129099-BUM-J-0112

Johnson Controls Unitary Products

7

SEQUENCE OF OPERATION

Continuous Blower

On cooling/heating thermostats with fan switch, when the fan switch is
set in the ON position, a circuit is completed between terminals R and G
of the thermostat. The blower motor is energized through the cool fan
terminal on the ignition control module.

Intermittent Blower - Cooling

On cooling/heating thermostats with fan switch, when the fan switch is
set in the auto position and the thermostat calls for cooling, a circuit is
completed between the R, Y and G terminals. The motor is energized
through the cool fan terminal and runs on the selected speed. The fan
off setting is fixed at 60 seconds for SEER enhancement.

Heating Cycle

When the system switch is set on HEAT and the fan is set on AUTO,
and the room thermostat calls for heat, a circuit is completed between
terminals R and W of the thermostat. When the proper amount of com-
bustion air is being provided, a pressure switch activates the ignition
control.

The ignition control provides a 30-second warm-up period. The gas
valve then opens for 10 seconds. If the flame is not detected within 2
seconds of the gas valve opening, the gas valve is shut off and a retry
operation begins. If the flame is lost for 2 seconds during the 10 second
stabilization period, the gas valve is shut off and a retry operation
begins. During a retry operation the ventor starts a 15 second inter-
purge and the ignitor warm-up time is extended to 27 seconds. If the
flame is established for more than 10 seconds after ignition, during a
retry, the control will clear the ignition attempt (retry) counter. If three
retries occur during a call for heat, the furnace will shut down for one
hour. If at the end of the one hour shut down there is a call for heat, the
furnace will initiate a normal start cycle. If the problem has not been cor-
rected the furnace will again lockout after three retries.

A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit will result in a disruption in the flame and be sensed within 0.8
seconds. The gas valve will de-energize and the control will begin a
recycle operation. A normal ignition sequence will begin after a 15 sec-
ond inter-purge. If during the three recycles the gas supply does not
return, or the fault condition is not corrected the ignition control will lock-
out for 60 minutes. 

During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the gas valve. When the power is restored,
the gas valve will remain de-energized and the ignition sequence will
immediately restart.

As the gas starts to flow and ignition occurs, the flame sensor begins its
sensing function. If a flame is detected during the 10 second flame sta-
bilization period the circulating blower will energize 30 seconds after the
gas valve opens (20 seconds after the flame stabilization period ends).
Normal furnace operation will continue until the thermostat circuit
between R and W is opened. When the thermostat circuit opens, the
ignition control is de-energized. When the ignition control is de-ener-
gized, the gas flow stops, and the burner flames are extinguished. The
ventor continues to operate for 15 seconds after the gas flow stops.

The blower motor continues to operate for the amount of time set by the
fan-off delay "Jumper" located on the ignition control board. Refer to
Figure 6. The heating cycle is complete, and the furnace is ready for the
start of the next heating cycle.

Hot Surface Ignition System

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be
open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.

 FIGURE 6: 

Furnace Control Board

HOT SURFACE IGNITION SYSTEM

Do not attempt to light this furnace by hand (with a match or any other
means). There may be a potential shock hazard from the components
of the hot surface ignition system. The furnace can only be lit auto-
matically by its hot surface ignition system.

Never bypass pressure switch to allow furnace operation. To do
so will allow furnace to operate under potentially hazardous con-
ditions.

Do not try to repair controls. Replace defective controls with
UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

FAN ON
ADJUSTMENT
JUMPER

HEA

T

XFMR

L1

COOL

TRANSFORMER

LINE VOLTAGE

BLACK - HIGH SPEED

RED -LOW SPEED

FAN OFF
JUMPER

NEUTRALS

FUSE 3A

Содержание DGAA

Страница 1: ...r read all sections of this manual and keep the manual for future reference SECTION I SAFETY 1 The furnace area must be kept clear and free of combustible mate rials gasoline and other flammable vapors and liquids 2 Insulating materials may be combustible The furnace must be kept free and clear of insulating materials The furnace area must be examined when installed in an insulated space or when i...

Страница 2: ...asses it over the hot furnace heat exchanger and circulates the warmed air through the ductwork to the house The furnace is equipped with the controls necessary for proper opera tion The various components referred to in this manual and on the fur nace rating plate are identified in Figure 1 WARRANTY AND RESPONSIBILITIES It is the sole responsibility of the home owner to make certain that the gas ...

Страница 3: ...ew yellow tips The burner flames for propane gas should appear blue with moderate yellow tips The flame should appear cylindrical in shape and should extend from the end of the burner into the heat exchanger Observing Burner Operation 1 Observe burner to make sure it ignites Observe color of flame On natural gas the flame will burn blue with appreciably yellow tips On Propane gas a yellow flame ma...

Страница 4: ... roof jack 4 Check the gas valve and line connections for leaks 5 Make any adjustments necessary for good operation SAFETY INFORMATION Read the Instructions Below Before Trying to Start the Furnace 1 This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 2 BEFORE OPERATING smell all around the applian...

Страница 5: ...re the area is well ventilated Follow instruction To turn off the appliance Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin 2 Remove the filter door 3 Remove the air filter by sliding it down the track The air filter will slide out of the rack 4 Replace throw away filter s with the same size new filter s Throw away filter s may be replaced with c...

Страница 6: ... doors Dis connect the gas supply piping at the union to permit removal of the entire burner and gas control assembly from the vestibule panel Use the wrench boss on the gas valve when removing or installing this piping 3 Unplug the igniter from the wire harness Disconnect sensor wires Identify and note the location of all leads for ease of reinstallation 4 Remove the screws holding the burner ass...

Страница 7: ...ly does not return or the fault condition is not corrected the ignition control will lock out for 60 minutes During burner operation a momentary loss of power for 50 milliseconds or longer will de energize the gas valve When the power is restored the gas valve will remain de energized and the ignition sequence will immediately restart As the gas starts to flow and ignition occurs the flame sensor ...

Страница 8: ...ure switch hose or faulty pressure switch 4 FLASH Limit Switch Open this indicates that a primary or auxiliary limit switch has opened its normally closed contacts With this fault code the control will operate the supply air blower and inducer This condition may be caused by dirty filter improperly sized duct system incorrect blower speed setting incorrect firing rate or faulty blower motor 5 FLAS...

Страница 9: ... through your qualified service installer or refer to the service center list in your booklet It is not recommended that the homeowner purchase install or replace any components of this furnace Contact your local contactor dealer or service provider for additional information 9 23 19 22 21 18 17 16 1 7 5 12 11 13 4 BURNER ORIFICE SEE CHART 3 2 14 10 15 6 CONTROL BOX DETAIL 6 20 ...

Страница 10: ... S1 37319806100 S1 37319806100 S1 37319806100 S1 37319806100 21 Plug Connector S1 02521192000 S1 02521192000 S1 02521192000 S1 02521192000 22 Capacitor Run See Note 3 Old see note 4 S1 02420063000 S1 02420063000 S1 02420063000 S1 02420063000 Capacitor New see note 4 S1 02435602000 S1 02435602000 S1 02435602000 S1 02435602000 Capacitor Units built on after 8 11 2008 S1 02435813000 S1 02435813000 S1...

Страница 11: ...gram Wiring 157953 157953 26 Strike Door S1 02118364000 S1 02118364000 27 Latch Door S1 02118365000 S1 02118365000 28 Housing Blower S1 37323864001 S1 37323864001 29 Gasket Combustion Air Box S1 01006900005 S1 01006900005 30 Gasket Burner S1 01006742000 S1 01006742000 31 Gasket Booster Assembly S1 01006900015 S1 01006900015 32 Gasket Heat Exchanger S1 01006900001 S1 01006900001 NOTE Not Shown New ...

Страница 12: ...129099 BUM J 0112 12 Johnson Controls Unitary Products SECTION IV WIRING DIAGRAM FIGURE 8 Wiring Diagram DGAA ...

Страница 13: ...129099 BUM J 0112 Johnson Controls Unitary Products 13 FIGURE 9 Wiring Diagram DGAH ...

Страница 14: ...e maintenance as set out in the operation and service instructions 10 Cleaning replacement of filters or any other routine maintenance as set out in the User s Information Maintenance and Service Manual 11 Replacement or cleaning of nozzles or orifices 12 Fuses either internal or external to the product 13 Excessive fuel or electricity consumption THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES E...

Отзывы: