255029-YTG-C-0506
Unitary Products Group
9
Electrical Data - (For Multi-Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60
Models
Heater
Models
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75
°
C Wire Size - AWG
Circuit
Circuit
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/240
208/240
208/240
208/240 208/240 208/240 208/240 208/240 208/240
AHP36C**(N,H)21
4HK16501506
47.48 / 54.5 21.68 / 25.00
—
50 / 60
25 / 25
—
8 / 6
10 / 10
—
4HK16501806
43.88 / 50.31 39.75 / 45.80
—
45 / 60
40 / 50
—
8 / 6
8 / 8
—
AHP42C**(N,H)21
4HK16501506
47.60 / 54.75 21.68 / 25.00
—
50 / 60
25 / 25
—
8 / 6
10 / 10
—
4HK16501806
44.00 / 50.56 39.75 / 45.80
—
45 / 60
40 / 50
—
8 / 6
8 / 8
—
AHP48D**(N,H)21
SHP48D**N21
4HK16501506
47.60 / 54.75 21.68 / 25.00
—
50 / 60
25 / 25
—
8 / 6
10 / 10
—
4HK16501806
44.00 / 50.56 39.75 / 45.80
—
45 / 60
40 / 50
—
8 / 6
8 / 8
—
4HK16502006
47.60 / 54.75 43.35 / 50.00
—
50 / 60
40 / 50
—
8 / 6
8 / 8
—
AHP60D**(N,H)21
SHP60D**N21
4HK16501506
52.85 / 59.50 21.68 / 25.00
—
60 / 60
25 / 25
—
6 / 6
10 / 10
—
4HK16501806
49.25 / 55.31 39.75 / 45.81
—
50 / 60
45 / 60
—
6 / 6
8 / 6
—
4HK16502006
52.85 / 59.50 43.35 / 50.00
—
60 / 60
45 / 50
—
6 / 6
8 / 8
—
4HK16502506
52.85 / 59.50 43.35 / 50.00 21.68 / 25.00
60 / 60
45 / 50
25 / 25
6 / 6
8 / 8
10 / 10
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Electrical Data - 3 Ø - 208/230-3-60
Models
Heater
Model
Max. Static
& Min. CFM
Total Heat
1
kW Staging
kW
MBH
W1 Only
W2 Only
W1 + W2
Static
Tap
208
240
208
240
208
240
208
240
208
240
AHP24B**(N,H)21
4HK06501025
Data not available for this release.
Check for latest revision of this document
or Air Handler Installation Instructions.
Documents available on-line
www.upgnet.com
AHP30B**(N,H)21
4HK06501025
AHP36C**(N,H)21
4HK06501025
4HK06501525
4HK06501825
AHP42C**(N,H)21
4HK06501025
4HK06501525
4HK06501825
AHP48D**(N,H)21
SHP48D**N21
4HK06501025
4HK06501525
4HK06501825
AHP60D**(N,H)21
SHP60D**N21
4HK06501025
4HK06501525
4HK06501825
4HK06502525
1. See conversion table on page 7.
Electrical Data - (For Single Source Power Supply) - Copper Wire 3 Ø - 208/230-3-60
Models
Heater
Models
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75
°
C Wire Size - AWG
208V
240V
208V
240V
208V
240V
AHP24B**(N,H)21
4HK06501025
Data not available for this release.
Check for latest revision of this document
or Air Handler Installation Instructions.
Documents available on-line
www.upgnet.com
AHP30B**(N,H)21
4HK06501025
AHP36C**(N,H)21
4HK06501025
4HK06501525
4HK06501825
AHP42C**(N,H)21
4HK06501025
4HK06501525
4HK06501825
AHP48D**(N,H)21
SHP48D**N21
4HK06501025
4HK06501525
4HK06501825
AHP60D**(N,H)21
SHP60D**N21
4HK06501025
4HK06501525
4HK06501825
4HK06502525
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.