Unitary Products Group

FURNACE USER MAINTENANCE

Blower Care

Even with good filters properly in place, blower wheels and motors will
become dust laden after long months of operation. The entire blower
assembly should be inspected annually. If the motor and wheel are
heavily coated with dust, they can be brushed and cleaned with a vac-
uum cleaner. If the blower cannot be properly cleaned without removing
it from the furnace, then this service must be performed by a qualified
service agency.

The blower can be serviced/removed through the blower access panel
on the inside of the furnace. If there is a combustion air pipe installed
inside the furnace, it may have to be removed to access the blower
access panel. After the combustion air pipe is removed, it is easy to
remove the inside blower access panel by pushing it up, against a
spring, or removing the screws of the access panel. Blower is now
ready to be serviced through the opening.

If the blower has to be removed through the inside blower access panel,
then the top flange, blower door switch and bottom flange will also have
to be removed on some models, On some other models, top and bot-
tom angles will have to be removed to slide the blower out of the fur-
nace.

Air Filters

The filters should be checked every 3 months. On new construction,
check the filters every week for the first four weeks and every three
weeks after that, especially if the indoor fan is running continuously.
When replacing the filter(s), refer to Table 1 to be sure you install the
right size filter for your furnace. Dirty filters greatly restrict the flow of air
and may cause damage to the moving parts of the furnace. If the filters
become clogged the heat exchangers and blower motor could overheat
resulting in a potentially dangerous situation.

Never operate your furnace without a suitable air filter.

Use the following procedure to determine the filter size. 

1.

Measure the furnace width and use that measurement to deter-
mine the cabinet width.

A 17-1/2” wide cabinet is a “B” cabinet.

A 21” wide cabinet is a “C” cabinet.

A 24-1/2” wide cabinet is a “D” cabinet.

2.

After you determine the cabinet size and what return configuration
you have, look up the recommended filter size from Table 1.

Removing Filters

Some downflow furnaces have their filters located on the top of the fur-
nace in an external filter rack. To check filters you should:

1.

Follow the instructions to turn off the appliance before servicing.

2.

Filters are installed in the return air plenum above the blower
assembly. An “A” frame assembly supports the filters. Lift the filter
slightly and remove for service.

3.

Follow the instructions “HOW TO CLEAN YOUR FURNACE’S FIL-
TER”.

4.

Reverse the procedure to reinstall filters.

5.

Follow the operating instructions to place appliance in operation.

Externally Mounted Air Filters

Some installations may have the air filter in a rack attached to the cas-
ing of the furnace or placed in the return air duct. You can gain access
to the filter by pulling on the door or unscrewing the retaining screw,
then slide the filter(s) out of its channel. Replace throw away filter(s)
with the same size new filter(s). Throw away filter(s) may be replaced
with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as
described in the manufacturer instructions or as described below and
then re-installed.

How to Clean your Filter

High-velocity filters may be cleaned with a vacuum cleaner or washed
with a garden hose. Be sure to shake off excess water and allow filter to
completely dry before re-installing the filter.

To replace the filter after cleaning you must do the following:

1.

Slide filter into place.

2.

Snap the door on or place the door in position and tighten the
retaining screws, if provided.

3.

Make sure the door is secure to the end of the filter rack.

4.

For filter grilles, place the filter into the grilles, close the grille cover
and tighten the retaining screw.

Every time the filters are changed the following items should be visually
inspected:

Check combustion air and vent pipe for blockage or leakage.

Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.

Check the drain lines to make sure there are no cracks or leaks.

Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the fur-
nace and its components must be done by a qualified service pro-
fessional.

If, during the inspection of your furnace, you find any of the following
conditions:

Excessive amounts of dust and lint on components.

Damaged or deteriorated components or surfaces.

Leaks or blockage in the vent pipe passages.

Water on any surface inside or outside of the furnace.

Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the fur-
nace, and set thermostat to the desired temperature.

Motor Lubrication

The motors in these furnaces are permanently lubricated, and do not
require periodic oiling.

Before proceeding, be sure the area is well ventilated. Turn
the thermostat OFF. If the blower is running, wait until it
stops automatically. Turn OFF the gas and electrical power
supplies to the furnace. Check all metal parts and surfaces
to be sure they have cooled to room temperature before
you begin.

Make sure you DO NOT move the clip-on weight on the
indoor fan wheel when cleaning the wheel. This weight is
used to balance the wheel. Moving the weight will cause
the fan wheel to vibrate.

TABLE 1: 

Filter Sizes

Input

BTU/H (kW)

CFM 

(m

3

/min)

Cabinet 

Size

Top Return 

Filter in(cm)

60 (17.6)

1200 (34)

B

(2) 14 x 20 (36 x 51)

80 (23.4)

1200 (34)

B

(2) 14 x 20 (36 x 51)

80 (23.4)

1600 (45)

C

(2) 14 x 20 (36 x 51)

100 (29.3)

2000 (57)

C

(2) 14 x 20 (36 x 51)

120 (35.1)

2000 (57)

D

(2) 14 x 20 (36 x 51)

Содержание FC9V DH Series

Страница 1: ...deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone including cell phone in your...

Страница 2: ...nace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Examine the furnace casing for obvious signs of deterioration 6 Examine the burner flames to make sure they are in good adjust ment Refer to the pictorial sketch shown in Figure 2 as a compari son to th...

Страница 3: ...ructions 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove burner door 5 Move gas control switch to the OFF position Do not force 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to next step 7 Move gas control switch to t...

Страница 4: ...hed to the cas ing of the furnace or placed in the return air duct You can gain access to the filter by pulling on the door or unscrewing the retaining screw then slide the filter s out of its channel Replace throw away filter s with the same size new filter s Throw away filter s may be replaced with cleanable filter s at this time Cleanable filter s may be cleaned as described in the manufacturer...

Страница 5: ...nd the rear heat exchanger tubes Then vacuum loose the scale and dirt from each tube 9 Replace all components in reverse order Reconnect all wiring 10 Restore electrical power and gas supply to the furnace 11 Check furnace operation Cleaning the Secondary Heat Exchanger 1 Follow steps 1 7 under cleaning the Heat Exchanger 2 Remove the vent piping from the vent blower housing Disconnect the drain l...

Страница 6: ...The thermostat opens the R to Y and R to G circuits The Outdoor Unit is de energized The 60 second Blower Off Delay timing circuit is initiated After 60 seconds the Cool and EAC relays are de energized CONTROL BOARD Variable speed motors will adjust the motor speed in order to maintain the indoor fan CFM The control board is used to control the blower speed thus the CFM when the unit is operating ...

Страница 7: ... a higher speed will take 30 seconds and any ramp down to a lower speed or off will take 60 seconds Tap D is the normal profile best suited for most of the country where neither excessive humidity nor extremely dry conditions are the norm On a call for cooling the motor will ramp up to 63 of full capacity and will stay there for 90 seconds then will ramp up to full capacity At the end of the cooli...

Страница 8: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the flame is lost 5 times 4 recycles during the heating cycle This could be caused by low gas pressure or faulty gas valve The furnace will lock out for one hour and then restart 9 RED FLASHES Indicates re...

Страница 9: ...ucts Group 9 SECTION III REPLACEMENT PARTS LIST 70 34 57 2 59 61 54 5 26 68 8 52 62 12 7 25 27 13A 26 51 25 71 1 15 50 51 18 17 20 45 68 47 49 29 13 5 8 35 52 4 2 41 42 43 46 44 16 14 3 10 13 34 9 6 19 22 28 29 32 31 48 53 58 62 49 ...

Страница 10: ... 39 MISCELLANEOUS 40 41 RESTRICTOR COMBUSTION BLWR 42 GASKET COMBUSTION BLOWER 43 GASKET CONDENSATE PAN 44 GASKET CONDENSING COIL 45 GASKET GAS CONTROLS 46 GASKET UPPER COND PAN 2 Req d 47 GASKET COMBUSTION AIR TRANSITION 48 GROMMET MANIFOLD SEAL 49 PLUG WINDOW CLEAR 1 5 50 GROMMET MOTOR MOUNT 3 Req d 51 FERRULE MOTOR MOUNT 3 Req d 52 PAN CONDENSATE 53 ORIFICE BURNER Natural 45 54 TRAP CONDENSATE ...

Страница 11: ...ENT TERMINATION KIT 2 ALL MODELS 1CB0317 COMBUSTIBLE FLOOR BASE 17 1 2 CABINET 1CB0321 21 CABINET 1CB0324 24 1 2 CABINET 1TK0917 COIL TRANSITION KIT 17 1 2 CABINET 1TK0921 21 CABINET 1TK0924 24 1 2 CABINET REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete parts list refer to the contact information below Visit our website at www source1parts com for the follow...

Страница 12: ...271042 UUM A 0407 12 Unitary Products Group SECTION IV WIRING DIAGRAM FIGURE 8 Wiring Diagram ...

Страница 13: ...271042 UUM A 0407 Unitary Products Group 13 NOTES ...

Страница 14: ...271042 UUM A 0407 14 Unitary Products Group NOTES ...

Страница 15: ...271042 UUM A 0407 Unitary Products Group 15 NOTES ...

Страница 16: ...nly to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servicing 3 Damages resulting from accident abuse fire flood alteration or acts of God tampering altering defacing or removing the product serial number will serve to void this warranty 4 Damages resulting...

Отзывы: