IM 05P02C41-15EN   page 14/14

n

 DeviceNet  Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (DNET)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

125K: 125k bps

250K: 250k bps

500K: 500k bps

125K

EASY

(ADR)

Address

0 to 63

63

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0, 11 to 15

0

n

 CC-Link  Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (CC-L)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

156K: 156k bps

625K: 625k bps

2.5K: 2.5k bps

5M: 5M bps

10M: 10M bps

10M

EASY

(ADR)

Address

1 to 64

1

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0, 11 to 15

(0, 11: Ver.1.10) (12 to 15: Ver.2.00)

0

■ Display Function Setting Parameter 

Menu symbol: 

 (DISP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PCMD)

Active color PV display 

switch

0: Fixed in white

1: Fixed in red

2: Link to alarm 1 (Alarm OFF: white, 

Alarm ON: red)

3: Link to alarm 1 (Alarm OFF: red, 

Alarm ON: white)

4: Link to alarm 1 or 2 (Alarm OFF: 

white, Alarm ON: red)

5: Link to alarm 1 or 2 (Alarm OFF: 

red, Alarm ON: white)

6: PV limit (Within range: white, Out 

of range: red)

7: PV limit (Within range: red, Out of 

range: white)

8: SP deviation (Within deviation: 

white, Out of deviation: red)

9: SP deviation (Within deviation: red, 

Out of deviation: white)

10: Link to DI (ON: red, OFF: white)

0

EASY

(PCH)

PV color change high 

limit

Set a display value when in PV limit 

or SP deviation.

-19999 to 30000 (Set a value within 

the input range.)

Decimal point position depends on 

the input type.

0

(PCL)

PV color change low limit

0

(PTSL)

Program display pattern 

selection

PTN: Pattern display

SK.RP: Ramp and soak display

PTN

STD

(BAR1)

Upper bar-graph display 

registration

0: Disable

1: 

OUT, Heating-side OUT, Internal value 

in Position proportional control

2: Cooling-side OUT

3: PV

4: SP

5: Deviation

6: 

Loop-2 OUT, Loop-2 heating-side OUT

7: Loop-2 cooling-side OUT

8: Loop-2 PV

9: Loop-2 SP

10: Loop-2 deviation

11 to 16: Disable

17: Feedback input (valve opening)

18: PV terminals analog input

19: RSP terminals analog input

20: AIN2 terminals analog input

21: AIN4 terminals analog input

22: Segment progress

23: Time event and alarm status

23

(BAR2)

Lower bar-graph display 

registration

0

(BDV)

Bar-graph deviation 

display band

0.0 to 100.0% of PV input range span 

(EUS)

10.0 % 

of PV 

input 

range 

span

STD

(GUID)

Guide display ON/OFF

OFF: Nondisplay, ON: Display

ON

(ECO)

Economy mode

OFF: Disable

1: Economy mode ON (All indications 

except PV display OFF)

2: Economy mode ON (All indications 

OFF)

3: Brightness 10 % (whole indication)

OFF

(BRI)

Brightness

(Dark) 1 to 5 (Bright)

3

EASY

(MLSD)

Least significant digital 

mask of PV display

OFF: With least significant digit

ON: Without least significant digit

OFF

STD

■ SELECT Display Setting Parameter

Menu symbol: 

 (CSEL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(CS1 to CS5)

SELECT Display-1 to -5 

registration

Register the operation parameter 

(except the Operation Mode) that is 

frequently modified to display it in the 

Operation Display.

OFF, 2201 to 5000

For the setting range, see User's 

Manual.

OFF

STD

Use the following table to record SELECT Display setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

CSn

■ Key Lock Setting Parameter 

Menu symbol: 

 (KLOC)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(COM.W)

Communication write 

enable/disable

OFF: Enable, ON: Disable

OFF

STD

(DATA)

Front panel parameter 

data (▼,▲) key lock

OFF: Unlock, ON: Lock

OFF

(RUN)

Front panel RUN key 

lock

OFF

(RST)

Front panel RST key lock

OFF

(PTN)

Front panel PTN key lock

OFF

(MODE)

Front panel MODE key 

lock

OFF

■ DI Function Registration Parameter

Menu symbol: 

 (DI.SL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PRG)

Switch to PROG (Start 

of program operation)

Set an I relay number of contact 

input.

Set “OFF” to disable the function.

Standard terminals

DI1: 5025, DI2: 5026, DI3: 5027

E1-terminal area

 

DI11: 5041, DI12: 5042, DI13: 5043, 

DI14: 5044, DI15: 5045, DI16: 5046

E2 -terminal area

 

DI21: 5057, DI22: 5058, DI23: 5059, 

DI24: 5060, DI25: 5061, DI26: 5062

E3-terminal area

 

DI31: 5073, DI32: 5074, DI33: 5075, 

DI34: 5076, DI35: 5077

E4-terminal area

 

DI41: 5089, DI42: 5090, DI43: 5091, 

DI44: 5092, DI45: 5093, DI46: 5094

5025

STD

(RST)

Switch to RESET (Stop 

of program operation)

5026

(LOC)

Switch to LOCAL(LSP) 

(Start of local-mode 

operation)

5027

(REM)

Switch to REMOTE

5046

(P/R)

PROG/RESET Switch

OFF

(P/H)

PROG/HOLD Switch

OFF

(P/L)

PROG/LOCAL(LSP) 

Switch

OFF

(HOLD)

Switch to HOLD (Start 

of hold-mode operation)

OFF

(ADV)

Advance of segment

OFF

(WAIT)

Wait ON/OFF switch

OFF

(A/M)

AUTO/MAN switch

OFF

(AT)

Auto-tuning START/STOP 

switch

OFF

(LAT)

Latch release

OFF

(LCD)

LCD backlight ON/OFF 

switch

OFF

(PVRW)

PV red/white switch

OFF

■ DI Function Numbering Parameter

Menu symbol: 

 (DI.NU)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PT.B0)

Bit-0 of program pattern 

number

See next table.

5089

EASY

(PT.B1)

Bit-1 of program pattern 

number

5090

(PT.B2)

Bit-2 of program pattern 

number

5091

(PT.B3)

Bit-3 of program pattern 

number

5092

(PT.B4)

Bit-4 of program pattern 

number

5093

(PT.B5)

Bit-5 of program pattern 

number

Set an I relay number of contact input.

Set “OFF” to disable the function.

Standard terminals 

DI1: 5025, DI2: 5026, DI3: 5027

E1-terminal area

 

DI11: 5041, DI12: 5042, DI13: 5043, 

DI14: 5044, DI15: 5045, DI16: 5046

E2 -terminal area

DI21: 5057, DI22: 5058, DI23: 5059, 

DI24: 5060, DI25: 5061, DI26: 5062

E3-terminal area

 

DI31: 5073, DI32: 5074, DI33: 5075, 

DI34: 5076, DI35: 5077

E4-terminal area

 

DI41: 5089, DI42: 5090, DI43: 5091, 

DI44: 5092, DI45: 5093, DI46: 5094

OFF

STD

(PN.B0)

Bit-0 of PID number

OFF

(PN.B1)

Bit-1 of PID number

OFF

(PN.B2)

Bit-2 of PID number

OFF

(PN.B3)

Bit-3 of PID number

OFF

(MP.B0)

Bit-0 of manual preset 

output number

OFF

(MP.B1)

Bit-1 of manual preset 

output number

OFF

(MP.B2)

Bit-2 of manual preset 

output number

OFF

■ AL1-AL3 Function Registration Parameter

Menu symbol: 

 (ALM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(AL1.S)

AL1 function selection

Set an I relay number. For the items 

other than below, see User's Manual.

Ex.) Set the number 4353 for AL1.S 

to use the alarm 1.

Set “OFF” to disable the function.

Setting range: 4001 to 6304

No function: OFF, 

 

PV event 1: 4801, PV event 2: 4802, 

 

PV event 3: 4803, PV event 4: 4805, 

 

PV event 5: 4806, PV event 6: 4807, 

 

PV event 7: 4809, PV event 8: 4810, 

 

Time event 1: 4817, Time event 2: 4818, 

 

Time event 3: 4819, Time event 4: 4821, 

 

Time event 5: 4822, Time event 6: 4823, 

 

Time event 7: 4825, Time event 8: 4826, 

 

Time event 9: 4833, Time event 10: 4834, 

 

Time event 11: 4835, Time event 12: 4837,  

 

Time event 13: 4838, Time event 14: 4839, 

 

Time event 15: 4841, Time event 16: 4842, 

 

Alarm 1: 4353, Alarm 2: 4354, 

 

Alarm 3: 4355, Alarm 4: 4357

 

Alarm 5: 4358, Alarm 6: 4359, 

 

Alarm 7: 4361, Alarm 8: 4362

 

AUTO (ON ) / MAN (OFF) status: 4177

Program RESET status: 4181

Program RUN status: 4182

Local operation status: 4183

Remote operation status: 4185

HOLD mode status: 4189

Program advance status: 4187

Pattern end signal (1 second): 4265

Pattern end signal (3 seconds): 4266

Pattern end signal (5 seconds): 4267

Wait end signal (1 second) : 4257

Wait end signal (3 seconds) : 4258

Wait end signal (5 seconds) : 4259

Output tracking (ON) switching signal: 4186

FAIL (Normally ON) output: 4256

4801

STD

(AL2.S)

AL2 function selection

4802

(AL3.S)

AL3 function selection

4803

(OR.S)

OUT relay function 

selection

OFF

(OR2.S)

OUT2 relay function 

selection

OFF

■ DO Setting Parameter (E1/E2/E3/E4-terminal Area)

Menu symbol: 

 (DO)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(DO1.S)

DO11/DO21/DO31/DO41

 

function selection

Same as AL1.S

Set “OFF” to disable the function.

Initial value: DO11=4805, DO12=4806

 

DO13=4807, DO14=4809,

 

DO15=4810, DO21=4817,

 

DO22=4818, DO23=4819

 

DO24=4821, DO25=4822,

 

DO31=4823, DO32=4825,

 

DO33=4826, DO34=4833,

 

DO35=4834,

 

DO41 to DO45=OFF

See left

Table 

below

STD

(DO2.S)

DO12/DO22/DO32/DO42

 

function selection

See left

(DO3.S)

DO13/DO23/DO33/DO43

 

function selection

See left

(DO4.S)

DO14/DO24/DO34/DO44

 

function selection

See left

(DO5.S)

DO15/DO25/DO35/DO45

 

function selection

See left

Use the following table to record DO setting value.

Parameter

E1-terminal Area

E2-terminal Area

E3-terminal Area

E4-terminal Area

DO1.S
DO2.S
DO3.S
DO4.S
DO5.S

■ System Setting Parameter

Menu symbol: 

 (SYS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial value User 

setting

Display 

level

(R.MD)

Restart mode

Set how the controller should recover from 

a power failure of 5 seconds or more.

CONT: Continue action set before 

power failure.

MAN: Start from MAN.

RESET: Start from AUTO and RESET. 

Outputs the preset output value.

CONT

STD

(R.TM)

Restart timer

Set time between power on and the 

instant where controller starts compu

-

tation. 0 to 10 s

0

(EPO)

Input error preset 

output

Set preset output value when the input burnout 

or ADC error occurs. Manual output is priori-

tized when the input burnout occurs in MAN.

0: Preset output

1: 0% output

2: 100% output

0

STD

(FREQ)

Power frequency

AUTO, 60: 60 Hz, 50: 50 Hz

AUTO

EASY

(QSM)

Quick setting mode OFF: Disable

ON: Enable

ON

(LANG)

Guide display 

language

ENG: English

FRA: French

GER: German

SPA: Spanish

Depends on 

the model 

and suffix 

codes

(PASS)

Password setting

0 (No password) to 65535

0

■ Error and Version Confirmation Parameter (for display only)

Menu symbol: 

 (VER)

Parameter 

symbol

Name of Parameter

Status record

Display 

level

(PA.ER)

Parameter error status

EASY

(OP.ER)

Option error status

(AD1.E)

A/D converter error status 1 

(AD2.E)

A/D converter error status 2 

(PV1.E)

Loop-1 PV input error status

(PV2.E)

Loop-2 PV input error status

(LA.ER)

Ladder error status

(MCU)

MCU version

(DCU)

DCU version

(ECU1)

ECU-1 version (E1-terminal area)

(ECU2)

ECU-2 version (E2-terminal area)

(ECU3)

ECU-3 version (E3-terminal area)

(ECU4)

ECU-4 version (E4-terminal area)

(PARA)

Parameter version

(H.VER)

Product version

(

SER1

)

Serial number 1

(SER2)

Serial number 2 

(MAC1)

MAC address 1 (E3-terminal area)

(MAC2)

MAC address 2 (E3-terminal area)

(MAC3)

MAC address 3 (E3-terminal area)

* The parameters for Loop-2 are unavailable in Single-loop control.

■ Parameter Display Level Parameter

Menu symbol: 

 (LVL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(LEVL)

Parameter display level

EASY: Easy setting mode

STD: Standard setting mode

PRO: Professional setting mode

STD

EASY

* For Professional setting mode, see User’s Manual.

Trademarks

● Our product names or brand names mentioned in this manual are 

  the trademarks or registered trademarks of Yokogawa Electric Corporation.

● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks

  of Adobe Systems Incorporated.

● Ethernet is a registered trademark of XEROX Corporation in the United States.

● Modbus is a registered trademark of Schneider Electric.

● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.

● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.

● CC-Link is a registered trademark of CC-Link Partner Association.

● We do not use the TM or ® mark to indicate these trademarks or 

  registered trademarks in this manual.

● All other product names mentioned in this manual are trademarks

  or registered trademarks of their respective companies.

Содержание UTAdvanced UP55A

Страница 1: ...al area 4 5 CH3 RS485 communication Max 38 4 kbps 2 wire 4 wire CC3 CC Link communication with Modbus master function PD3 PROFIBUS DP communication with Modbus master function DN3 DeviceNet communicat...

Страница 2: ...nd measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC vo...

Страница 3: ...uit CAUTION When connecting two or more crimp on terminal lugs to the single terminal block bend the crimp on terminal lugs before tightening the screw Note that the wiring of two or more crimp on ter...

Страница 4: ...on faulted green red flashing No electricity CHK MNS 1 2 3 4 5 Suffix code Type 3 3 except Type 2 3 CC Link communication with Modbus master RS 485 RSB RSA SG 407 408 409 CC L If the UP is located at...

Страница 5: ...stall and wire a controller Monitoring and control of regular operations Adjust PID using auto tuning or manually for PID control Other setup Operation NO NO NO YES YES YES Control mode Single loop co...

Страница 6: ...DE menu is displayed ALRM menu is displayed 1 2 3 4 5 Show the Operation Display Hold down the key for 3 seconds Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET...

Страница 7: ...between digits Press the Down arrow key until TSP appears Press the Down arrow key Press the Down arrow key 12 Set the segment PID number Segment time 50 minutes 13 Press the SET ENTER key Press the D...

Страница 8: ...User s Manual Program Pattern Data parameters for segments Maximum value of PV input range Maximum value of PV input scale Unit A program pattern can be drawn in the right table Minimum value of PV i...

Страница 9: ...2 3 4 Show the Operation Display Hold down the PARAMETER key for 3 seconds to display MODE menu Press the SET ENTER key Press the SET ENTER key The parameter HOLD Pause cancel release of program oper...

Страница 10: ...g Advance Function Advance can be performed during program operation using any of the following 1 MODE key 2 Parameter 3 Contact input and 4 Communication The following shows an example of switching u...

Страница 11: ...mits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 17 Cooling side OUT high limit 18 Cooling side OUT low limit Add 100 for de energized For example when the PV...

Страница 12: ...a decimal point position using LL50A Parameter Set ting Software 0 Table below STD Parameter n 01 n 02 n 03 n 04 n 05 n 06 n 07 n 08 n 09 n 10 Pn n 10 segment Linearizer 1 2 Setting Parameter Menu sym...

Страница 13: ...back input error or break occurs 2 Valve position estimating type 0 RTS Retransmission output type of RET OFF Disable PV1 PV SP1 SP OUT1 OUT Valve opening 0 to 100 in Position proportional control LPS...

Страница 14: ...DI25 5061 DI26 5062 E3 terminal area DI31 5073 DI32 5074 DI33 5075 DI34 5076 DI35 5077 E4 terminal area DI41 5089 DI42 5090 DI43 5091 DI44 5092 DI45 5093 DI46 5094 OFF STD PN B0 Bit 0 of PID number OF...