IM 05P08D81-11EN  page 4/4

7.  Setup Procedure

The following flowchart shows the setup procedure for UT32A-D/MDL. 

Perform setup through communication or the LL50A Parameter Setting Software (sold 

separately).

Install and wire a controller.

Monitoring and control of regular operations

Adjust PID using auto-tuning or manually for PID control.

 

(Set parameters through communication.)

Operation

NO

YES

PID tuning

Installation

and wiring

Power ON

Parameter

Settings

Parameter

Settings

Use LL50A

Software?

LL50A: Parameter setting software (sold 

separately)

See the LL50A Parameter Setting Software 

User’s Manual (IM 05P05A01-01EN).

Use LL50A with the controller turned on. 

(The dedicated cable must be connected. 

LL50A Light-loader adapter cannot be 

used.)

The maintenance port is not isolated from 

the PV input terminal. Use the port only for 

maintenance purposes, such as for setting 

the controller parameters.

To set parameters through 

communication, you need to 

create a program on the host 

device side. For controller 

parameter information (registers, 

relays), see the following 

manuals.

• For setup through RS485 serial 

communication or Ethernet 

communication, see the 

UTAdvanced Series Communi-

cation Interface User’s Manual 

(IM 05P07A01-01EN).

• For setup through an open 

network, see the UTAdvanced 

Series Communication 

Interface (Open Network) 

User’s Manual (IM 05P07A01-

02EN).

8.  Operations

The controller status can be verified with the LED.

Status

LED

Lit/Blinks

Description

Normal

Green

Lit

Communication error

Green

Blinks

Check the communication wiring and settings.

Instrument failure

Red

Lit

Parameter error/Hardware failure/Ladder program 

corruption.

Input error

Red

Blinks

S

ensor burnout, input over

Check the input wiring and settings.

LED lamp

UT32A/MDL Front

(with terminal cover)

Check the operating status (run/stop, auto/manual, remote/local, etc.) of the 

controller through communication or the LL50A Parameter Setting Software (sold 

separately).

For details, see the (1) UT32A-D Digital Indicating Controller User’s Manual (IM 

05P08D81-01EN), (2) UTAdvanced Series Communication Interface (RS-485, 

Ethernet) User’s Manual (IM 05P07A01-01EN), and (3) LL50A Parameter Setting 

Software User’s Manual (IM 05P05A01-02EN).

9.  Troubleshooting

If a problem appears to be complicated, contact our sales representatives.

Is the controller

defective?

Contact us for repair. Problem solved.

The LED lamp 

is unlit.

Yes

Yes

No

Yes

No

No

Yes

Check wiring of the

power terminals.

The LED

 lamp is flashing 

in red.

(I/O signal failure?)

The LED lamp is 

lit in red.

Yes

No

Check the 

supply voltage.

Check the 

specifications and polarity

 of connected devices .

Check the communication-

related parameters.

Check the specifications

of communication 

devices.

Check the

communication wiring.

(Communication failure?)

Yes

Normal?

Check the specifications

of the controller.

Yes

No

Correct?

Correct the error(s).

Check the I/O specifications

of the controller.

The LED

 lamp is flashing 

in green.

  Errors at Power On

The errors shown below may occur in the fault diagnosis when the power is turned on. (For details of Setpoint display and input/output action when each error occurs, see User’s Manual (IM 

05P08D31-01EN).)

You can view the details of each error through communication or the LL50A Parameter Setting Software (sold separately). (View on the register monitor.)

For details on each register, see the UTAdvanced Series Communication Interface (RS485, Ethernet) User’s Manual (IM 05P07A01-01EN).

LED display

Parameter that displays error details

Error description

Cause and diagnosis

Remedy

Unlit

Faulty MCU RAM / MCU ROM

MCU RAM / MCU ROM are failed.

Faulty.  Contact us for repair.

Red, lit

Setup parameter (PA.ER)

(Register no.: 2068) Bit 0=1

System data error

System data is corrupted.

Faulty.  Contact us for repair.

Setup parameter (PA.ER)

(Register no.: 2068) Bit 1=1

Calibration value error

Initialized to calibrated default value because of corrupted factory default 

value.

Faulty.  Contact us for repair.

Setup parameter (PA.ER)

(Register no.: 2068) Bit 2=1

User (parameter) default value 

error

User parameter is corrupted.

Initialized to factory default value.

Check and reconfigure the initialized 

setting parameters. Error indication is 

erased when the power is turned on 

again.

Setup parameter (PA.ER)

(Register no.: 2068) Bit 4=1

Setup parameter error

Setup parameter data is corrupted.

Initialized to user default value.

Setup parameter (PA.ER)

(Register no.: 2068) Bit 5=1

Operation parameter error

Operation parameter data is corrupted.

Initialized to user default value.

Setup parameter (PA.ER)

(Register no.: 2068) Bit 8=1

Faulty FRAM

Data writing (storing) to FRAM is impossible.

Faulty.  Contact us for repair.

Setup parameter (OP.ER)

(Register no.: 2070) Bit 0=1

Nonresponding hardware of 

extended function (E1 to E4-

terminal areas)

Inconsistence of system data and hardware of extended function.

Nonresponding communication between hardware of extended 

function (E1 to E4-terminal areas).

Faulty. Contact us for repair.

Setup parameter (LA.ER)

(Register no.: 2012) Bit 0=1

Corrupted ladder program

Ladder program is corrupted. 

Operates without ladder program.

Download the ladder program again.

  Errors during Operation

The errors shown below may occur during operation. (For input/output action when each error occurs, see User’s Manual (IM 05P08D31-01EN).)

You can view the details of each error through communication or the LL50A Parameter Setting Software (sold separately). (View on the register monitor.)

For details on each register, see the UTAdvanced Series Communication Interface (RS485, Ethernet) User’s Manual (IM 05P07A01-01EN).

LED display

Parameter that displays

error details

Error description

Cause and diagnosis

Remedy

Red, lit

Setup parameter (AD1.E)

(Register no.: 2001)

PV input: Bit 0=1

PV2 input: Bit 1=1

Analog input terminal ADC error

•PV input

•PV2 input (E1-terminal area)

Analog input terminal AD value error

Faulty.

Contact us for repair.

Setup parameter (AD1.E)

(Register no.: 2001)

PV input: Bit 5=1

PV2 input: Bit 6=1

Universal input terminal RJC error

•PV input

•PV2 input (E1-terminal area)

Universal input terminal RJC error

Faulty.

Contact us for repair.

Set the parameter RJC to OFF to erase 

error indication.

Red, blinks

Setup parameter (AD1.E)

(Register no.: 2001)

PV input: Bit 8=1

PV2 input: Bit 9=1

Analog input terminal burnout error

•PV input

•PV2 input (E1-terminal area)

Analog input terminal sensor burnout

Check wiring and sensor.

Error indication is erased in normal 

operation.

Setup parameter

Loop-1 (PV1.E) (Register no.: 2002) Bit 0=1

Loop-2 (PV2.E) (Register no.: 2018) Bit 0=1

PV input burnout error

(Loop-1, Loop-2)

Burnout of analog input connected to PV

Check wiring and sensor of connected 

analog input terminals.

Error indication is erased in normal 

operation.

Setup parameter

Loop-1 (PV1.E) (Register no.: 2002)

Over-scale: Bit 4=1

Under-scale: Bit 5=1

Loop-2 (PV2.E) (Register no.: 2018)

Over-scale: Bit 4=1

Under-scale: Bit 5=1

PV input over-scale

PV input under-scale

(PV values out of -5 to 105%)

(Loop-1, Loop-2)

PV input is out of -5 to 105%. Also occurs when the data out of range 

which is the ladder calculation result is input.

Check analog input value or ladder 

program.

Check the error in 

LL50A software. 

Setup parameter (LA.ER)

(Register no.: 2012)

Overflow: Bit 1=1

Ladder program error: Bit 1=1

Load factor over 100%: Bit 4=1

Load factor over 200%: Bit 5=1

Ladder calculation overflow

Floating point computation for ladder calculation is infinite.

Check the ladder program.

Ladder program error

Ladder program is corrupted.

Download the ladder program again. If 

the error indication is still not erased, 

there is a fault. Contact us for repair.

Load factor over 100%

Computation does not end within the control period (load factor is 

100% or more).

Change the control period or reduce 

the number of steps for the ladder 

program.

Load factor over 200%

(Forced end)

Computation does not end within the control period (load factor is 200% or 

more).

Change the control period or reduce the 

number of steps for the ladder program.

Green, blinks

Setup parameter (OP.ER)

(Register no.: 2070) Bit 8=1

Peer-to-peer communication error Peer-to-peer communication error

Check that the target devices are 

connected correctly.

Recovery at normal receipt.

Check the error in 

LL50A software. 

Setup parameter

Loop-1 (PV1.E) (Register no.: 2002) Bit 14=1

Loop-2 (PV2.E) (Register no.: 2018) Bit 14=1

Auto-tuning time-out

(Loop-1, Loop-2)

Auto-tuning does not end even when 24 hours have elapsed after the 

start of tuning.

Check the process. Hold down any key to 

erase the error indication

Green, blinks

Setup parameter (OP.ER)

(Register no.: 2070) Bit 8=1

Communication error 

(RS-485 communication)

Framing parity error

Buffer overflow 

Inter-character time-out 

Checksum error (PC link communication with checksum) 

CRC check error (Modbus/RTU)

LRC check error (Modbus/ASCII)

Check the communication parameters.

Recovery at normal receipt.

Hold down any key to stop blinking.

Communication error 

(coordinated operation)

Inconsistence of loop between coordinated master and slaves

Check the communication parameters.

Recovery at normal receipt. Change from remote 

to local mode to stop blinking.

When the mode is changed from remote to 

local, SP tracking does not work even if it is 

set to ON.

Communication from coordinated master is interrupted for 2 seconds.

Red, lit

Setup parameter (PA.ER)

(Register no.: 2068) Bit 8=1

Faulty FRAM

Writing (storing) data to FRAM is impossible.

Faulty. Contact us for repair.

Unlit

Faulty MCU / DCU

(ROM / RAM error, corrupted)

MCU / DCU is corrupted.

Faulty. Contact us for repair.

•  Authorised Representative in the EEA

  Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The Nether-

lands) is the Authorised Representative of Yokogawa Electric Corporation for this 

Product in the EEA.

•  Printed Manuals

Model

Description

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Standard code model

»

IM 05P01D31-11EN

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Detailed code model

»

IM 05P01D31-15EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) 

Operation Guide 

«

Standard code model

»

IM 05P01D81-11EN

UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) 

Operation Guide 

«

Standard code model

»

IM 05P08D31-11EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) 

Operation Guide 

«

Standard code model

»

IM 05P08D81-11EN

UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote 

Input, Panel Mounting Type) Operation Guide 

«

Standard code model

»

IM 05P01D31-81EN

UT32A Digital Indicating Controller Operation Guide 

«

Entry model

»

IM 05P01F31-11EN

Precautions on the Use of the UTAdvanced Series

IM 05P01A01-11EN

UTAP005 Wall Moount Bracket User's Manual

IM 05P06A31-02Z1

•  Electronic Manuals

  You can download the latest manuals from the following website:

  URL: http://www.yokogawa.com/ns/ut/im/

Model

Description

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Standard code model

»

IM 05P01D31-11EN

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Detailed code model

»

IM 05P01D31-15EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) 

Operation Guide 

«

Standard code model

»

IM 05P01D81-11EN

UT35A/UT32A Digital Indicating Controller User’s Manual

IM 05P01D31-01EN

UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) 

Operation Guide 

«

Standard code model

»

IM 05P08D31-11EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) 

Operation Guide 

«

Standard code model

»

IM 05P08D81-11EN

UT32A-D, UT32A-D/MDL Digital Indicating Controller User’s Manual

IM 05P08D31-01EN

UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote 

Input, Panel Mounting Type) Operation Guide 

«

Standard code model

»

IM 05P01D31-81EN

UT32A Digital Indicating Controller Operation Guide 

«

Entry model

»

IM 05P01F31-11EN

UT32A Digital Indicating Controller User’s Manual 

«

Entry model

»

IM 05P01F31-01EN

UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
UTAdvanced Series Communication Interface (Open Network) User’s Manual

IM 05P07A01-02EN

LL50A Parameter Setting Software Installation Manual

IM 05P05A01-01EN

LL50A Parameter Setting Software User’s Manual

IM 05P05A01-02EN

Precautions on the Use of the UTAdvanced Series

IM 05P01A01-11EN

UTAP005 Wall Moount Bracket User's Manual

IM 05P06A31-02Z1

•  General Specification

Model

Description

UT35A/UT32A Digital Indicating Controller (Panel Mounting Type)

GS 05P01D31-01EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01D81-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)

GS 05P08D31-01EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) GS 05P08D81-01EN
LL50A Parameter Setting Software

GS 05P05A01-01EN

The last two characters of the manual number and general specification number indicate the 

language in which the manual is written.