<1. Introduction>
1-3
IM 01C50T01-02EN
1.1 Matching of DD and
Instruments
Before using a HART configuration tool, confirm
that the DD for the instrument is installed in the
configuration tool.
Device type:
Device Revision:
DD Revision:
The device revision of the transmitter and DD can
be confirmed as shown below. If the correct DD is
not installed in the configuration tool, download it
from the official web site of FieldComm Group.
(1) Confirmation of device revision for the
transmitter
• Confirmation on integral indicator
(A case of integral indicator code D is specified)
Refer to the section 2.1
• Confirmation by using HART configuration tool
a) Connect the configuration tool to the
transmitter.
b) Confirm numerical number displayed on “Fld
dev rev” column.
• Procedure to call up the display
Device Setup → Detailed Setup → Device
Information → Revision#’s → Fld dev rev
(2) Confirmation of device revision for the
configuration tool
Confirm the device revision from the installed
DD file name according to the procedure
provided for the configuration tool.
The first two digits indicate the device revision
and the next two digits indicate the DD revision.
0201.XXX
DD revision
Device revision
NOTE
Device revision of DD file is given in hexadecimal.