<4. Diagnostics >
4-5
IM 01C50T01-02EN
(4) TC Short (only for YTA710)
This function detects any short circuit at TC
sensors. When the current is applied and the
resistance of a sensor is (S1 RP23, S2 RP43
in Sensor Diagnostics Information) below the
threshold, the function outputs the Short alarm.
Parameter setting: Set the thresholds at “S1 TC
Short Thrshld” and “S2 TC Short Thrshld” (for
the 2-input specification).
Alarm output: When the resistance is below
the threshold, the function outputs the alarm
of Sensor1 short (AL.12) or Sensor2 short
(AL.13).
• Procedure to call up the display
Device setup → Diag/Service → Diagnostics →
Sensor Diag → Sensor Diag Setting → S1(2)
TC Short Thrshld
Set thresholds.
NOTE
Release the Device Status mask in order to
output the Sensor1 (2) Short alarm. (Initial value
is set in the mask)
(5) RTD Short (only for 3-wire and 4-wire, only
for YTA710)
This function detects any short circuit at the sensor
during the RTD or Ohm measurement. When the
resistance of the Sensor (S1 RC1 to S1 RC4, S2
RC3, S2 RC4 in Sensor Diagnostics Information)
is below the threshold, the function outputs a short
circuit alarm.
Parameter setting: Not necessary
Alarm output: When the resistance is below the
threshold, the function outputs the alarm of
Sensor1 short or Sensor2 short.
NOTE
• Release the Device Status mask in order to
output the Sensor1 (2) Short alarm. (Initial
value is set in the mask)
• In case of 3 wire RTD or ohm connection,
if actual connection and connection setting
is imbalance, unforeseen alarm may be
generated.
(6) RTD Corrosion (only for 3-wire and 4-wire,
only for YTA710)
This function detects any corrosion at the terminals
and along the measurement cables. When the
resistance of the terminals and cables (S1 RC1 TO
S1 RC4, S2 RC3, S2 RC4 in sensor diagnostics
information.) is above the threshold, the function
outputs a corrosion alarm (AL.14 and AL.15).
Parameter setting:
Device Setup → Diag/Service → Diagnostics
→ Sensor Diag → Sensor1(2) Diag setting →
S1(S2) RTD Corr Thrshld,
NOTE
Release the Device Status mask in order to
output the Sensor1 (2) Corrosion alarm. (Initial
value is set in the mask)
(7) Sensor Drift
When the difference between Sensor1 and Sensor2
temperatures becomes larger than the threshold,
this function outputs an alarm. This indicates
that there is some problem at either Sensor1
or Sensor2. The function can be enabled when
Sensor type is set to TC and RTD.
Parameter setting: Set a threshold for the
temperature difference between Sensor1
and Sensor2 at Sns Drift thrshld. When the
threshold is 0.0, the function is not enabled.
Alarm output: When the temperature difference is
larger than the threshold, the function outputs
the alarm of Sensor Drift.
• Procedure to call up the display
Device setup → Diag/Service → Diagnostics →
Sensor Diag →Sensor Diag Setting → Sns Drift
Thrshld
Set thresholds.
NOTE
Release the Device Status mask in order to
output the Sensor Drift alarm. (Initial value is set
in the mask)