York 18 Seer-CZH Series Скачать руководство пользователя страница 17

835965-UIM-A-0112

Johnson Controls Unitary Products

17

SECTION VI: SYSTEM CHARGE

1. The factory charge in the outdoor unit includes enough charge for

the unit, a 15 ft. line set and the smallest rated indoor coil match-up.
Some indoor coil matches may require additional charge. See tabu-
lar data sheet provided in unit literature packet for charge require-
ments.

2. Once line size/length and indoor coil adders have been figured,

weigh in this amount of charge by adding it through the liquid service
port while the indoor side of the system is still under a vacuum. The
vacuum that is on the indoor side of the system will allow you to add
most of the charge adder. If you are not able to add the full amount
then add the remainder after starting up the system to verify proper
subcooling. The subcooling charging method is explained further in
this section.

3. Release the refrigerant charge from the outdoor unit into the system.

Open both the liquid and vapor service valves at outdoor unit by
removing the plunger cap and with an allen wrench back out coun-
ter-clockwise until valve stem just touches the chamfered retaining
wall. ”PRECAUTIONS DURING BRAZING SERVICE VALVE”.

4. Replace plunger cap finger tight, then tighten an additional 1/12 turn

(1/2 hex flat). Cap must be replaced to prevent leaks.

5. Use the following subcooling charging method whenever additional

refrigerant is required for the system charge. A superheat charging
method is not suitable for TXV equipped systems.

Measurement Method

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly.

Subcooling Charging Method

This condensing unit must only be used with the matching thermostatic
expansion valve kit listed in the Tabular Data Sheet. This unit 

must 

be

charged during 

cooling single stage operation (Y1), second-stage

(Y1 & Y2) 

operation only

Charging should be matched per the 

subcooling chart located on the rating plate.
1. Set the system running in the 

cooling (Y1) or second-stage (Y1 &

Y2) 

cooling mode by setting the thermostat at least 6°F below the

room temperature.

2. Operate the system for a minimum of 15-20 minutes.

3. Refer to the Tech Guide for the recommended airflow and verify

thisindoor airflow (it should be about 400 SCFM per ton).

4. Measure the liquid refrigerant pressure P and temperature T at the

service valve.

5. Calculate the saturated liquid temperature ST from Table 1 "R-410A

Saturation Properties".

6. Subcooling temperature TC = Saturated Temperature (ST) - Liquid

Temp (T).

Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level. See Table 1
for R-410A saturation temperatures.
After disconnecting manifold gauge set check flare caps on service
ports to be sure they are leak tight. DO NOT OVERTIGHTEN (between
40 and 60 inch - lbs. maximum).
The “Total System Charge” must be permanently stamped on the unit
data plate.
Total system charge is determined as follows:
1. Determine outdoor unit charge from tabular data sheet.

2. Determine indoor coil adjustment from tabular data sheet.

3. Calculate the line charge using the tabular data sheet if line length is

greater than 15 feet.

4. Total system charge = item 1 + item 2 + item 3.

5. Permanently stamp the unit data plate with the total amount of refrig-

erant in the system.

SECTION VII: INSTRUCTING THE OWNER

Assist owner with processing warranty cards and/or online registration.
Review Owners Manual, provide a copy to the owner, and provide guid-
ance on proper operation and maintenance. Instruct the owner or the
operator how to start, stop, and adjust temperature setting.

The installer should also instruct the owner on proper operation and
maintenance of all other system components.

MAINTENANCE

1. Dirt should not be allowed to accumulate on the outdoor coils or

other parts in the air circuit. Clean as often as necessary to keep
the unit clean. Use a brush, vacuum cleaner attachment, or other
suitable means.

2. The outdoor fan motor is permanently lubricated and does not

require periodic oiling.

Refrigerant charging should only be carried out by a qualified air
conditioning contractor.

R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the Upright Posi-
tion.
 Always charge the system slowly with the tank in the upright
position.

DO NOT attempt to pump “Total System Charge” into outdoor unit
for maintenance, service, etc. This may cause damage to the com-
pressor and/or other components. the outdoor unit only has enough
volume for the factory charge, not the “Total System Charge”.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The pressure P and temperature T measured at the liquid
service port is 360 Psig and 93°F. From Table 1, the saturated tem-
perature for 360 Psig is 109°. The subcooling temperature TC =
109°-93°=16°F

Содержание 18 Seer-CZH Series

Страница 1: ...m 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Display 19 Operational Fault Codes 20 Sensor or Switch Fa...

Страница 2: ...layer of hot air into the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoo...

Страница 3: ...raeder cap seal 3 Loosen and remove distributor cap seal 4 Install the thermal expansion valve to the orifice distributor assembly with supplied fittings Hand tighten and turn an additional 1 4 turn t...

Страница 4: ...ions The total system refrigerant charge is retained within the outdoor unit during shipping and installation The reusable service valves are pro vided to evacuate and charge per this instruction Seri...

Страница 5: ...the nitrogen source from the liquid fitting service port 9 Replace the Schrader core in the liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be...

Страница 6: ...ating Control 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness C...

Страница 7: ...M must be set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the inst...

Страница 8: ...SHU PXVW EH VHW WR 6 1 67 5 21 7 21 5 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8...

Страница 9: ...PSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 9 XPLGLILHU 2SWLRQDO 9 OHFWURQLF LU OHDQHU 2SWLRQDO LUVW 6WDJH RPSUHVVRU 20 9ROW RPPRQ 5 9ROW...

Страница 10: ...6 6 1 67 5 21 7 21 5 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 9ROW RPPRQ 5 9ROW...

Страница 11: ...se 2 Connection of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of t...

Страница 12: ...DHUM jumper to YES if humidistat is to be used G L 8 9 V F L 8 9 V PV 8 9 ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor Extern...

Страница 13: ...Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Modulating Heat Par...

Страница 14: ...1 Move HUMIDISTAT jumper to YES if humidistat is to be used FL9C FC9C PC9 ID MODELS External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optional External Humidistat Optional Open on Hu...

Страница 15: ...ith batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage...

Страница 16: ...Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve...

Страница 17: ...n Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover...

Страница 18: ...control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are conne...

Страница 19: ...ster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer...

Страница 20: ...o be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout c...

Страница 21: ...s started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch befo...

Страница 22: ...835965 UIM A 0112 22 Johnson Controls Unitary Products SECTION IX WIRING DIAGRAM FIGURE 18 Single Stage Wiring Diagram 2 4 Ton...

Страница 23: ...835965 UIM A 0112 Johnson Controls Unitary Products 23 FIGURE 19 Single Stage Wiring Diagram 5 Ton...

Страница 24: ...shed in U S A 835965 UIM A 0112 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 562156 UIM B 1211 501562 UIM B 1211 Johnson Controls Unitary Products 5005 York Drive Norman OK 73...

Отзывы: