IM 05P02C41-15EN page 14/14
n
DeviceNet Communication Setting Parameter (E3-terminal Area)
Menu symbol:
(DNET)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(BR)
Baud rate
125K: 125k bps
250K: 250k bps
500K: 500k bps
125K
EASY
(ADR)
Address
0 to 63
63
(BPS)
Baud rate
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
(FILE)
Profile number
0, 11 to 15
0
n
CC-Link Communication Setting Parameter (E3-terminal Area)
Menu symbol:
(CC-L)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(BR)
Baud rate
156K: 156k bps
625K: 625k bps
2.5K: 2.5k bps
5M: 5M bps
10M: 10M bps
10M
EASY
(ADR)
Address
1 to 64
1
(BPS)
Baud rate
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
(FILE)
Profile number
0, 11 to 15
(0, 11: Ver.1.10) (12 to 15: Ver.2.00)
0
■ Display Function Setting Parameter
Menu symbol:
(DISP)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PCMD)
Active color PV display
switch
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white,
Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF:
white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF:
red, Alarm ON: white)
6: PV limit (Within range: white, Out
of range: red)
7: PV limit (Within range: red, Out of
range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation: red,
Out of deviation: white)
10: Link to DI (ON: red, OFF: white)
0
EASY
(PCH)
PV color change high
limit
Set a display value when in PV limit
or SP deviation.
-19999 to 30000 (Set a value within
the input range.)
Decimal point position depends on
the input type.
0
(PCL)
PV color change low limit
0
(PTSL)
Program display pattern
selection
PTN: Pattern display
SK.RP: Ramp and soak display
PTN
STD
(BAR1)
Upper bar-graph display
registration
0: Disable
1:
OUT, Heating-side OUT, Internal value
in Position proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6:
Loop-2 OUT, Loop-2 heating-side OUT
7: Loop-2 cooling-side OUT
8: Loop-2 PV
9: Loop-2 SP
10: Loop-2 deviation
11 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
19: RSP terminals analog input
20: AIN2 terminals analog input
21: AIN4 terminals analog input
22: Segment progress
23: Time event and alarm status
23
(BAR2)
Lower bar-graph display
registration
0
(BDV)
Bar-graph deviation
display band
0.0 to 100.0% of PV input range span
(EUS)
10.0 %
of PV
input
range
span
STD
(GUID)
Guide display ON/OFF
OFF: Nondisplay, ON: Display
ON
(ECO)
Economy mode
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications
OFF)
3: Brightness 10 % (whole indication)
OFF
(BRI)
Brightness
(Dark) 1 to 5 (Bright)
3
EASY
(MLSD)
Least significant digital
mask of PV display
OFF: With least significant digit
ON: Without least significant digit
OFF
STD
■ SELECT Display Setting Parameter
Menu symbol:
(CSEL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(CS1 to CS5)
SELECT Display-1 to -5
registration
Register the operation parameter
(except the Operation Mode) that is
frequently modified to display it in the
Operation Display.
OFF, 2201 to 5000
For the setting range, see User's
Manual.
OFF
STD
Use the following table to record SELECT Display setting value.
Parameter
n=1
n=2
n=3
n=4
n=5
CSn
■ Key Lock Setting Parameter
Menu symbol:
(KLOC)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(COM.W)
Communication write
enable/disable
OFF: Enable, ON: Disable
OFF
STD
(DATA)
Front panel parameter
data (▼,▲) key lock
OFF: Unlock, ON: Lock
OFF
(RUN)
Front panel RUN key
lock
OFF
(RST)
Front panel RST key lock
OFF
(PTN)
Front panel PTN key lock
OFF
(MODE)
Front panel MODE key
lock
OFF
■ DI Function Registration Parameter
Menu symbol:
(DI.SL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PRG)
Switch to PROG (Start
of program operation)
Set an I relay number of contact
input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045, DI16: 5046
E2 -terminal area
DI21: 5057, DI22: 5058, DI23: 5059,
DI24: 5060, DI25: 5061, DI26: 5062
E3-terminal area
DI31: 5073, DI32: 5074, DI33: 5075,
DI34: 5076, DI35: 5077
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093, DI46: 5094
5025
STD
(RST)
Switch to RESET (Stop
of program operation)
5026
(LOC)
Switch to LOCAL(LSP)
(Start of local-mode
operation)
5027
(REM)
Switch to REMOTE
5046
(P/R)
PROG/RESET Switch
OFF
(P/H)
PROG/HOLD Switch
OFF
(P/L)
PROG/LOCAL(LSP)
Switch
OFF
(HOLD)
Switch to HOLD (Start
of hold-mode operation)
OFF
(ADV)
Advance of segment
OFF
(WAIT)
Wait ON/OFF switch
OFF
(A/M)
AUTO/MAN switch
OFF
(AT)
Auto-tuning START/STOP
switch
OFF
(LAT)
Latch release
OFF
(LCD)
LCD backlight ON/OFF
switch
OFF
(PVRW)
PV red/white switch
OFF
■ DI Function Numbering Parameter
Menu symbol:
(DI.NU)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PT.B0)
Bit-0 of program pattern
number
See next table.
5089
EASY
(PT.B1)
Bit-1 of program pattern
number
5090
(PT.B2)
Bit-2 of program pattern
number
5091
(PT.B3)
Bit-3 of program pattern
number
5092
(PT.B4)
Bit-4 of program pattern
number
5093
(PT.B5)
Bit-5 of program pattern
number
Set an I relay number of contact input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045, DI16: 5046
E2 -terminal area
DI21: 5057, DI22: 5058, DI23: 5059,
DI24: 5060, DI25: 5061, DI26: 5062
E3-terminal area
DI31: 5073, DI32: 5074, DI33: 5075,
DI34: 5076, DI35: 5077
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093, DI46: 5094
OFF
STD
(PN.B0)
Bit-0 of PID number
OFF
(PN.B1)
Bit-1 of PID number
OFF
(PN.B2)
Bit-2 of PID number
OFF
(PN.B3)
Bit-3 of PID number
OFF
(MP.B0)
Bit-0 of manual preset
output number
OFF
(MP.B1)
Bit-1 of manual preset
output number
OFF
(MP.B2)
Bit-2 of manual preset
output number
OFF
■ AL1-AL3 Function Registration Parameter
Menu symbol:
(ALM)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(AL1.S)
AL1 function selection
Set an I relay number. For the items
other than below, see User's Manual.
Ex.) Set the number 4353 for AL1.S
to use the alarm 1.
Set “OFF” to disable the function.
Setting range: 4001 to 6304
No function: OFF,
PV event 1: 4801, PV event 2: 4802,
PV event 3: 4803, PV event 4: 4805,
PV event 5: 4806, PV event 6: 4807,
PV event 7: 4809, PV event 8: 4810,
Time event 1: 4817, Time event 2: 4818,
Time event 3: 4819, Time event 4: 4821,
Time event 5: 4822, Time event 6: 4823,
Time event 7: 4825, Time event 8: 4826,
Time event 9: 4833, Time event 10: 4834,
Time event 11: 4835, Time event 12: 4837,
Time event 13: 4838, Time event 14: 4839,
Time event 15: 4841, Time event 16: 4842,
Alarm 1: 4353, Alarm 2: 4354,
Alarm 3: 4355, Alarm 4: 4357
Alarm 5: 4358, Alarm 6: 4359,
Alarm 7: 4361, Alarm 8: 4362
AUTO (ON ) / MAN (OFF) status: 4177
Program RESET status: 4181
Program RUN status: 4182
Local operation status: 4183
Remote operation status: 4185
HOLD mode status: 4189
Program advance status: 4187
Pattern end signal (1 second): 4265
Pattern end signal (3 seconds): 4266
Pattern end signal (5 seconds): 4267
Wait end signal (1 second) : 4257
Wait end signal (3 seconds) : 4258
Wait end signal (5 seconds) : 4259
Output tracking (ON) switching signal: 4186
FAIL (Normally ON) output: 4256
4801
STD
(AL2.S)
AL2 function selection
4802
(AL3.S)
AL3 function selection
4803
(OR.S)
OUT relay function
selection
OFF
(OR2.S)
OUT2 relay function
selection
OFF
■ DO Setting Parameter (E1/E2/E3/E4-terminal Area)
Menu symbol:
(DO)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(DO1.S)
DO11/DO21/DO31/DO41
function selection
Same as AL1.S
Set “OFF” to disable the function.
Initial value: DO11=4805, DO12=4806
DO13=4807, DO14=4809,
DO15=4810, DO21=4817,
DO22=4818, DO23=4819
DO24=4821, DO25=4822,
DO31=4823, DO32=4825,
DO33=4826, DO34=4833,
DO35=4834,
DO41 to DO45=OFF
See left
Table
below
STD
(DO2.S)
DO12/DO22/DO32/DO42
function selection
See left
(DO3.S)
DO13/DO23/DO33/DO43
function selection
See left
(DO4.S)
DO14/DO24/DO34/DO44
function selection
See left
(DO5.S)
DO15/DO25/DO35/DO45
function selection
See left
Use the following table to record DO setting value.
Parameter
E1-terminal Area
E2-terminal Area
E3-terminal Area
E4-terminal Area
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
■ System Setting Parameter
Menu symbol:
(SYS)
Parameter
symbol
Name of Parameter
Setting Range
Initial value User
setting
Display
level
(R.MD)
Restart mode
Set how the controller should recover from
a power failure of 5 seconds or more.
CONT: Continue action set before
power failure.
MAN: Start from MAN.
RESET: Start from AUTO and RESET.
Outputs the preset output value.
CONT
STD
(R.TM)
Restart timer
Set time between power on and the
instant where controller starts compu
-
tation. 0 to 10 s
0
(EPO)
Input error preset
output
Set preset output value when the input burnout
or ADC error occurs. Manual output is priori-
tized when the input burnout occurs in MAN.
0: Preset output
1: 0% output
2: 100% output
0
STD
(FREQ)
Power frequency
AUTO, 60: 60 Hz, 50: 50 Hz
AUTO
EASY
(QSM)
Quick setting mode OFF: Disable
ON: Enable
ON
(LANG)
Guide display
language
ENG: English
FRA: French
GER: German
SPA: Spanish
Depends on
the model
and suffix
codes
(PASS)
Password setting
0 (No password) to 65535
0
■ Error and Version Confirmation Parameter (for display only)
Menu symbol:
(VER)
Parameter
symbol
Name of Parameter
Status record
Display
level
(PA.ER)
Parameter error status
EASY
(OP.ER)
Option error status
(AD1.E)
A/D converter error status 1
(AD2.E)
A/D converter error status 2
(PV1.E)
Loop-1 PV input error status
(PV2.E)
Loop-2 PV input error status
(LA.ER)
Ladder error status
(MCU)
MCU version
(DCU)
DCU version
(ECU1)
ECU-1 version (E1-terminal area)
(ECU2)
ECU-2 version (E2-terminal area)
(ECU3)
ECU-3 version (E3-terminal area)
(ECU4)
ECU-4 version (E4-terminal area)
(PARA)
Parameter version
(H.VER)
Product version
(
SER1
)
Serial number 1
(SER2)
Serial number 2
(MAC1)
MAC address 1 (E3-terminal area)
(MAC2)
MAC address 2 (E3-terminal area)
(MAC3)
MAC address 3 (E3-terminal area)
* The parameters for Loop-2 are unavailable in Single-loop control.
■ Parameter Display Level Parameter
Menu symbol:
(LVL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(LEVL)
Parameter display level
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode
STD
EASY
* For Professional setting mode, see User’s Manual.
Trademarks
● Our product names or brand names mentioned in this manual are
the trademarks or registered trademarks of Yokogawa Electric Corporation.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
of Adobe Systems Incorporated.
● Ethernet is a registered trademark of XEROX Corporation in the United States.
● Modbus is a registered trademark of Schneider Electric.
● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
● CC-Link is a registered trademark of CC-Link Partner Association.
● We do not use the TM or ® mark to indicate these trademarks or
registered trademarks in this manual.
● All other product names mentioned in this manual are trademarks
or registered trademarks of their respective companies.