background image

835965-UIM-A-0112

Johnson Controls Unitary Products

7

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures 7-8. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

INDOOR CFM CONFIGURATION

For proper system operation the indoor CFM must be set properly. 

Refer to the Technical Guide for the outdoor unit for the recommended
air flow settings for each size condensing unit and matching indoor unit.

Set the cooling speed per the instructions for the air handler or furnace.
Verify the airflow. 

If installed as a communicating system (outdoor, indoor, and thermo-
stat), the system will automatically adjust to the optimal airflow settings.
These parameters can also be modified using the Touch Screen Com-
municating Control. Refer to the Touch Screen Communicating Control
owner’s manual for this procedure. Manual setting of the airflow on the
ID equipment is not necessary with the Touch Screen Communicating
Control.

 FIGURE 7:  

Communicating AC with Communicating Air Handler or 

Furnace

R

C

Y1

Y2

Touch Screen

Communicating

Control

Air Handler/Furnace

Communicating

Control

Air Conditioner

Communicating

Control

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

 FIGURE 8:  

Communicating AC with Non-Communicating Air Handler 

or Furnace using Communicating Interface Control

R

C

Y1

Y2

HUM

W2

DHUM

W

G

C

R

O

Y

Y2

HUM

W2

DHUM

W

G

C

R

O

Y

Y2

Touch Screen

Communicating

Control

Communicating

Indoor

Interface Control

Non-Communicating

Indoor Unit

Air Conditioner

Communicating

Control

Wire per

non-comm.

installation

manual

Assume that

connections

are from

thermostat

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

Содержание 18 Seer-CZH Series

Страница 1: ...m 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Display 19 Operational Fault Codes 20 Sensor or Switch Fa...

Страница 2: ...layer of hot air into the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoo...

Страница 3: ...raeder cap seal 3 Loosen and remove distributor cap seal 4 Install the thermal expansion valve to the orifice distributor assembly with supplied fittings Hand tighten and turn an additional 1 4 turn t...

Страница 4: ...ions The total system refrigerant charge is retained within the outdoor unit during shipping and installation The reusable service valves are pro vided to evacuate and charge per this instruction Seri...

Страница 5: ...the nitrogen source from the liquid fitting service port 9 Replace the Schrader core in the liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be...

Страница 6: ...ating Control 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness C...

Страница 7: ...M must be set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the inst...

Страница 8: ...SHU PXVW EH VHW WR 6 1 67 5 21 7 21 5 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8...

Страница 9: ...PSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 9 XPLGLILHU 2SWLRQDO 9 OHFWURQLF LU OHDQHU 2SWLRQDO LUVW 6WDJH RPSUHVVRU 20 9ROW RPPRQ 5 9ROW...

Страница 10: ...6 6 1 67 5 21 7 21 5 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 9ROW RPPRQ 5 9ROW...

Страница 11: ...se 2 Connection of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of t...

Страница 12: ...DHUM jumper to YES if humidistat is to be used G L 8 9 V F L 8 9 V PV 8 9 ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor Extern...

Страница 13: ...Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Modulating Heat Par...

Страница 14: ...1 Move HUMIDISTAT jumper to YES if humidistat is to be used FL9C FC9C PC9 ID MODELS External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optional External Humidistat Optional Open on Hu...

Страница 15: ...ith batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage...

Страница 16: ...Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve...

Страница 17: ...n Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover...

Страница 18: ...control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are conne...

Страница 19: ...ster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer...

Страница 20: ...o be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout c...

Страница 21: ...s started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch befo...

Страница 22: ...835965 UIM A 0112 22 Johnson Controls Unitary Products SECTION IX WIRING DIAGRAM FIGURE 18 Single Stage Wiring Diagram 2 4 Ton...

Страница 23: ...835965 UIM A 0112 Johnson Controls Unitary Products 23 FIGURE 19 Single Stage Wiring Diagram 5 Ton...

Страница 24: ...shed in U S A 835965 UIM A 0112 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 562156 UIM B 1211 501562 UIM B 1211 Johnson Controls Unitary Products 5005 York Drive Norman OK 73...

Отзывы: