561926-YTG-A-0410
Johnson Controls Unitary Products
29
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
CZH06011(C)
INDOOR COIL MODEL NO.
FC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1750
1850
1950
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
57.1 61.0 60.6 66.2 71.1 58.0 61.4 61.2 66.8 72.2 58.8 61.6 61.8 67.3 73.3
S.C.
58.1 53.7 44.6 44.7 36.4 59.0 54.7 46.2 45.8 36.6 59.8 55.6 47.7 46.8 36.8
K.W.
3.20 3.25 3.26 3.32 3.36 3.27 3.32 3.31 3.39 3.44 3.36 3.40 3.38 3.47 3.53
75
T.C.
55.3 58.5 58.0 63.4 68.2 56.0 58.8 58.4 63.9 68.9 56.7 59.1 58.7 64.3 69.5
S.C.
56.3 52.5 43.9 43.6 34.8 57.0 53.5 44.9 44.6 34.9 57.7 54.5 45.8 45.6 34.9
K.W.
3.69 3.74 3.74 3.80 3.86 3.77 3.80 3.79 3.87 3.93 3.85 3.88 3.86 3.95 4.01
85
T.C.
53.6 55.9 55.4 60.6 65.3 54.1 56.2 55.5 60.9 65.5 54.6 56.5 55.6 61.2 65.8
S.C.
54.5 51.3 43.2 42.5 33.1 55.1 52.4 43.6 43.5 33.1 55.6 53.4 44.0 44.4 33.0
K.W.
4.19 4.23 4.22 4.29 4.35 4.26 4.29 4.28 4.35 4.41 4.34 4.36 4.35 4.43 4.49
95
T.C.
51.8 53.3 52.8 57.8 62.4 52.2 53.6 52.7 58.0 62.2 52.6 53.9 52.5 58.2 62.0
S.C.
52.7 50.1 42.5 41.5 31.5 53.1 51.3 42.4 42.3 31.4 53.5 52.4 42.1 43.2 31.2
K.W.
4.69 4.71 4.70 4.77 4.84 4.76 4.77 4.76 4.83 4.90 4.83 4.85 4.83 4.91 4.97
105
T.C.
48.6 49.8 49.3 53.9 58.3 49.1 50.1 49.3 54.1 58.2 49.5 50.4 49.2 54.2 58.1
S.C.
49.5 47.7 40.5 39.8 30.1 50.0 48.7 40.7 40.6 30.1 50.4 49.6 40.8 41.3 30.1
K.W.
5.39 5.40 5.38 5.46 5.54 5.46 5.47 5.44 5.53 5.60 5.54 5.55 5.52 5.60 5.67
115
T.C.
45.6 46.3 46.0 50.2 54.3 46.1 46.7 46.0 50.3 54.3 46.5 47.1 46.0 50.4 54.2
S.C.
46.4 45.4 38.6 38.2 28.7 46.9 46.2 39.0 38.9 29.0 47.4 46.9 39.4 39.6 29.1
K.W.
6.06 6.07 6.04 6.13 6.22 6.14 6.14 6.11 6.20 6.28 6.23 6.22 6.19 6.28 6.36
125
T.C.
42.6 42.8 42.6 46.4 50.3 43.1 43.3 42.7 46.5 50.4 43.5 43.7 42.7 46.5 50.4
S.C.
43.4 43.2 36.6 36.6 27.4 43.9 43.7 37.4 37.2 27.8 44.3 44.1 38.1 37.8 28.2
K.W.
6.74 6.75 6.71 6.80 6.89 6.82 6.82 6.78 6.87 6.96 6.91 6.90 6.86 6.96 7.04
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
AV/SV*60
–
0.97
0.95
1.02
AHX60
–
0.97
0.98
1.04
F4FV060
–
0.96 0.96 0.99
MV20D
FC/MC/PC60D
0.96 0.96 0.99
MV20D
UC60D
0.96 0.96 0.99
MV20D
FC/MC62D
1.00 1.00 1.00
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*C16
FC/PC60C
0.96
0.92
1.00
T*(8,L)X*C20
FC/PC60C
0.97
0.92
0.99
T*(8,L)X*C20
FC/MC/PC60D
0.97
0.92
0.99
T*9X*C20
FC/PC60C
0.94
0.91
1.03
T*9X*D20
FC/MC/PC60D
0.97
0.95
0.99
T*9X*C20
FC/MC/PC60D
0.97
0.93
0.99
T*(8,L)X*C20
FC/MC62D
0.98
0.96
1.00
T*9X*C20
FC/MC62D
0.97
0.94
0.99
T*9X*D20
FC/MC62D
0.95
0.93
1.01
T*9X*D20
HD60
0.94
0.89
1.03
T*(8,L)X*C16
UC60C
0.94
0.90
1.00
T*(8,L)X*C20
UC60C
0.96
0.90
1.00
T*(8,L)X*C20
UC60D
0.96
0.90
1.00
T*9X*D20
UC60D
0.92
0.91
1.03
T*9X*C20
UC60C
0.95
0.91
0.99
T*9X*C20
UC60D
0.95
0.91
0.99
(Y*9C/T*9V)*D20 FC/MC62D
0.97 0.94 1.02
(Y*(8,L)C/T*8V)*C20
FC/PC60C
0.96 0.93 1.00
(Y*9C/T*9V)*C20 FC/PC60C
0.96 0.93 1.02
(Y*9C/T*9V)*D20 HC60
0.94 0.90 1.01
(Y*(8,L)C/T*8V)*C20
HD60
0.97 0.93 1.00
(Y*9C/T*9V)*C20 HD60
0.97 0.94 1.03
(Y*9C/T*9V)*D20 HD60
0.96 0.92 1.02
(Y*(8,L)C/T*8V)*C20
UC60C
0.94 0.89 1.00
(Y*9C/T*9V)*C20 UC60C
0.93 0.89 1.02
(Y*9C/T*9V)*D20 UC60D
0.94 0.89 1.01
Furnaces
Coils
T.C.
S.C.
KW