![YOKOGAWA YFGW410 Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/yokogawa/yfgw410/yfgw410_user-manual_3527281065.webp)
<9. Connection Device Type>
9-18
IM 01W03D02-01EN
F0906.ai
AI algorithm
PV AI Publish
Scale
O/S
Auto
Simulate
Mode.Target
Switch
Simulate Value
Operator
Input
Modbus
Device
Range
Scale
PV
PV
Mode and PV.Status
handling
Transducer
Value
Figure 9.2
Example schema of analog input object
Table 9.5
Diagnostic Status Detail
Bit
Diagnostic Status Detail
Description
Diagnostic
status
assignment bit
NAMUR
NE107
Category
*
Diagnostic Status Detail.1
31
ADAPTER FAIL
FN310 failure
Bit27
F
30
ANTENNA FAIL
FN110 failure
Bit27
F
28
INTERNAL BUS FAIL
Communication failure between FN110 and
FN310
Bit27
F
27
SENSOR FAIL
Disconnection or communication error,
between the Modbus device and FN310
Bit26
F
15
DEVICE CONNECTION ERR
Connection error between the Modbus
device and FN310
Bit25
C
9
LOWBAT_ALM
Low remaining battery voltage
Bit19
M
8
CRITICAL LOWBAT
Low remaining battery voltage
Bit20
M
7
ADAPTER TEMP HI
FN310 temperature is above +85°C
Bit22
O
6
ADAPTER TEMP LO
FN310 temperature is below -40°C
Bit22
O
5
ANTENNA TEMP HI
FN110 temperature is above +85°C
Bit22
O
4
ANTENNA TEMP LO
FN310 temperature is below -40°C
Bit22
O
Diagnostic Status Detail.2
31
AI1 OUT OF SERVICE
AI1 O/S Mode
Bit24
C
30
AI2 OUT OF SERVICE
AI2 O/S Mode
Bit24
C
29
AI3 OUT OF SERVICE
AI3 O/S Mode
Bit24
C
28
AI4 OUT OF SERVICE
AI4 O/S Mode
Bit24
C
15
AI1 SIMULATION ACTIVE
AI1 Simulate Mode
Bit17
C
14
AI2 SIMULATION ACTIVE
AI2 Simulate Mode
Bit17
C
13
AI3 SIMULATION ACTIVE
AI3 Simulate Mode
Bit17
C
12
AI4 SIMULATION ACTIVE
AI4 Simulate Mode
Bit17
C
Diagnostic Status Detail.3
31
DEVICE IMPEDANCE1 TOO HIGH Input1 impedance value of SENCOM is high
Bit5
M
30
DEVICE IMPEDANCE1 TOO LOW Input1 impedance value of SENCOM is low
Bit5
M
29
DEVICE IMPEDANCE2 TOO HIGH Input2 impedance value of SENCOM is high
Bit5
M
28
DEVICE IMPEDANCE2 TOO LOW Input2 impedance value of SENCOM is low
Bit5
M
*: NAMUR NE 107 “Self-Monitoring and Diagnosis of Field Devices”