background image

IM 05P08D81-11EN  page 1/4

Contents

1.  Safety Precautions

2.  Model and Suffix Codes

3.  How to Install

4.  Hardware Specifications

5.  How to Connect Wires

6.  Terminal Wiring Diagrams

7.  Setup Procedure

8. Operations

9.  Troubleshooting

Introduction

Thank you for purchasing the UT32A-D/MDL Controller. (The UT32A-D with option 

 

/MDL has no display.)

This operation guide describes the installing, wirings, setup flow, and troubleshooting 

of the UT32A-D/MDL. The guide should be provided to the end user of this product.

Be sure to read this operation guide before using the product in order to ensure 

correct operation. For details of each function, refer to the electronic manual. Before 

using the product, refer to the table of Model and Suffix Codes to make sure that the 

delivered product is consistent with the model and suffix codes you ordered. Also 

make sure that the following items are included in the package.

• Digital Indicating Controller (the model you ordered)

 ..............................

x1

• Unit Label (L4502VZ)

 ..............................................................................

x1

• Tag Label (L4502VE)

 ..............................................................................

x1

  (Only when ordered.)

• Operation Guide (this document)

 ............................................................

x2 (A3 size)

  (Installation and Wiring, Initial Settings, Operations, and Parameters)

Target Readers

This guide is intended for the following personnel;

•  Engineers responsible for installation, wiring, and maintenance of the equipment.

•  Personnel responsible for normal daily operation of the equipment.

1.  Safety Precautions

The following symbol is used on the instrument. It indicates the possibility of injury 

to the user or damage to the instrument, and signifies that the user must refer to the 

operation guide or user’s manual for special instructions. The same symbol is used in 

the operation guide and user’s manual on pages that the user needs to refer to, together 

with the term “WARNING” or “CAUTION.”

WARNING 

Calls attention to actions or conditions that could cause serious 

or fatal injury to the user, and indicates precautions that should be 

taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to 

the user or damage to the instrument or property and indicates pre-

cautions that should be taken to prevent such occurrences.

AC

AC/DC

 

The equipment wholly protected by double insulation or reinforced insulation.

  

Functional grounding terminals 

   

(Do not use this terminal as a protective grounding terminal).

Note

Identifies important information required to operate the instrument.

  Warning and Disclaimer

(1) YOKOGAWA makes no warranties regarding the product except those stated in 

the WARRANTY that is provided separately.

(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to 

any person or entity for any loss or damage, direct or indirect, arising from the 

use of the product or from any unpredictable defect of the product.

  Safety, Protection, and Modification of the Product

(1) In order to protect the system controlled by this product and the product itself, 

and to ensure safe operation, observe the safety precautions described in the 

operation guide. Use of the instrument in a manner not prescribed herein may 

compromise the product's functions and the protection features inherent in the 

device. We assume no liability for safety, or responsibility for the product's quality, 

performance or functionality should users fail to observe these instructions when 

operating the product.

(2) Installation  of protection  and/or safety circuits with respect to a lightning 

protector; protective equipment for the system controlled by the product and the 

product itself; foolproof or fail-safe design of a process or line using the system 

controlled by the product or the product itself; and/or the design and installation 

of other protective and safety circuits are to be appropriately implemented as the 

customer deems necessary.

(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts 

or consumables.

(4) This product is not designed or manufactured to be used in critical applications 

that directly affect or threaten human lives. Such applications include nuclear 

power  equipment,  devices  using  radioactivity,  railway  facilities,  aviation 

equipment, air navigation facilities, aviation facilities, and medical equipment. 

If so used, it is the user’s responsibility to include in the system additional 

equipment and devices that ensure personnel safety.

(5) Modification of the product is strictly prohibited.

(6) This product is intended to be handled by skilled/trained personnel for electric devices.

(7) This product is UL Recognized Component. In order to comply with UL standards, 

end-products are necessary to be designed by those who have knowledge of the 

requirements.

WARNING 

Power Supply

  Ensure that the instrument’s supply voltage matches the voltage 

of the power supply before turning ON the power.

l

  Do Not Use in an Explosive Atmosphere

  Do not operate the instrument in locations with combustible 

or explosive gases or steam. Operation in such environments 

constitutes an extreme safety hazard. Use of the instrument in 

environments with high concentrations of corrosive gas (H

2

S, 

SO

X

, etc.) for extended periods of time may cause a failure.

l

  Do Not Remove Internal Unit

  The internal unit should not be removed by anyone other than 

YOKOGAWA's service personnel. There are dangerous high voltage 

parts inside. Additionally, do not replace the fuse by yourself.

l

  Damage to the Protective Construction

  Operation of the instrument in a manner not specified in the 

operation guide may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-

ment this product may cause radio interference in which case the 

user needs to take adequate measures.

2.  Model and Suffix Codes

  UT32A-D/MDL «Standard Code Model»

Model

Suffix code

Option 

code

Description

UT32A

/MDL

(Required)

Digital Indicating Controller (Power supply: 100-240 

V AC) (provided with 3 DIs, and 3 DOs) (*2)

Type 1: 

Basic 

control

-D

Dual-loop type

Type 2: 

Functions

1

RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire)

Type 3: 

Open networks

0

None

Fixed code

-1

Temperature unit: deg C & deg F

Case color

1

Black (Light charcoal gray)

Fixed code

-00

Always "-00" (for Standard Code Model)

Option codes

/MDL

(Required)

Mount on DIN rail (without the display parts and keys)

/DC

Power supply 24 V AC/DC

/CT

Coating (*1)

/CV

Terminal cover

*1:  When the /CT option is specified, the UT32A does not conform to the safety standards (UL 

and CSA) and CE marking (Products with /CT option are not intended for EEA-market).

*2:  UT32A-D has a panel mount type (without option /MDL). Please see the Operation Guide 

(IM 05P08D31-11EN).

* For information on other Model types, see Manuals in Section-9.

■ Customized Product

  For customized product, the product is identified by the option code of /S# (where ‘#’ 

is a number).

  Contact your supplier in case your instrument has option /S#, and you are not 

in the possession of FX1-[Model code]-S# or IM [Model code]-S# (where [Model 

code] means, for example, UT55A).

  Accessories (sold separately)

The following is an accessory sold separately.

•  LL50A Parameter Setting Software

Model

Suffix code

Description

LL50A

-00

Parameter Setting Software

•  External Precision Resistor 

Model

Suffix code

Description

X010

See the General Specifications (*) Resistance Module

 

*: Necessary to input the current signal to the voltage input terminal.

•  Terminal Cover

  For UT32A: Model UTAP002

• Manuals

 

Note: Manuals can be downloaded from a website. URL: http://www.yokogawa.com/ns/ut/im/

• Brackets

  Part number: L4502TP (2 pcs for upper and lower sides)

•  Wall mount bracket

  For UT32A-D/MDL: Model UTAP005

•  Areas close to flammable articles

  Absolutely do not place the instrument directly on flam-

mable surfaces. If such a circumstance is unavoidable 

and the instrument must be placed close to a flammable 

item, provide a shield for it made of 1.43 mm thick plated 

steel or 1.6 mm thick unplated steel with a space of at 

least 150 mm between it and the instrument on the top, 

bottom, and sides.

•  Areas subject to being splashed with water

WARNING 

Be sure to turn OFF the power supply to the controller before in-

stalling it on the enclosure to avoid an electric shock.

  Mounting on a DIN Rail

Insert the DIN rail into the top area of DIN rail groove (at one location) on the rear 

panel, and secure in place with the bottom slide lock.

DIN rail

DIN rail

Slide lock

Fit into here

Push

CAUTION

Make sure that foreign materials do not enter the inside of the in-

strument through the case’s slit holes.

  Removing from the DIN Rail

Insert a flat-blade screwdriver (guideline: 100 mm shaft length, 6 mm blade width, 0.8 

mm blade thickness) into the bottom slide lock hole and pull down to release the slide 

lock. When slide lock is unlocked, the instrument can be removed from the DIN rail.

DIN rail

Slide lock

Pull

Push up

DIN rail

150 mm

150 mm

150 mm

150 mm

Operation

Guide

IM 05P08D81-11EN

UT32A-D/MDL

Digital Indicating Controller

 

(Dual-loop, DIN Rail Mounting Type)

Operation Guide

This operation guide describes installation, wiring, and other tasks required to make the 

controller ready for operation.

4th Edition : Mar. 2018

«Standard Code Model»

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATION

Network Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN

YOKOGAWA CORPORATION OF AMERICA

Head office and for product sales

2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.

Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2015 Yokogawa Electric Corporation

 

Protection of Environment

  Waste Electrical and Electronic Equipment (WEEE), Directive

This is an explanation of how to dispose of this product based on Waste Electrical 

and Electronic Equipment (WEEE), Directive. This directive is only valid in the EU.

●  Marking

This  product  complies  with  the  WEEE  Directive  marking 

requirement. This marking indicates that you must not discard 

this electrical/electronic product in domestic household waste.

●  Product Category

With reference to the equipment types in the WEEE directive, 

this product is classified as a “Small equipment” product.
Do not dispose in domestic household waste. When disposing 

products in the EU, contact your local Yokogawa Europe B.V. office.

3.  How to Install

  Installation Location

The instrument should be installed in indoor locations meeting the following 

conditions:

•  Instrumented enclosure

  This instrument is designed to be mounted in an instrumented enclosure. Mount 

the instrument in a location where its terminals will not inadvertently be touched.

 

Be sure to mount the instrument in an enclosure with a door.

•  Well ventilated locations

  Mount the instrument in well ventilated locations to prevent the instrument’s inter-

nal temperature from rising. 

  However, make sure that the terminal portions are not exposed to wind. Exposure 

to wind may cause the temperature sensor accuracy to deteriorate. To mount mul

-

tiple indicating controllers, see the external dimensions which follow. If mounting 

other instruments adjacent to the instrument, comply with these external dimen-

sions to provide sufficient clearance between the instruments.

•  Locations with little mechanical vibration

  Install the instrument in a location subject to little mechanical vibration.

•  Horizontal location

  Mount the instrument horizontally and ensure that it is level, with no inclination to 

the right or left.

Note

If the instrument is moved from a location with low temperature and low humidity 

to a place with high temperature and high humidity, or if the temperature changes 

rapidly, condensation will result. Moreover, in the case of thermocouple inputs, 

measurement errors will result. To avoid such a situation, leave the instrument in the 

new environment under ambient conditions for more than 1 hour prior to using it.

Do not mount the instrument in the following locations:

• Outdoors

•  Locations subject to direct sunlight or close to a heater

  Install the instrument in a location with stable temperatures that remain close to an 

average temperature of 23°C. Do not mount it in locations subject to direct sunlight 

or close to a heater. Doing so adversely affects the instrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or 

corrosive gases

  The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely 

affects the instrument. Do not mount the instrument in locations subject to any of 

these substances.

•  Areas near electromagnetic field generating sources

  Do not place magnets or tools that generate magnetism near the instrument. If the 

instrument is used in locations close to a strong electromagnetic field generating 

source, the magnetic field may cause measurement errors.

Отзывы: