5.2 Setting Jumper
The SKYD is provided with the following jumpers.
Other SKYDs excluding the SKYD-x04 are not provided with the ALM1, 2 jumpers.
(Can be set by using the JHT200 Handy Terminal.)
Jumper Code
Jumper Name
Except SKYD-x04
SKYD-x04
W.P.
Parameter Write Protect
Available
Available
ALM1
Alarm 1 action setting jumper
Not available
Available
ALM2
Alarm 2 action setting jumper
(except SKYD-10x)
Not available
Available
• Parameter Write Protect jumper
When this jumper is set to ON, changing of parameters by the key switches and Handy
Terminal is disabled. “LOC” will be displayed on the display setter if the “→” switch is
pressed with the SP1 or SP2 parameter displayed on the display setter.
To cancel the “LOC” display and return to the previous display, press any key.
• Alarm action setting jumper
This jumper is for setting the direction of alarm action.
The table below shows the relationship between direction of alarm action and direction of
relay action.
Direction of alarm relay action: De-energized at normal operation
ALMn
Direction of alarm action
Input value < Set point
Set point < Input value
DIR
Direct (high-limit alarm)
Output relay de-energized
Output relay energized
RVS
Reverse (low-limit alarm)
Output relay energized
Output relay de-energized
Direction of alarm relay action: Energized at normal operation
ALMn
Direction of alarm action
Input value < Set point
Set point < Input value
DIR
Direct (high-limit alarm)
Output relay energized
Output relay de-energized
RVS
Reverse (low-limit alarm)
Output relay de-energized
Output relay energized