General
Specifications
n
GENERAL
The Model SISD Isolator accepts a 1 to 5V DC input
signal. The input signal is isolated from the power
supply common and from the Isolator output signal.
There are two outputs: 1 to 5V and 4 to 20mA DC.
With the VJ77 Parameter Setting Tool you can do the
following:
· Read/write all parameters at once
· Save read parameters to a file
· Copy parameters to other devices of the same model
and suffix code (only with style code R or S).
n
STANDARD SPECIFICATIONS
Input Signal
Input: 1 to 5V DC(one input)
Input Resistance: 1 MΩ
Square Root Characteristic
Computation: E = 2 E – 1 + 1
E : Output Signal from computation function, E : Input Signal
0
0
1
Lowcut Function: At E
1
is less than 1% , the output is
proportional to input.
Output Signals
Output:
1 to 5V DC(one output), 4 to 20 mA
DC(one output)
Load Resistance: At least 2 kΩ(1 to 5 V DC output),
up to 750 Ω (4 to 20 mA DC output)
BRAIN Communication Function
Setting of each parameter, monitoring of input/output
values, and configuration by a PC (VJ77), JHT200
Handy Terminal* or BT200 BRAIN Terminal*.
*:
When connecting a PC (VJ77) or the JHT200
Handy Terminal, the adapter for modular-jack
(model E9786WH) is required. When using the
BT200 BRAIN Terminal of YOKOGAWA Electric
Corporation, the communication cable of 5-pin
connector type (model F9182EE) and the adapter
for modular-jack (model E9786WH) are required.
n
MOUNTING AND APPEARANCE
Mounting: Rack mounting.
Wiring
Signal Wiring: ISO M4 size (4mm) screws on
terminal block.
Power and Ground Wiring
100 V version: JIS C 8303 two-pin plug with
earthing contact(IEC A5-15, UL458)
Cable length: 300 mm
Power supply terminal type (option
code /TB)
220 V version: CEE 7 VII(CENELEC standard)
plug (option code /A2ER).
Model SISD (Style S)
Isolator
GS 01B04N01-02E
GS 01B04N01-02E
©Copyright Jan. 1983 (YK)
13th Edition Jan. 2021 (YK)
Cable length: 300 mm
Power supply terminal type (option
code /A2TB)
External Dimensions: 180 (H)× 48(W)× 300 (D)
Depth behind panel(mm)
Weight:
1.7 kg (including rack-mounting case)
n
STANDARD PERFORMANCE
Accuracy: ±0.2% of span(±0.5% of span with square
root characteristic)
Maximum Power Consumption:
70 mA with 24 V DC supply,
5.0 VA with 100 V AC supply,
6.0 VA with 220 V AC supply.
n
POWER SUPPLY AND ISOLATION
Power Supply Rated Voltage:
100 V version:
24-110 VDC , -10 %, +10 %, 100 mA
100-120 VAC , -10 %, +10 %, 50/60 Hz, 7.0 VA
220 V version:
135-300 VDC , -10 %, +10 %, 15 mA
200-240 VAC , -10 %, +10 %, 50/60 Hz, 10.0 VA
Power Supply Input Voltage: AC/DC both usage
100 V version: DC drive 20 to 130 V, no polarity
AC drive 80 to 138 V, 47 to 63 Hz
220 V version: DC drive 120 to 340 V, no polarity
AC drive 138 to 264 V, 47 to 63 Hz
Insulation Resistance
Between I/O terminals and Ground:
100 MΩ/500 V DC
Between Power and Ground:
100 MΩ/500 V DC.
Dielectric Strength
Between I/O terminals and Ground:
500 V AC for 1 minute.
Between Power and Ground:
1000 V AC for 1 minute(100 V version)
1500 V AC for 1 minute(220 V version)
Between Input terminal and Output terminal:
1000 V AC for 1 minute
Содержание YS80 Series
Страница 1: ...User s Manual Y okogawa Electric Corporation IM 01B04N01 02E 10th Edition Model SISD Style S Isolator...
Страница 2: ......
Страница 4: ...Blank...
Страница 12: ...Blank...
Страница 16: ...Blank...
Страница 28: ...Blank...
Страница 34: ...Blank...
Страница 40: ......