background image

107273-UUM-C-0306

8

Unitary Products Group

To Replace Blower Wheel:

1.

 

Turn off all power to the burner before servicing.

2.

 Disconnect the burner motor wires.

3.

Remove the bolts securing the blower motor to the
housing.

4.

Remove the blower motor and wheel.

5.

Remove the existing wheel.

6.

As shown at right, slide the new blower wheel onto the shaft.

Slide blower wheel toward motor until the bottom rim is 1/8” from
the motor face.

Rotate the wheel until the set screw is centered on the flat of the
motor shaft.

Tighten the set screw to secure the wheel.

7.

Install the motor on the burner housing. Tighten the bolts. Recon-
nect the motor wires.

8.

Restore power, start the burner, and perform combustion tests.
Refer to “Set combustion with instruments.”

Check / Adjust Electrodes

Check the electrode tip settings. Adjust if necessary to comply with the
dimensions shown in Figure 10. To adjust, loosen the electrode clamp
screw and slide / rotate the electrodes as necessary. Securely tighten
the clamp screw when finished.

U

OIL FURNACE SEQUENCE OF OPERATION

The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.

Continuous Blower

DFAA cooling/heating thermostats have a fan switch that has an ON
and AUTO position. In the ON position the thermostat circuit is com-
pleted between terminals R and G. The motor will operate continuously.

DFAH models are heating only.

Intermittent Blower - Cooling

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling. The motor
will operate until the call for cooling is removed by the thermostat.

Heating Cycle

When the thermostat switch on a DFAA is set on HEAT and the fan is
set on AUTO, (DFAH has no manual fan operation), and there is a call
for heat, a circuit is completed between terminals R and W of the ther-
mostat. There is a 10 second delay to allow the burner motor to come
up to speed at which time the primary control provides power to the igni-
tion transformer, the solenoid valve on the oil pump opens and fuel oil
starts to flow to the nozzle, ignition occurs and the flame sensor begins
its sensing function. The blower motor will energize after the air temper-
ature at the fan control is above 110° F, if a flame is detected. Normal
furnace operation will continue until the thermostat circuit between R
and W is opened, which causes the ignition system and oil pump sole-
noid valve to de-energize and the burner flames to be extinguished.
The blower motor will operate until the fan switch is below 90° F. The
heating cycle is complete and ready for the start of the next cycle.

If the flame is not detected within 15 seconds of the primary control, it
will turn off the oil burner. There will be 3 retries before the primary con-
trol will lockout. If the flame is lost for 2 seconds during the 15 second
stabilization period, the ignition transformer is energized and a retry
operation begins. If flame is not detected within 15 seconds during the
retry, the primary control will go into recycle mode. Once the primary
control locks out the reset button must be pressed before an ignition
retry occurs.

A momentary loss of fuel oil, flame blowout, or a faulty cad-cell detector
will result in a disruption in the flame and be sensed within 1.0 seconds.
The oil pump solenoid valve will de-energize and the primary control will
begin a recycle operation. A normal ignition sequence will begin after a
15 second inter-purge. If during the three recycles the fuel oil supply
does not return, or the fault condition is not corrected the primary con-
trol will lock out. 

During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the primary control. When the power is
restored, the primary control will remain de-energized and the ignition
sequence will immediately restart.

TYPICAL PRIMARY CONTROL SEQUENCE OF 

OPERATION

1.

STANDBY - The burner is idle, waiting for a call for heat. When a
call for heat is initiated, there is a 2-6 second delay while the con-
trol performs a safe start check.

2.

VALVE-ON DELAY - If applicable, the ignition and motor are
turned on for a 15 second valve-on delay.

3.

TRAIL FOR IGNITION (TFI) - The fuel valve is opened, if applica-
ble. A flame should be established within the 15 second lockout
time (30 seconds on some models).

4.

LOCKOUT - If flame is not seen at the end of the TFI or is seen
during valve-on delay or postpurge, the control shuts down on
safety lockout and must be reset. If the control locks out three
times in a row, the control enters restricted lockout. Follow the
instructions on the front to reset it.

5.

IGNITION CARRYOVER - Once flame is established, the ignition
remains on for an additional 10 seconds to ensure flame stability. If
the control is wired for intermittent duty ignition, the ignition unit
stays on the entire time the motor is running.

6.

RUN - The burner runs until the call for heat is satisfied. The signal
is then sent to burner motor-off delay, if applicable, and it is shut
down and sent to standby.

7.

RECYCLE - If the flame is lost while the burner is firing, the control
shuts down the burner, enters a 60 second recycle delay, and then
repeats the above ignition sequence. If flame is lost three times in
a row, the control locks out to prevent cycling with repetitious flame
loss due to poor combustion.

 FIGURE 10: Electrode Settings

Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.

1/16"

Nozzle-to-tip
Spacing

5/32"
Gap

END VIEW

SIDE VIEW

5/16” above
nozzle center

Содержание DFAA

Страница 1: ...eath or prop erty damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL FUEL OIL Do not try to light any appliance Turn off the electric switch Immediately call your service technician DO NOT start the furnace If the control reset button has been pushed more than one time the chamber may be flooded with oil ...

Страница 2: ...ency Examine the furnace as outlined below in steps 1 6 before each heating season Use Figures 2 and 3 for visual reference 1 Examine the heat exchanger through a field installed access panel located on the supply air plenum Visually examine the exte rior sections of the vent combustion air piping and the connectors to be sure that they are physically sound without holes or exces sive corrosion 2 ...

Страница 3: ...ot try to light the burner by hand 2 BEFORE OPERATING smell all around the appliance area for fuel oil Be sure to smell next to the floor because fuel oil is heavier than air and will settle on the base of the chamber Look for any oil leaks around the base of the furnace 3 Use only your hand to turn the manual oil line valve attached the pump to the on position Never use tools If the valve will no...

Страница 4: ... you must do the following 1 Before proceeding be sure the area is well ventilated Follow instruction To turn off the appliance Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin 2 Remove the louvered blower door by pulling on the indentated handles on both sides of the bottom of the door 3 Remove the air filter by sliding them down The air filter w...

Страница 5: ...l safety lockout timing Check ignition system for proper operation Inspect the vent system for soot accumulation or other restriction Clean the appliance thoroughly according to the manufacturer s recommendations TABLE 1 Filter Sizes Blower Door Return inches cm 2 16 x 20 2 41 x 51 Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel This weight is used to b...

Страница 6: ...he connector tube assembly 6 Push the nozzle assembly in at the flare fitting end until the assembly is inside the burner housing Be sure to keep the flare end at a slight angle upwards to avoid dripping oil on the combus tion air fan below 7 Slide the nozzle assembly up and out of the burner assembly Take extra precautions with the electrodes when removing the nozzle assembly so the insulators do...

Страница 7: ...coupling Do not force the pump shaft on to the coupling 22 Reinstall the nozzle assembly and tighten the assembly to the burner housing with the splined nut 23 Reconnect the connector tube assembly and tighten the flare fit ting 24 Check the transformer spring contacts If worn replace 25 Push the transformer up and forward checking to make sure the springs are touching the electrode rods 26 Put th...

Страница 8: ... 15 seconds of the primary control it will turn off the oil burner There will be 3 retries before the primary con trol will lockout If the flame is lost for 2 seconds during the 15 second stabilization period the ignition transformer is energized and a retry operation begins If flame is not detected within 15 seconds during the retry the primary control will go into recycle mode Once the primary c...

Страница 9: ...p and oil valve closes TROUBLESHOOTING AND MAINTENANCE IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting pro cedures IMPORTANT This control contains no field serviceable parts Do not attempt to take it apart Replace entire control if operation is not as described To completely troubleshoot an oil burner installati...

Страница 10: ... mary control by using the following equipment 1 Screwdriver 2 Voltmeter 0 to 150 VAC range 3 Insulated jumper wire with both ends stripped 4 Follow the oil burner operation and oil burner control troubleshoot ing steps in Tables 5 and 6 TABLE 4 Cad Cell Resistance When Sensing Flame Flashes Cad Cell Resistance in Ohms 1 Less than 400 2 More than 400 and less than 800 3 More than 800 and less than...

Страница 11: ... motor Flashes indicator light at 1 2 second on 1 2 second off Depress reset button to return to power up sequence c When flame is detected Carry Over period begins 5 Control enters Ignition Carry Over period continues to spark for 10 to 30 seconds a Turns on indicator light b If flame is lost and lockout time has not expired R7184 returns to Trial for Ignition period c If flame is lost and lockou...

Страница 12: ...oltage should be 120 VAC 3 Check indicator light with burner off no call for heat no flame Indicator light is on Cad cell or controller is defective sees external light or connections are shorted Go to step 4 Indicator light is off Go to step 5 4 Shield cad cell from external light Indicator light turns off Eliminate external light source or permanently shield cad cell Indicator light stays on Rep...

Страница 13: ...onnect line voltage power and close line switch d Start burner Burner locks out Go to Step 11 Burner keeps run ning System is okay 11 Check cad cell a Disconnect line voltage power and open line switch b Remove existing cad cell and replace with new cad cell c Disconnect all wires from ther mostat terminals to be sure there is no call for heat d Reconnect line voltage power and close line switch e...

Страница 14: ...107273 UUM C 0306 14 Unitary Products Group SECTION III WIRING DIAGRAM OIL FIRED FURNACE FIGURE 13 Wiring Diagram for DFAA Oil Fired Furnace ...

Страница 15: ...107273 UUM C 0306 Unitary Products Group 15 FIGURE 14 Wiring Diagram for DFAH Oil Fired Furnace ...

Страница 16: ...ase of malfunction For this reason it is never practical to assume that the furnace will operate unattended for a long period of time especially if there is a possibility of damage to your property because of freezing So if you plan to be away from home arrange for someone to check your house every day DESCRIPTION This furnace shall be installed in the downflow position Figure 17 shows a typical m...

Страница 17: ...front panels Follow the operating instructions to place the furnace in operation Observing Burner Operation 1 Observe burner to make sure it ignites Observe color of flame On natural gas the flame will burn blue with appreciably yellow tips On Propane gas a yellow flame may be expected If flame is not the proper color call a qualified service technician for service 2 Let furnace heat until blower ...

Страница 18: ...e some gas is heavier than air and will settle on the floor C Use only your hand to push the gas control switch to the on position Never use tools If the switch will not operate by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified servi...

Страница 19: ...ed with dust they can be brushed and cleaned with a vac uum cleaner If the blower cannot be properly cleaned without removing it from the furnace then call a qualified service agency Only a qualified service agency can perform this service Motor Lubrication The motors in these furnaces are permanently lubricated and do not require periodic oiling WARRANTY AND RESPONSIBILITIES It is the sole respon...

Страница 20: ... wrench boss on the gas valve when removing or installing this piping Refer to Figure 18 3 Unplug the black and white line voltage wires at the quick connec tor terminals Identify and note the location of all leads for ease of reinstallation 4 Unplug the red and black wires that are connected to the T T terminals on the primary control These wires can be disconnected at the quick connect terminals...

Страница 21: ...107273 UUM C 0306 Unitary Products Group 21 SECTION VI WIRING DIAGRAM GAS CONVERSION BURNER FIGURE 20 Wiring Diagram for DFAA Gas Conversion Burner ...

Страница 22: ...107273 UUM C 0306 22 Unitary Products Group FIGURE 21 Wiring Diagram for DFAH Gas Conversion Burner ...

Страница 23: ...THE 30 SECOND PREPURGE AND 8 SECOND SAFE START CHECK CYCLE 3 CHECK FOR 120 VAC AT GAS VALVE TERMINALS REPLACE PRIMARY IGNITION CONTROL CHECK ELECTRICAL WIRING AND CONNECTIONS BE SURE LEADS ARE ON CORRECT GAS VALVE TERMINALS 4 MAKE SURE LEADS ARE ON THE CORRECT GAS VALVE 5 CHECK FOR CORRECT MANIFOLD PRESSURE 6 REPLACE GAS VALVE OK OK OK OK OK NO NO NO OK OK OK NO NO NO OK OK OK OK OK OK 1 CHECK THE...

Страница 24: ...GNITION ELECTRODE ROD 6 REPLACE PRIMARY IGNITION CONTROL REPLACE PRIMARY IGNITION CONTROL CHECK THE FLAME SENSING CIRCUIT FOR 1 GROUNDED FLAMEROD 2 DAMAGE TO FLAMEROD LEAD INSULATION NOTE MAKE SURE THE FLAMEROD CIRCUIT AND OR PRIMARY CONTROL IS MOISTURE FREE 1 RESET CONTROL MOTOR STARTS AFTER 30 SECOND PREPURGE CYCLE AND 8 SECOND SAFE START CHECK MOTOR CONTINUES TO RUN BUT FLAME IS NOT ESTABLISHED...

Страница 25: ...CYCLE FLAME IS ESTABLISHED A STABLE MICROAMPERE CURRENT OF 8 OR MORE IS REQUIRED FOR DEPENDABLE OPERATION 4 MICROAMPERE READING IS LESS THAN 8 OR UNSTABLE 1 CHECK FOR PROPER THERMOSTAT INSTALLATION AND LOCATION 2 CHECK THERMOSTAT HEAT ANTICIPATOR FOR CORRECT SETTING 3 CHECK LOW VOLTAGE CIRCUIT FOR BAD WIRING ELECTRICAL CONNECTIONS AND OR SWITCHES 4 CHECK LINE VOLTAGE CIRCUIT FOR BAD WIRING ELECTRI...

Страница 26: ...06 26 Unitary Products Group SECTION VII OIL BURNER REPAIR PARTS LIST 1 3 2 2 3 2 12 9 11 10 8 7 6 5 4 13 HEAT COOL DFAA HEAT ONLY DFAH CONTROL BOX DETAIL 15 1 14 16 17 DFAA066BBTA DFAH066BBSA DFAA084BBTA DFAH084BBSA ...

Страница 27: ...witch System 7681 3301 7681 3301 1 5 Transformer 115 24V 40 VA 1 6 Filter 16x20x1 2 Req d 1214 2511 1214 2511 1 7 Panel Door Upper 7900 7631 7900 7631 1 8 Panel Door Lower Short 7900 7671 7900 7671 1 9 Motor 024 31948 000 024 31949 000 1 10 Plug Connector 025 21192 000 025 21192 000 1 11 Capacitor Run 7 5MFD 370V 024 20045 000 1 12 Wheel Blower 026 19654 003 026 19654 003 1 13 Fan Relay Blower 1 1...

Страница 28: ...0 026 39212 000 2 11 Motor Oil Burner 026 39213 000 026 39213 000 2 12 Blower Wheel 026 39214 000 026 39214 000 2 13 Coupling 026 33072 000 026 33072 000 2 14 Primary Ignition Control Valve On Delay 026 39215 000 026 39215 000 2 15 Electrical Box 026 39216 000 026 39216 000 2 16 Igniter 026 39217 000 026 39217 000 2 17 Cad Cell Detector 026 39218 000 026 39218 000 2 18 Flange Gasket 026 39219 000 ...

Страница 29: ...19 49 9 27 27 46 26 25 16 14 20 8 51 56 57 53 42 1 43 6 38 31 34 33 32 41 16 30 40 40 40 39 35 36 37 28 6 28 29 6 4 10 11 5 17 55 6 6 6 15 23 24 12 45 MINIMUM INPUT 66 000 BTU HR MAXIMUM INPUT 84 000 BTU HR ELECTRICAL POWER SUPPLY 115V 60HZ 1 FUELS NATURAL L P GAS 3 5 W C MOUNTING FIXED FLANGE f BURNER MODELS SC80 C ...

Страница 30: ...CYCLER 1 P 26 101243 001 CONTROL IGN H S87K1008 DI 1 P 27 100603 008 SCREW HXSLT 8 18 X 1 25 2 P 28 100603 001 SCREW 6 20 X 375 4 P 29 101154 001 RING BLOWER MOUNTING 1 P 30 63888 001 TUBE AIR INLET YORK 1 M 31 63887 001 DECAL AIR SETTING YORK 1 P 32 63892 001 TUBE DUCT OUTSIDE AIR 7 1 2 LG 1 P 33 63885 001 SHAFT BUTTERFLY DISC AIR 1 P 34 63884 001 DISC BUTTERFLY AIR 1 P 35 63883 001 ELBOW 1 1 2 S...

Страница 31: ...107273 UUM C 0306 Unitary Products Group 31 NOTES ...

Страница 32: ...form normal or routine maintenance as set out in the operation and service instructions 10 Cleaning replacement of filters or any other routine maintenance as set out in the User s Information Maintenance and Service Manual 11 Replacement or cleaning of nozzles or orifices 12 Fuses either internal or external to the product 13 Excessive fuel or electricity consumption THIS WARRANTY IS IN LIEU OF A...

Отзывы: