Finishing the Settings

10.

When 

Setting complete

 screen is displayed, do either of the following:

Press the 

 key to set other alarms.

To finish setting the alarm, press the 

ESC

 key.

02-02 CH/level 1

Setting complete

11.

Hold down the 

MENU

 key for 3 seconds to return to Operation mode.

Explanation

In step 7, you can select an alarm type on the table below.

Type

Description

H

High Limit Alarm: An alarm occurs when the input value exceeds the alarm value.

L

Low Limit Alarm: An alarm occurs when the input value falls below the alarm value.

h

Difference High Limit Alarm*: An alarm occurs when the difference in the input values of
two channels is greater than or equal to the specified value.

l

Difference Low Limit Alarm*: An alarm occurs when the difference in the input values of
two channels is less than or equal to the specified value.

R

High Limit on Rate-of-Change Alarm**: The rate-of-change of the measured values is
checked over a certain time (interval). An alarm occurs if the rate-of-change of the
measured value in the rising direction is greater than or equal to the specified value.

r

Low Limit on Rate-of-Change Alarm**: The rate-of-change of the measured values is
checked over a certain time (interval). An alarm occurs if the rate-of-change of the
measured value in the falling direction is greater than or equal to the specified value.

T

Delay High Limit Alarm***: An alarm occurs when the measured value remains above
the alarm value for a specified time period (alarm delay period).

t

Delay Low Limit Alarm***: An alarm occurs when the measured value remains below
the alarm value for a specified time period (alarm delay period).

*

Can be specified on channels set to delta computation.

** You must set the interval in Basic Setting mode.
*** You can select T or t when the alarm delay function is enabled in Basic Setting mode.

Setting the Input Range and Alarm on Measurement Channels

Содержание VigilantPlant mR20000

Страница 1: ...Operation Guide Yokogawa Electric Corporation IM 04P02B01 02E 2nd Edition Models 437101 437102 437103 437104 437106 437112 437118 437124 R20000 Recorder 4 P 2 B 1 0 2 E 0 2...

Страница 2: ...ens Pen Model 30 Installing Replacing the Plotter Pen Pen Model 31 Installing Replacing the Ribbon Cassette Dot Model 31 Checking or Setting the Date Time 33 Setting the Input Range and Alarm on Measu...

Страница 3: ...Standards and EMC Standards This recorder conforms to IEC safety class I provided with terminal for protective grounding Installation Category II Measurement category II CAT II and EN61326 1 EMC stand...

Страница 4: ...e Software YOKOGAWA makes no warranties regarding the software accompanying this product except those stated in the WARRANTY that is provided separately Use the software on a single PC You must purcha...

Страница 5: ...be specified simultaneously on the dot models A4 and F1 cannot be specified simultaneously on the pen models 3 C3 and C7 cannot be specified simultaneously 4 H2 and N2 cannot be specified simultaneou...

Страница 6: ...cs 3 pcs 3 pcs 250 0 1 100 0 1 10 0 1 250 0 1 100 0 1 10 0 1 B9573AN 1 1 1 1 1 1 1 2 1 1 1 1 1 1 B9906JA B9902AM B9902AN B9902AP B9902AQ B9902AR B9900BX 415920 415921 415922 438920 438921 438922 Note...

Страница 7: ...Checking the Version Number You can check the version number on the System display The System display cannot be shown at the factory default condition First register the System display to the display...

Страница 8: ...rder settings can be printed Internal Light A light is provided for easier viewing of the recording area of the chart paper Display Measured values can be displayed numerically or using bar graphs on...

Страница 9: ...ey panel They lights up the recording area of the chart paper Recording pen Records the measured value Plotter pen Prints various types of information Printer carriage Records measured values and prin...

Страница 10: ...the SHIFT key to switch the setup item or the value in reverse order LEFT RIGHT Key Moves the cursor to the right when entering a value or character Press this key while holding down the SHIFT key to...

Страница 11: ...t errors will result when using thermocouples In this case let the recorder adjust to the new environment for at least one hour before using it The chart paper may be adversely affected by a rapid cha...

Страница 12: ...he figure shows the case when the mounting brackets are used on the top and bottom of the case Screw temporarily Fix in place Front Panel Panel Mounting bracket Mounting bracket Torque driver flat bla...

Страница 13: ...d tolerance is 3 however tolerance is 0 3 mm when below 10 mm External Dimensions of the Portable Type H5x Option 288 11 34 11 34 10 53 7 11 3 43 11 18 12 98 0 5 288 180 5 267 5 87 284 329 7 12 7 Unit...

Страница 14: ...Length of the stripped section of the wire Approx 5 mm Take measures to prevent noise from entering the measurement circuit Move the measurement circuit away from the power cable power circuit and gro...

Страница 15: ...Channel 4 A B b Screw input terminal Clamped input terminal H2 option Pen Model Dot Model Channel 1 to 6 Channel 7 to 12 Channel 13 to 18 Channel 19 to 24 Channel 1 Channel 2 Channel 3 Channel 4 Chann...

Страница 16: ...is applied to the cable wired to the recorder the terminals of the recorder and or the cable can be damaged In order to prevent tension from being applied directly on the terminals fasten all wiring...

Страница 17: ...NC NO C NC NO C NC I01 I02 I03 I04 I05 I06 NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC A3 F1 I01 I02 I03 I04 I05 I06 I01 I02 I03 I04 I05 I06 NO C NC NO C NC R1 CE FAIL 1 2 3 4 5 C 1 2 3 4 5 C R1...

Страница 18: ...utput relay settings Remote Control Input Terminals 1 to 5 Remote control input terminals C Common Remote control input terminals 1 to 5 are expressed as numbers 1 to 5 in the remote control input set...

Страница 19: ...d a switch or fuse to the ground line Portable Type H5x Option Ensure that the source voltage matches the rated power supply voltage of the instrument before connecting the power cord Connect the powe...

Страница 20: ...P1 24 VDC AC power supply Wiring Procedure Portable Type H5x Option 1 Check that the power switch to the instrument is turned OFF 2 Connect the plug on the accessory power cord to the power supply co...

Страница 21: ...tion M1 option Measurement recording and alarm detection cannot be carried out in this mode Operation mode Power ON Setting mode Data display setup screen Basic Setting mode MENU 1 Display End Store a...

Страница 22: ...sic Setting Mode Hold down the MENU key for 3 seconds to enter Setting mode Next hold down both the DISP key and the FUNC key for 3 seconds The Basic Setting mode display appears The top and bottom li...

Страница 23: ...y the operation is cancelled and the display returns to a higher level menu In other words if you do not show the Setting complete screen the changes you made up to that point are discarded Press the...

Страница 24: ...he character is to be inserted Press the DISP key to show Ins DISP and then press the DISP key A space for one character is inserted Enter the character Position to insert the character Display Ins DI...

Страница 25: ...tion Light DST DST Start month Start day Start time End month End day End time mm h Tag Periodic are not displayed in the default condition To display these items settings must be changed in Basic Set...

Страница 26: ...assword Suffix_S P_Adj Pen number Value End End Timeout Duration Keep alive Host Level Suffix primary IP address Subnet mask Primary server Secondary server Gateway Suffix secondary Indicator Increase...

Страница 27: ...damage to the chart cassette platen the cylindrical section that holds the paper during the recording operation Be sure to replace the chart paper ahead of time Loading the Chart Paper 1 Open the door...

Страница 28: ...topper on either side Chart holder Black Stopper Front cover Chart holder Transparent Stopper Chart holder Transparent 1 2 3 2 4 Load the chart paper Riffle the chart thoroughly before loading Make su...

Страница 29: ...ssette back into the recorder case Align the left and right projections with the guide grooves of the recorder and press the entire chart cassette into the recorder case The chart cassette is fixed in...

Страница 30: ...ition That Is Not Easily Accessible below 4 Remove the cap from the new felt pen and insert the pen firmly into the pen holder From the top pen 1 red pen 2 green pen 3 blue and pen 4 violet 5 Return t...

Страница 31: ...r carriage If you do the carriage position may be offset and the recorder may not print correctly 1 Open the door If recording is in progress press the RCD key to stop the recording 2 Press the FUNC k...

Страница 32: ...the ribbon feeding knob in the direction of the arrow to align the ribbon feeding shaft of the cassette with the ribbon feeding shaft of the holder Groove for the ribbon cassette stopper Ribbon feed...

Страница 33: ...anuary to May in the figure below Press the key three times to move the cursor to the month position Next press the key four times to change the value from 1 to 5 04 01 17 10 39 47 04 05 17 10 39 47 A...

Страница 34: ...key with Range shown on the screen Set Range Input range and record Displays a description of the setup item Selecting the Channel Range 3 Press the key to set the first channel to 02 and then press...

Страница 35: ...the decimal point The measured values in the range of 0 0 to 500 0 are recorded in a width of 180 mm on the chart paper 1V 5V 1 5V standard signal 0 0 500 0 Scale left Scale right 1 000 5 000 Span le...

Страница 36: ...Decima Setting Scaling Right 11 Likewise set Scale right to 500 0 and press the key Scale right 500 0 2000 0 3000 0 Displays the scaling range The Setting complete screen is displayed When this screen...

Страница 37: ...o 30000 excluding the decimal point The measured values in the range of 0 0 to 400 0 m3 h are recorded in a width of 180 mm on the chart paper Chart paper 180 mm 20 V 20 V Linear scaling Measurable ra...

Страница 38: ...the scaling range 11 Press the key to select the desired digit Scale left 0 00 200 00 300 00 12 Press the key to select space and then press the key Scale left is set to 0 0 Scale left 0 0 200 00 300...

Страница 39: ...ue in the appropriate unit and used as the measured value of the channel Also the low cut function input less than a given measured value is fixed to 0 can be used Skip Disables measurement display pe...

Страница 40: ...ss the key to select On and then press the key On Enables the alarm of the selected alarm level Alarm On On Off Displays possible choices 7 Press the key to select H and then press the key The letter...

Страница 41: ...value R High Limit on Rate of Change Alarm The rate of change of the measured values is checked over a certain time interval An alarm occurs if the rate of change of the measured value in the rising d...

Страница 42: ...le Dot Model The recording examples may appear differently from the actual recording as a result of functional improvements made on the recorder after this manual was written Stopping the Recording Wh...

Страница 43: ...00 4320 4500 4800 5400 6000 7200 8000 9000 10800 12000 Chart speed on the pen model unit mm h On the dot model enter a vale to set the chart speed The chart speed can be set in the range of 1 to 1500...

Страница 44: ...500 0 1CH mg cm3 RED 50mm h_ 08 00 25mm h 09 52 START 205 ABCDEF 1H3 10 09 1H3 10 05 50mm h 14 55 Printout Description Figure Dot Model 1 1 1 1 Alarm printout Message printout Manual printout Channel...

Страница 45: ...n is printed when an alarm occurs or releases Time of alarm occurrence release Indicates that there are alarms that are not printed because the alarm printout buffer is full Level number Alarm type Ch...

Страница 46: ...ng the Displayed Channel Using Keys If auto switching is not specified the channel switches each time the CH UP key is pressed in ascending order All channels are displayed in order Display Example Fl...

Страница 47: ...the key is pressed Select the TAG001A Tag_1CH digital display and then press the key TAG001A 200 0 mV 4 Press the key to set the channel switching interval and then press the key Interval Sets the ch...

Страница 48: ...200 0 mV TAG001A 200 0 mV Batch Number 000001 999 9 999 9 999 9 999 9 999 9 999 9 999 9 999 9 999 9 999 9 999 9 999 9 01dH 1999 9ABCDEF 0AH9999999 9ABCDEF 01dH 1999 9ABCDEF 01dH 1999 9ABCDEF 1 DI DO d...

Страница 49: ...arm printout buffer Clears the data waiting to be printed in the message printout buffer This is displayed when the settings are changed to use the key lock function It is used to activate or release...

Страница 50: ...suspended However the recorder continues the measurement and alarm detection in the background When printout is complete trend recording resumes If an alarm occurs during the printout the alarm is pri...

Страница 51: ...sages can be printed only during trend recording However regardless of whether trend recording is in progress or not messages waiting to be printed are temporarily stored in the buffer memory Message...

Страница 52: ...use the key lock function this operation activates or releases the key lock For details on setting the key lock function see section 7 10 Setting the Key Lock Function in the R20000 Recorder User s M...

Страница 53: ...Off Alarm Type H L h l R r T t H Alarm Value Depends on the alarm type Alarm Relay On Off Off Alarm Relay number I01 to I06 I11 to I16 I21 to I26 I31 to I36 I01 Unit CH 01 to 24 01 Unit Unit 6 charact...

Страница 54: ...t Right Within the recording span range mm Left 0 Right 180 Math Aux Partial CH 0A 0B 0C 0D 0E 0F 0G 0J 0K 0M 0N 0P 0A 1A 1B 1C 1D 1E 1F 1G 1J 1K 1M 1N 1P Math Aux Partial Partial On Off Off Math Aux...

Страница 55: ...to Burnout CH 01 to 24 01 Burnout Burnout Off Up Down Off RJC CH 01 to 24 01 RJC RJC Internal External Internal RJC RJC Volt 20000 to 20000 V 0 V Color Channel Dot Model 01 to 24 01 07 13 19 Purple Co...

Страница 56: ...t speed Time adjust Record On Off Math start stop M1 Math reset M1 Manual print Alarm ACK Message1 Message2 Message3 Message4 Message5 Priority R_RCD BT1 BatchCMT switch BT1 None M1 BT1 option Computa...

Страница 57: ...cters or less Admin admin User1 to 6 user1 to user6 Ethernet LoginSet Password 4 characters or less Administrator 0 User1 to 6 1 to 6 Ethernet Timeout Timeout On Off Off Ethernet Timeout Duration 1 to...

Страница 58: ...al comment Not Use Not Batch MSG format Not Use Not Adjustment Setup Item Pen Dot Selectable Range or Selections Default Value P_Adj P_Adj Dot Model Hysteresis Zero Full Hysteresis Pen Model Zero Full...

Страница 59: ...er Plotter motor Plotter carriage Chart paper feed motor Display Plotter pen Felt pen PEN ASSY B9902AM B9902AN B9902AP B9902AQ Red Green Blue Violet At a pen speed of 10 cm s 100 000 characters PEN AS...

Отзывы: