7. Setup Procedure
The following flowchart shows the setup procedure for UT32A-D/MDL.
Perform setup through communication or the LL50A Parameter Setting Software (sold
separately).
Install and wire a controller.
Monitoring and control of regular operations
Adjust PID using auto-tuning or manually for PID control.
(Set parameters through communication.)
Operation
NO
YES
PID tuning
Installation
and wiring
Power ON
Parameter
Settings
Parameter
Settings
Use LL50A
Software?
LL50A: Parameter setting software (sold
separately)
See the LL50A Parameter Setting Software
User’s Manual (IM 05P05A01-01EN).
Use LL50A with the controller turned on.
(The dedicated cable must be connected.
LL50A Light-loader adapter cannot be
used.)
The maintenance port is not isolated from
the PV input terminal. Use the port only for
maintenance purposes, such as for setting
the controller parameters.
To set parameters through
communication, you need to
create a program on the host
device side. For controller
parameter information (registers,
relays), see the following
manuals.
• For setup through RS485 serial
communication or Ethernet
communication, see the
UTAdvanced Series Communi-
cation Interface User’s Manual
(IM 05P07A01-01EN).
• For setup through an open
network, see the UTAdvanced
Series Communication
Interface (Open Network)
User’s Manual (IM 05P07A01-
02EN).
8. Operations
The controller status can be verified with the LED.
Status
LED
Lit/Blinks
Description
Normal
Green
Lit
Communication error
Green
Blinks
Check the communication wiring and settings.
Instrument failure
Red
Lit
Parameter error/Hardware failure/Ladder program
corruption.
Input error
Red
Blinks
S
ensor burnout, input over
Check the input wiring and settings.
LED lamp
UT32A/MDL Front
(with terminal cover)
Check the operating status (run/stop, auto/manual, remote/local, etc.) of the
controller through communication or the LL50A Parameter Setting Software (sold
separately).
For details, see the (1) UT32A-D Digital Indicating Controller User’s Manual (IM
05P08D81-01EN), (2) UTAdvanced Series Communication Interface (RS-485,
Ethernet) User’s Manual (IM 05P07A01-01EN), and (3) LL50A Parameter Setting
Software User’s Manual (IM 05P05A01-02EN).
9. Troubleshooting
If a problem appears to be complicated, contact our sales representatives.
Is the controller
defective?
Contact us for repair. Problem solved.
The LED lamp
is unlit.
Yes
Yes
No
Yes
No
No
Yes
Check wiring of the
power terminals.
The LED
lamp is flashing
in red.
(I/O signal failure?)
The LED lamp is
lit in red.
Yes
No
Check the
supply voltage.
Check the
specifications and polarity
of connected devices .
Check the communication-
related parameters.
Check the specifications
of communication
devices.
Check the
communication wiring.
(Communication failure?)
Yes
Normal?
Check the specifications
of the controller.
Yes
No
Correct?
Correct the error(s).
Check the I/O specifications
of the controller.
The LED
lamp is flashing
in green.
■
Errors at Power On
The errors shown below may occur in the fault diagnosis when the power is turned on. (For details of Setpoint display and input/output action when each error occurs, see User’s Manual (IM
05P08D31-01EN).)
You can view the details of each error through communication or the LL50A Parameter Setting Software (sold separately). (View on the register monitor.)
For details on each register, see the UTAdvanced Series Communication Interface (RS485, Ethernet) User’s Manual (IM 05P07A01-01EN).
LED display
Parameter that displays error details
Error description
Cause and diagnosis
Remedy
Unlit
—
Faulty MCU RAM / MCU ROM
MCU RAM / MCU ROM are failed.
Faulty. Contact us for repair.
Red, lit
Setup parameter (PA.ER)
(Register no.: 2068) Bit 0=1
System data error
System data is corrupted.
Faulty. Contact us for repair.
Setup parameter (PA.ER)
(Register no.: 2068) Bit 1=1
Calibration value error
Initialized to calibrated default value because of corrupted factory default
value.
Faulty. Contact us for repair.
Setup parameter (PA.ER)
(Register no.: 2068) Bit 2=1
User (parameter) default value
error
User parameter is corrupted.
Initialized to factory default value.
Check and reconfigure the initialized
setting parameters. Error indication is
erased when the power is turned on
again.
Setup parameter (PA.ER)
(Register no.: 2068) Bit 4=1
Setup parameter error
Setup parameter data is corrupted.
Initialized to user default value.
Setup parameter (PA.ER)
(Register no.: 2068) Bit 5=1
Operation parameter error
Operation parameter data is corrupted.
Initialized to user default value.
Setup parameter (PA.ER)
(Register no.: 2068) Bit 8=1
Faulty FRAM
Data writing (storing) to FRAM is impossible.
Faulty. Contact us for repair.
Setup parameter (OP.ER)
(Register no.: 2070) Bit 0=1
Nonresponding hardware of
extended function (E1 to E4-
terminal areas)
Inconsistence of system data and hardware of extended function.
Nonresponding communication between hardware of extended
function (E1 to E4-terminal areas).
Faulty. Contact us for repair.
Setup parameter (LA.ER)
(Register no.: 2012) Bit 0=1
Corrupted ladder program
Ladder program is corrupted.
Operates without ladder program.
Download the ladder program again.
■
Errors during Operation
The errors shown below may occur during operation. (For input/output action when each error occurs, see User’s Manual (IM 05P08D31-01EN).)
You can view the details of each error through communication or the LL50A Parameter Setting Software (sold separately). (View on the register monitor.)
For details on each register, see the UTAdvanced Series Communication Interface (RS485, Ethernet) User’s Manual (IM 05P07A01-01EN).
LED display
Parameter that displays
error details
Error description
Cause and diagnosis
Remedy
Red, lit
Setup parameter (AD1.E)
(Register no.: 2001)
PV input: Bit 0=1
PV2 input: Bit 1=1
Analog input terminal ADC error
•PV input
•PV2 input (E1-terminal area)
Analog input terminal AD value error
Faulty.
Contact us for repair.
Setup parameter (AD1.E)
(Register no.: 2001)
PV input: Bit 5=1
PV2 input: Bit 6=1
Universal input terminal RJC error
•PV input
•PV2 input (E1-terminal area)
Universal input terminal RJC error
Faulty.
Contact us for repair.
Set the parameter RJC to OFF to erase
error indication.
Red, blinks
Setup parameter (AD1.E)
(Register no.: 2001)
PV input: Bit 8=1
PV2 input: Bit 9=1
Analog input terminal burnout error
•PV input
•PV2 input (E1-terminal area)
Analog input terminal sensor burnout
Check wiring and sensor.
Error indication is erased in normal
operation.
Setup parameter
Loop-1 (PV1.E) (Register no.: 2002) Bit 0=1
Loop-2 (PV2.E) (Register no.: 2018) Bit 0=1
PV input burnout error
(Loop-1, Loop-2)
Burnout of analog input connected to PV
Check wiring and sensor of connected
analog input terminals.
Error indication is erased in normal
operation.
Setup parameter
Loop-1 (PV1.E) (Register no.: 2002)
Over-scale: Bit 4=1
Under-scale: Bit 5=1
Loop-2 (PV2.E) (Register no.: 2018)
Over-scale: Bit 4=1
Under-scale: Bit 5=1
PV input over-scale
PV input under-scale
(PV values out of -5 to 105%)
(Loop-1, Loop-2)
PV input is out of -5 to 105%. Also occurs when the data out of range
which is the ladder calculation result is input.
Check analog input value or ladder
program.
Check the error in
LL50A software.
Setup parameter (LA.ER)
(Register no.: 2012)
Overflow: Bit 1=1
Ladder program error: Bit 1=1
Load factor over 100%: Bit 4=1
Load factor over 200%: Bit 5=1
Ladder calculation overflow
Floating point computation for ladder calculation is infinite.
Check the ladder program.
Ladder program error
Ladder program is corrupted.
Download the ladder program again. If
the error indication is still not erased,
there is a fault. Contact us for repair.
Load factor over 100%
Computation does not end within the control period (load factor is
100% or more).
Change the control period or reduce
the number of steps for the ladder
program.
Load factor over 200%
(Forced end)
Computation does not end within the control period (load factor is 200% or
more).
Change the control period or reduce the
number of steps for the ladder program.
Green, blinks
Setup parameter (OP.ER)
(Register no.: 2070) Bit 8=1
Peer-to-peer communication error Peer-to-peer communication error
Check that the target devices are
connected correctly.
Recovery at normal receipt.
Check the error in
LL50A software.
Setup parameter
Loop-1 (PV1.E) (Register no.: 2002) Bit 14=1
Loop-2 (PV2.E) (Register no.: 2018) Bit 14=1
Auto-tuning time-out
(Loop-1, Loop-2)
Auto-tuning does not end even when 24 hours have elapsed after the
start of tuning.
Check the process. Hold down any key to
erase the error indication
Green, blinks
Setup parameter (OP.ER)
(Register no.: 2070) Bit 8=1
Communication error
(RS-485 communication)
Framing parity error
Buffer overflow
Inter-character time-out
Checksum error (PC link communication with checksum)
CRC check error (Modbus/RTU)
LRC check error (Modbus/ASCII)
Check the communication parameters.
Recovery at normal receipt.
Hold down any key to stop blinking.
Communication error
(coordinated operation)
Inconsistence of loop between coordinated master and slaves
Check the communication parameters.
Recovery at normal receipt. Change from remote
to local mode to stop blinking.
When the mode is changed from remote to
local, SP tracking does not work even if it is
set to ON.
Communication from coordinated master is interrupted for 2 seconds.
Red, lit
Setup parameter (PA.ER)
(Register no.: 2068) Bit 8=1
Faulty FRAM
Writing (storing) data to FRAM is impossible.
Faulty. Contact us for repair.
Unlit
—
Faulty MCU / DCU
(ROM / RAM error, corrupted)
MCU / DCU is corrupted.
Faulty. Contact us for repair.
• Authorised Representative in the EEA
Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The Nether-
lands) is the Authorised Representative of Yokogawa Electric Corporation for this
Product in the EEA.
• Printed Manuals
Model
Description
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Standard code model
»
IM 05P01D31-11EN
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Detailed code model
»
IM 05P01D31-15EN
UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide
«
Standard code model
»
IM 05P01D81-11EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)
Operation Guide
«
Standard code model
»
IM 05P08D31-11EN
UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type)
Operation Guide
«
Standard code model
»
IM 05P08D81-11EN
UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote
Input, Panel Mounting Type) Operation Guide
«
Standard code model
»
IM 05P01D31-81EN
UT32A Digital Indicating Controller Operation Guide
«
Entry model
»
IM 05P01F31-11EN
Precautions on the Use of the UTAdvanced Series
IM 05P01A01-11EN
UTAP005 Wall Moount Bracket User's Manual
IM 05P06A31-02Z1
• Electronic Manuals
You can download the latest manuals from the following website:
URL: http://www.yokogawa.com/ns/ut/im/
Model
Description
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Standard code model
»
IM 05P01D31-11EN
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Detailed code model
»
IM 05P01D31-15EN
UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide
«
Standard code model
»
IM 05P01D81-11EN
UT35A/UT32A Digital Indicating Controller User’s Manual
IM 05P01D31-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)
Operation Guide
«
Standard code model
»
IM 05P08D31-11EN
UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type)
Operation Guide
«
Standard code model
»
IM 05P08D81-11EN
UT32A-D, UT32A-D/MDL Digital Indicating Controller User’s Manual
IM 05P08D31-01EN
UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote
Input, Panel Mounting Type) Operation Guide
«
Standard code model
»
IM 05P01D31-81EN
UT32A Digital Indicating Controller Operation Guide
«
Entry model
»
IM 05P01F31-11EN
UT32A Digital Indicating Controller User’s Manual
«
Entry model
»
IM 05P01F31-01EN
UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
UTAdvanced Series Communication Interface (Open Network) User’s Manual
IM 05P07A01-02EN
LL50A Parameter Setting Software Installation Manual
IM 05P05A01-01EN
LL50A Parameter Setting Software User’s Manual
IM 05P05A01-02EN
Precautions on the Use of the UTAdvanced Series
IM 05P01A01-11EN
UTAP005 Wall Moount Bracket User's Manual
IM 05P06A31-02Z1
• General Specification
Model
Description
UT35A/UT32A Digital Indicating Controller (Panel Mounting Type)
GS 05P01D31-01EN
UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01D81-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)
GS 05P08D31-01EN
UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) GS 05P08D81-01EN
LL50A Parameter Setting Software
GS 05P05A01-01EN
*
The last two characters of the manual number and general specification number indicate the
language in which the manual is written.