DESCRIPTION

Evaporator blower units are designed with two distinct mod-
ules to provide maximum application flexibility. The 25, 30
and 40 ton units are shipped as single packages with the
blower module mounted on top of the coil module, The
blower module can be repositioned in the field to meet almost
any installation requirement. Blower and coil modules for the
50 ton units are shipped separately to simplify handling.
These modules can be connected in the field with the same
flexibility as the smaller units.

The blower module includes the blower wheels and room for
a field-mounted motor and drive. The coil module includes
direct expansion coils, 2 in. throwaway filters, liquid line sole-
noid valves for both capacity reduction and pumpdown, ther-
mal expansion valves, distributors and a condensate drain
pan.

Every evaporator coil is pressurized with air to 325 psig and
leak tested under water. After the headers are brazed onto
the coil and the coil is installed in the unit, the coil is pressur-
ized with a combination of Refrigerant-22 and nitrogen to 150
psig for pressure testing and additional leak testing. After the
coil is evacuated and dehydrated, it is pressurized with a
holding charge of Refrigerant-22 for storage and/or shipping.

Steam coils, hot water coils, base sections, suspension hard-
ware, blower motors and drive packages are available as
field-installed accessories to provide additional application
flexibility.

These evaporator blowers, combined with condensing units,
provide years of quiet, efficient and dependable operation.
These units are manufactured under ISO 9001 Quality Sys-
tem Certification.

For Indoor Unit Installation details, please see document 035-
18496-000.

MODULAR DESIGN

These evaporator blowers can be arranged for a variety of air
discharge patterns in either the horizontal or vertical position.

Figure 2 shows three of the common installation arrange-
ments. Refer to the unit installation instructions for other pos-
sibilities.

Units may be bottom-supported or ceiling-suspended and
can be arranged to meet almost any space or duct require-
ments. Each unit is available with a choice of blower motors,
drive packages and other accessories to make them suitable
for most applications.

FACTORY-MOUNTED COMPONENTS

PART LOAD OPERATION These evaporator blowers have
multiple coils with pre-piped distributors, expansion valves
and solenoid valves. Field modifications are not required for
part load operations. Capacity reduction not only provides
economical operation, but also maintains more even temper-
ature and humidity levels in the conditioned space.

EASY SERVICE Serviceable expansion valves are provided
on every unit. These superior valves are factory-installed to
provide many years of trouble-free operation. If service is
required, it is not necessary to unbraze any joints.

PUMP-OUT Evaporator blowers include a solenoid valve for
non-recycling pump-out. When a cooling requirement in the
conditioned space is needed, the refrigerant is pumped into
the high side of the system before unit start-up.

ACCESSORIES

BASE SECTIONS (25, 30 and 40 ton only: Base sections
can be used to elevate units above the floor. If desired, out-
door air may be introduced through these sections by cutting
an access opening to accommodate the outdoor air duct con-
nection. These bases have a durable finish to match the
evaporator blower unit. They may have to be insulated for
certain applications.

SUSPENSION PACKAGES: These accessories can be used
to suspend horizontal units from above without interfering
with access to the unit. They can also be used for elevating a
floor-mounted unit (either horizontal or vertical) to provide
additional height for the installation of a trap at the conden-
sate drain connection. All suspension packages can be used
with vibration isolators.

HOT WATER COILS: Drainable water coils are available for
field installation between the blower and the coil modules of
both horizontal and vertical units. Since their casings match
the dimensions and the finish of the basic units, they become
an integral part of the unit after installation. The coils slide out
of their casings for easy installation. Coils have copper tubes
that have been mechanically expanded into aluminum fins.
Both headers are located on the same end of the coil. Coils
are leak-tested at 325 psig under water and dried before their
connections are capped for storage and shipping.

FIGURE 2:

UNIT INSTALLATION

Содержание 480

Страница 1: ...in up to 12 different positions and sus pended in various positions The LB600 can be positioned in up to 7 different arrangements and suspended also The LA LB line will give you the power to conditio...

Страница 2: ...4 STEAM COIL DIMENSIONS 14 15 BASE SECTION DIMENSIONS 14 16 BLOWER CURVE LA300 LB360 19 17 BLOWER CURVE LB480 21 18 BLOWER CURVE LB600 22 LIST OF TABLES Tbl Pg 1 STATIC RESISTANCES FOR UNIT ACCESSORIE...

Страница 3: ...n Options L Product Category L Air Handling Unit Cooling F Air Handling Unit Heat Pump A Product Identifier A R 22 Standard Efficiency 2 Pipe B R 22 Standard Efficiency 4 Pipe 300 Nominal Cooling Capa...

Страница 4: ...Each unit is available with a choice of blower motors drive packages and other accessories to make them suitable for most applications FACTORY MOUNTED COMPONENTS PART LOAD OPERATION These evaporator b...

Страница 5: ...erload protection DRIVE PACKAGES Different size pulleys and belts are available for each unit to provide a blower RPM range to meet almost any air delivery requirement Variable pitch motor pulleys can...

Страница 6: ...SUSPENSION ANGLES 1 BLOWER SECTION EVAP COIL SECTION CX 1 2 3 3 The same channels can be used in either position W hen used to support at vertical unit these channels should be cut to match the botto...

Страница 7: ...5 STEAM COIL 1 ROW 30 30 35 50 1 These weights should be added to each point load in table 3 2 This accessory can only be applied on units installed in the vertical position TABLE 5 UNIT BLOWER MOTOR...

Страница 8: ...3 8 12 4 1 3 16 2 78 6 B78 1LD0412 762 931 5 4 6 6 1 5 8 12 4 1 3 16 2 76 8 B75 TABLE 7 MOTOR OVERLOAD ELEMENTS1 1 These units are equipped from the factory with a cor rectly sized motor starter over...

Страница 9: ...05 495 585 675 LB480 1HW0407 75 12 800 348 447 547 646 746 16 000 389 500 611 722 833 19 200 425 547 668 790 911 LB600 75 16 000 389 500 611 722 833 20 000 436 561 686 810 935 24 000 473 610 746 882 1...

Страница 10: ...330 8 000 535 483 432 380 10 000 592 535 478 422 12 000 642 580 518 456 LB360 8 000 535 483 432 380 10 000 592 535 478 422 12 000 642 580 518 456 14 000 687 621 555 489 1 These capacities do not inclu...

Страница 11: ...ngs for piping and drain connections on following pages EVAPORATOR SECTION TABLE 12 UNIT DIMENSIONS LA300 LB360 LB480 MODEL A B C D E F G H J K L M LA300 100 1 8 95 5 8 33 1 4 36 5 8 74 2 1 2 18 7 8 1...

Страница 12: ...LB480 PIPING CONNECTIONS TABLE 13 UNIT CONNECTION SIZES Connection Entry Connection Size LA300 LB360 LB480 LB600 M2CX600 Suction Line Sys 1 2 1 8 1 1 8 1 3 8 2 1 8 Suction Line Sys 2 N A 1 1 8 1 3 8 2...

Страница 13: ...oup 13 FIGURE 11 UNIT DIMENSIONS LB600 FIGURE 12 LB600 PIPING CONNECTIONS END PANEL DETAIL 6 7 13 5 6 0 2 1 3 0 10 1 23 86 3 0 3 8 Liquid Line Sys 2 4 0 24 0 13 5 4 7 Liquid Line Sys 1 Condensate Drai...

Страница 14: ...AM COIL DIMENSIONS1 COIL MODEL UNIT MODEL DIMENSIONS A B C D E F G 1NF0454 LA300 LB360 100 1 8 37 7 8 4 3 8 18 3 8 1 1 2 2 2 1 2 1 Coils are field installed between the evaporator coil and the blower...

Страница 15: ...18 20 x 18 FILTERS THROWAWAY Size and Quantity Per Model Inches 16 x 20 x 2 6 20 x 20 x 2 3 20 x 22 x 2 16 x 25 x 2 6 20 x 25 x 2 10 6 3 25 x 25 x 2 6 Total Face Area feet2 34 7 42 6 53 1 OPERATING C...

Страница 16: ...hipping Weight lbs 1180 1180 1510 1572 Operating Weight lbs 1125 1146 1426 1640 Accessories Hot Water Coil 150 150 190 190 Steam Coil 160 160 Blower Motor 1750 RPM 117 5hp 117 5hp 120 7 5hp 120 7 5hp...

Страница 17: ...1 460 14 20 9 575 11 20 LB360 5 0 16 7 208 21 35 15 2 230 19 30 7 6 460 10 15 6 1 575 8 15 7 5 24 2 208 30 50 22 230 28 45 11 460 14 20 9 575 11 20 10 30 8 208 39 60 28 230 35 60 14 460 18 30 11 575 1...

Страница 18: ...ce units with steam or hot water coils are the only exception On these units the BHP must not exceed the nominal HP rating of the motor TABLE 20 FAN PERFORMANCE DATA 30 TON1 RPM CFM 10 000 11 000 12 0...

Страница 19: ...70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 LA300 LB360 Available external static pres sure for unit accessories and the duct system Internal unit resistance based on a dry coil...

Страница 20: ...e accessory static resistance table for additional information TABLE 22 FAN PERFORMANCE DATA 50 TON1 RPM CFM 16 000 18 000 20 000 22 000 24 000 SP2 BHP KW SP2 BHP KW SP2 BHP KW SP2 BHP KW SP2 BHP KW 6...

Страница 21: ...ternal unit resistance based on a dry coil plus 2 throwaway filters 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 0 8 0 6 0 4...

Страница 22: ...360 1 6 B H P 1 4 B H P 1 2 B H P 1 0 B H P 8 B H P 6 B H P 500 RPM 600 RPM 700 RPM 800 RPM 900 RPM 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 0 8 0 6 0 4 0 2 0 AvaIlable external static pres sur...

Страница 23: ...s of 18 gauge steel finished with baked enamel to provide a long lasting quality appearance Removable panels to provide easy access to the internal components for maintenance and service and A filter...

Страница 24: ...o change without notice Printed in U S A 036 21335 002 1 1102 Copyright by Unitary Products Group 2002 All rights reserved Supersedes 036 21335 001 B 0202 Unitary 5005 Norman Products York OK Group Dr...

Отзывы: