IM 05P02C41-15EN   page 12/14

Parameter

n=1

n=2

n=3

n=4

n=5

n=6

n=7

n=8

EHYn

ALn
VTn

HYn

DYNn

n: alarm number

 

n

 PV-related Setting Parameter

Menu symbol: 

 (PVS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BS)

PV input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % of 

PV input 

range 

span

EASY

(FL)

PV input filter

OFF, 1 to 120 s

OFF

 

n

 PID Setting Parameter

Menu symbol: 

 (PID)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P)

Proportional band

Heating-side proportion-

al band (in Heating/cool-

ing control)

0.0 to 999.9%

When 0.0% is set, it operates as 

0.1%.

Heating-side ON/OFF control applies 

when 0.0% in Heating/cooling control

5.0%

EASY

(I)

Integral time

Heating-side integral time 

(in Heating/cooling control)

OFF: Disable

1 to 6000 s

240 s

(D)

Derivative time

Heating-side derivative time 

(in Heating/cooling control)

OFF: Disable

1 to 6000 s

60 s

(OH)

Control output high limit

Heating-side control 

output high limit (in 

Heating/cooling control)

-4.9 to 105.0%, (OL<OH)

In Heating/cooling control: 0.1 to 

105.0% (OL<OH)

100.0%

(OL)

Control output low limit

Heating-side control 

output low limit (in Heat-

ing/cooling control)

-5.0 to 104.9%, (OL<OH), SD: Tight 

shut

In Heating/cooling control: 0.0 to 

104.9% (OL<OH)

0.0%

(MR)

Manual reset

Enabled when integral time is OFF.

The manual reset value equals the 

output value when PV = SP.

-5.0 to 105.0%

50.0%

(HYS)

Hysteresis (in ON/OFF 

control or Position 

proportional control)

Heating-side ON/OFF 

control hysteresis (in 

Heating/cooling control)

In ON/OFF control: 0.0 to 100.0% of 

PV input range span (EUS)

In Heating/cooling control or Position 

proportional control: 0.0 to 100.0%

In 

ON/OFF 

control: 

0.5 % of 

PV input 

range 

span 

In 

Heating/

cooling 

control or 

Position

-

proportional 

control: 

0.5 %

(HY.UP)

Upper-side hysteresis 

(in ON/OFF control)

0.0 to 100.0% of PV input range 

span (EUS)

0.5 % 

of PV 

input 

range 

span

(HY.LO)

Lower-side hysteresis 

(in ON/OFF control)

0.5 % 

of PV 

input 

range 

span

(DR)

Direct/reverse action 

switch

RVS: Reverse action

DIR: Direct action

RVS

STD

(Pc)

Cooling-side propor-

tional band

0.0 to 999.9%

 

(Cooling-side ON/OFF control ap-

plies when 0.0% in Heating/cooling 

control)

5.0%

EASY

(Ic)

Cooling-side integral 

time

OFF: Disable

1 to 6000 s

240 s

(Dc)

Cooling-side derivative 

time

OFF: Disable

1 to 6000 s

60 s

(OHc)

Cooling-side control 

output high limit

0.1 to 105.0%, (OLc<OHc) 

100.0%

(OLc)

Cooling-side control 

output low limit

0.0 to 104.9%, (OLc<OHc) 

0.0%

(HYSc)

Cooling-side ON/OFF 

control hysteresis

0.0 to 100.0%

0.5%

(DB)

Output dead band (in 

Heating/cooling control 

or Position proportional 

control)

In Heating/cooling control: -100.0 to 

50.0% 

In Position proportional control: 1.0 

to 10.0%

3.0%

(PO)

Preset output

Heating-side preset 

output (in Heating/cool-

ing control)

In RESET mode, fixed control output 

can be generated. In Position propor-

tional control, Valve opening can be 

set; -5.0 to 105.0%

0.0%

(POc)

Cooling-side preset 

output

In RESET mode, cooling-side fixed 

control output can be generated.

-5.0 to 105.0%

0.0%

EASY

If you are using two or more groups of PID parameters, use the following table to record their setting values.

Parameter

n=2

n=3

n=4

n=5

n=6

n=7

n=8

R

P

I

D

OH

OL

MR

HYS

HY.UP
HY.LO

DR

Pc

Ic

Dc

OHc

OLc

HYSc

DB
PO

POc

n: group number

n

 Tuning Parameter

Menu symbol: 

 

(TUNE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SC)

Super function

OFF: Disable

1: Overshoot suppressing function 

(normal mode)

2: Hunting suppressing function 

(stable mode)

 

Enables to answer the wider 

characteristic changes compared 

with response mode.

3: Hunting suppressing function 

(response mode)

 

Enables quick follow-up and short 

converging time of PV for the 

changed SP.

4: Overshoot suppressing function 

(strong suppressing mode)

 

Note: Setpoints 2 and 3 must be 

used in PID control or PI control. 

Disabled in the following controls:

 

1) ON/OFF control, 2) PD control, 

3) P control, 4) Heating/cooling 

control. 

Do not use the function for the 

control processes with response 

such as flow or pressure control.

OFF

EASY

(AT.TY)

Auto-tuning type

0: Normal

1: Stability

0

STD

(AR)

Anti-reset windup 

(excess integration 

prevention)

AUTO, 50.0 to 200.0%

AUTO

STD

(OPR)

Output velocity limiter

OFF: Disable

0.1 to 100.0%/s

OFF

(MPON)

Manual preset output 

number selection

Select the output used in MAN mode 

when switched from AUTO to MAN 

mode.

OFF: Hold the control output in AUTO 

mode (bumpless)

1: Use manual preset output 1 (output bump)

2: Use manual preset output 2 (output bump)

3: Use manual preset output 3 (output bump)

4: Use manual preset output 4 (output bump)

5: Use manual preset output 5 (output bump)

OFF

 to

(MPO1 to MPO5)

Manual preset output 1 

to 5

-5.0 to 105.0%

However, output is limited to the 

output high limit and low limit.

0.0%

Table 

below

Use the following table to record the manual preset output setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

MPOn

n

 Zone Control Parameter

Menu symbol: 

 (ZONE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to

(RP1 to RP7)

Reference point 1 to 7

Set reference points at which switch

-

ing is carried out between groups of 

PID constants according to the given 

temperature zone.

0.0 to 100.0% of PV input range (EU) 

(RP1 ≤ RP2 ≤ RP3 ≤ RP4 ≤ RP5 ≤ 

RP6 ≤ RP7)

100.0% 

of PV 

input 

range

Table 

below

STD

(RHY)

Zone PID switching 

hysteresis

Hysteresis can be set for switching at 

a reference point.

0.0 to 10.0% of PV input range span 

(EUS)

0.5 % 

of PV 

input 

range 

span

STD

(RDV)

Reference deviation

Set a deviation from SP. The PID for 

reference deviation is used if there 

is a larger deviation than the preset 

reference deviation.

OFF: Disable

0.0 + 1 digit to 100.0% of PV input 

range span (EUS)

OFF

STD

For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID selection.

Use the following table to record the reference point setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

n=6

n=7

RPn

n

 P Parameter (for Ladder Program)

Menu symbol: 

 (PPAR)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(P01 to P10)

P01 to P10 parameter

-19999 to 30000 (Set a decimal point 

position using LL50A Parameter Set-

ting Software.)

0

Table 

below

STD

Parameter

n=01

n=02

n=03

n=04

n=05

n=06

n=07

n=08

n=09

n=10

Pn

n

 10-segment Linearizer-1, -2 Setting Parameter

Menu symbol: 

 (PYS1)

 

 (PYS2)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PYS)

10-segment linearizer 

selection

OFF: Disable

PV: PV analog input

RSP: RSP analog input

AIN2: AIN2 analog input

AIN4: AIN4 analog input

PVIN: PV input

OUT: OUT analog output

OUT2: OUT2 analog output

RET: RET analog output

PV 

(CTLM

SGL)

STD

(A1)

10-segment linearizer 

input 1

-66.7 to 105.0% of input range (EU)

Output linearizer: -5.0 to 105.0%

0.0%

(B1)

10-segment linearizer 

output 1

10-segment linearizer bias: -66.7 to 

105.0% of input range span (EUS)

10-segment linearizer approximation: 

-66.7 to 105.0% of input range (EU)

Output linearizer: -5.0 to 105.0%

0.0%

 to 

 to 

(A2 to A11,B2 to 

B11)

10-segment linearizer 

input 2 to 11

10-segment linearizer 

output 2 to 11

Same as A1 and B1

Same 

as A1 

and 

B1

(PMD)

10-segment linearizer 

mode

0: 10-segment linearizer bias

1: 10-segment linearizer approxima-

tion

0

Use the following table to record the 10-segment linearizer input and output setting values.

Parameter

n=2

n=3

n=4

n=5

n=6

n=7

n=8

n=9

n=10

n=11

An

Bn

Setup Parameters

Hold down the PARAMETER key and Left arrow key simultaneously for 3 seconds to 

move from the Operation Display or Operation Parameter Setting Display to the Setup 

Parameter Setting Display.

Press the DISPLAY key once to return to the Operation Display.

Menu

key

key

key

key

key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

P a r a m e t e r  

Setting Display 

are changed in a 

circular pattern.

Hold down PARAMETER key and 

Left arrow key simultaneously for 3 sec.

DISPLAY key

PARAMETER key

SET/ENTER key

Move to the Operation Parameter Setting Display: Hold down the PARAMETER key for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the Model 

and Suffix codes, control mode (CTLM), control type (CNT), etc. The parameters for 

professional setting mode (LEVL: PRO) are not described in this manual. See User’s 

Manual.

n

 Control Function Setting Parameter

Menu symbol: 

 (CTL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(CTLM)

Control mode

When using the controls other than 

Single-loop control, see User's 

Manual. 

SGL

STD

SGL: Single-loop control

CAS1: Cascade primary-loop control

CAS: Cascade control

PVSW: Loop control with PV switching

PVSEL: Loop control with PV auto-

selector

(CNT)

Control type

PID: PID control

ONOF: ON/OFF control (1 point of 

hysteresis)

ONOF2: ON/OFF control (2 points of 

hysteresis)

H/C: Heating/cooling control

PID

 

or 

H/C

 

(for 

Heating/

Cooling 

type)

EASY

(ZON)

Zone PID selection

0: Segment PID selection

1: 

Zone PID selection (selection by PV)

2: Zone PID selection (selection by 

target SP)

4: 

Zone PID selection (selection by SP) 

5: Local PID selection

* If set to “Segment PID selection,” 

allows PID constants to be selected 

for each segments.

* If set to “Zone PID selection,” 

automatically selects PID constants 

according to the range set in the 

Reference point.

* If set to “Local PID selection,” local 

PID is selected irrespective of the 

operation modes.

1

STD

(SEG.T)

Segment setting method

TIME: Segment time setting

TM.RT: Segment ramp-rate setting

* Note: A change of setting deletes a 

program pattern. 

TIME

EASY

(TMU)

Program time unit

HH.MM: hour.minute

MM.SS: minute.second

HH.MM

(PT2.G)

Program pattern-2 

retransmission

OFF: Not used.

ON: used.

* The controller can serve as a program 

pattern generator.

* Retransmission output types (RTS, 

O1RS, or O2RS) need to be set to 

SP2.

OFF

STD

(SMP)

Input sampling period 

(control period)

100: 100 ms, 200: 200 ms

200

n

 PV Input Setting Parameter 

Menu symbol: 

 (PV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(IN)

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.0 to 150.0 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20 : 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

OFF

EASY

(UNIT)

PV input unit

-: No unit, C: Degree Celsius, 

 

-: No unit, - -: No unit, - - -: No unit, 

 

F: Degree Fahrenheit

C

(RH)

Maximum value of PV 

input range

Depends on the input type.

- For temperature input - 

Set the temperature range that is 

actually controlled. (RL<RH)

- For voltage / current input -

Set the range of a voltage / cur-

rent signal that is applied.

The scale across which the voltage 

/ current signal is actually controlled 

should be set using the maximum 

value of input scale (SH) and mini-

mum value of input scale (SL).

(Input is always 0% when RL = RH.)

Depends 

on the 

input type

(RL)

Minimum value of PV 

input range

Depends 

on the 

input type

(SDP)

PV input scale decimal 

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

Содержание UTAdvanced UP55A

Страница 1: ...al area 4 5 CH3 RS485 communication Max 38 4 kbps 2 wire 4 wire CC3 CC Link communication with Modbus master function PD3 PROFIBUS DP communication with Modbus master function DN3 DeviceNet communicat...

Страница 2: ...nd measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC vo...

Страница 3: ...uit CAUTION When connecting two or more crimp on terminal lugs to the single terminal block bend the crimp on terminal lugs before tightening the screw Note that the wiring of two or more crimp on ter...

Страница 4: ...on faulted green red flashing No electricity CHK MNS 1 2 3 4 5 Suffix code Type 3 3 except Type 2 3 CC Link communication with Modbus master RS 485 RSB RSA SG 407 408 409 CC L If the UP is located at...

Страница 5: ...stall and wire a controller Monitoring and control of regular operations Adjust PID using auto tuning or manually for PID control Other setup Operation NO NO NO YES YES YES Control mode Single loop co...

Страница 6: ...DE menu is displayed ALRM menu is displayed 1 2 3 4 5 Show the Operation Display Hold down the key for 3 seconds Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET...

Страница 7: ...between digits Press the Down arrow key until TSP appears Press the Down arrow key Press the Down arrow key 12 Set the segment PID number Segment time 50 minutes 13 Press the SET ENTER key Press the D...

Страница 8: ...User s Manual Program Pattern Data parameters for segments Maximum value of PV input range Maximum value of PV input scale Unit A program pattern can be drawn in the right table Minimum value of PV i...

Страница 9: ...2 3 4 Show the Operation Display Hold down the PARAMETER key for 3 seconds to display MODE menu Press the SET ENTER key Press the SET ENTER key The parameter HOLD Pause cancel release of program oper...

Страница 10: ...g Advance Function Advance can be performed during program operation using any of the following 1 MODE key 2 Parameter 3 Contact input and 4 Communication The following shows an example of switching u...

Страница 11: ...mits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 17 Cooling side OUT high limit 18 Cooling side OUT low limit Add 100 for de energized For example when the PV...

Страница 12: ...a decimal point position using LL50A Parameter Set ting Software 0 Table below STD Parameter n 01 n 02 n 03 n 04 n 05 n 06 n 07 n 08 n 09 n 10 Pn n 10 segment Linearizer 1 2 Setting Parameter Menu sym...

Страница 13: ...back input error or break occurs 2 Valve position estimating type 0 RTS Retransmission output type of RET OFF Disable PV1 PV SP1 SP OUT1 OUT Valve opening 0 to 100 in Position proportional control LPS...

Страница 14: ...DI25 5061 DI26 5062 E3 terminal area DI31 5073 DI32 5074 DI33 5075 DI34 5076 DI35 5077 E4 terminal area DI41 5089 DI42 5090 DI43 5091 DI44 5092 DI45 5093 DI46 5094 OFF STD PN B0 Bit 0 of PID number OF...

Отзывы: