURB DIMENSIONS...

Страница 22: ...036 21528 001 A 0303 22 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Страница 23: ...036 21528 001 A 0303 Unitary Products Group 23 FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Страница 24: ...036 21528 001 A 0303 24 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Страница 25: ...l be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height...

Страница 26: ...pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for room thermostat LED indication of...

Страница 27: ...036 21528 001 A 0303 Unitary Products Group 27...

Страница 28: ...001 A 0303 Copyright by Unitary Products Group 2003 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 73069 This product was manufactured in a plant whose qualit...

Отзывы: