36
IM 04P02B01-02E
Selecting the Input Type
5.
Press the
key to select
1-5V
and then press the
key (see “Explanation”
on page 39).
Mode=1-5V
Scales and records the
Setting Span Left
6.
Set Span left to
1.000
and press the
key.
Press the
key to select the desired digit.
Press the
key to select the value.
Span left= 1.000
0.800/ 1.200V
Displays the range of Span left.
Setting Span Right
7.
Likewise, set Span right to
5.000
and press the
key.
Span right= 5.000
4.800/ 5.200V
Displays the range of Span right.
Setting the Decimal Position and Scaling Left
8.
Display Scale left.
Scale left= 0.00
-200.00/ 300.00 Decima
Displays the scaling range.
9.
Press the
key to select the desired digit.
Scale left= 0.00
-200.00/ 300.00 Decima
10.
Press the
key to select space and then press the
key (Scale left is set
to
0.0
).
Scale left= 0.0
-200.00/ 300.00 Decima
Setting Scaling Right
11.
Likewise, set Scale right to
500.0
and press the
key.
Scale right= 500.0
-2000.0/ 3000.0
Displays the scaling range.
The
Setting complete
screen is displayed. When this screen is displayed, the
settings entered up to then are applied.
Finishing the Settings
12.
When
Setting complete
screen is displayed, press the
ESC
key.
The
Set=Range
screen is displayed.
03-03 Channel
Setting complete
Set=Range
Input range and record
Setting the Unit
13.
Press the
key to select
Unit
and then press the
key.
Set=Unit
Engineering unit for l
Displays the description of setting item.
14.
Press the
key to set the first channel to
03
and then press the
key.
First channel Last channel
CH=03-03
First channel 01-06
Displays the selectable range of channels.
15.
Likewise, set the last channel to
03
and then press the
key.
Setting the Input Range and Alarm on Measurement Channels
* When the key or key is pressed while holding down the SHIFT key, the operation is
reversed as when the respective key is pressed by itself.