IM 05P02D41-11EN   page 10/14

5.  Switching between AUTO and MAN

AUTO and MAN switching can be performed using any of the following: (1) MODE 

key, (2) Contact input, (3) Contact input, and (4) Communication.

The following shows an example of switching using the MODE key.

When AUTO and MAN switching function is assigned to the contact input, and the 

contact input is ON, the switching by key operation cannot be performed.

For details, see User’s Manual.

Displays ”MODE MAN” in AUTO mode. 

Displays ”MODE AUTO” in MAN mode.

1.
2.

3.

Press MODE key several times.

Show the Operation Display.

4.

MAN lamp is lit in MAN mode.

Press the SET/ENTER key.

When AUTO is switched into MAN, the control output value in AUTO mode is held. 

The controller can be operated manually from the hold value.

If the manual preset output is set (MPON parameter ≠ OFF), the controller can be 

operated manually from the arbitrary output value (MPO1 to MPO5 parameters).

6.  Manipulating Control Output in Manual Mode

NOTE

In manual mode, control output is manipulated by operating the keys (the value is 

changed using the Up/Down arrow keys, then outputted as it is).

Even if the SET/ENTER key is not pressed, the control output value changes ac-

cording to the displayed value.

In stop mode (when the RST lamp is lit), control output cannot be manipulated.

MAN lamp is lit.

Up arrow key: increases control output.
Down arrow key: decreases control output.

In Position proportional control:

Up arrow key; opens the valve.

Down arrow key; closes the valve.

Output; only while pressing a key. 

OUT; valve opening (0-100%)

Output manipulation in Position proportional control 

is not restricted from output limiters (OH, OL).

Manual operation in Heating/cooling control

Symbol of cooling side

Program pattern (PTNO.) number

Symbol of heating side

Heating-side control output

Cooling-side control output

Up arrow key: concurrently decreases cooling-side control output and increases 

heating-side control output.

Down arrow key: concurrently increases cooling-side control output and decreases 

heating-side control output.

(Either none of the heating-side and cooling-side outputs are presented, or both of 

them are presented according to the dead band setting.)

Actual output (%)

DB=24.8

Dead band: Operation parameter DB

Control computation output

Control computation output

12.4

0

-12.4

Manipulated output change

when a dead band is positive (+)

Actual output (%)

100

DB= -24.8

12.4

0

-12.4

Manipulated output change

when a dead band is negative (-)

100

Cooling-side

manipulated output

Heating-side

manipulated output

Heating-side

manipulated output

Cooling-side

manipulated output

7.  Enabling/Disabling Hold Mode of Program Operation

Enabling/disabling hold mode of program operation can be performed during pro-

gram operation using any of the following: (1) MODE key, (2) Parameter, (3) Contact 

input, and (4) Communication.

The following shows an example of switching using the MODE key.

1.
2.

3.

4.

Show the Operation Display.

Press the MODE key.

The number of segments included 

in the selected program pattern.

The segment number for which 

operation is in progress.

The figure below is displayed while the right 

arrow key hold down.

Displays ”HOLD ON” in PROG mode. 

Displays ”HOLD OFF” in HOLD mode.

HLD lamp is lit in HOLD mode.

Press the SET/ENTER key.

The parameter HOLD (Pause/cancel release 

of program operation) is displayed (during 

program operation.) 

1.
2.

3.

4.

Show the Operation Display.

Press the MODE key.

The number of segments included 

in the selected program pattern.

The segment number for which 

operation is in progress.

The figure below is displayed while the right 

arrow key hold down.

Displays ”HOLD ON” in PROG mode. 

Displays ”HOLD OFF” in HOLD mode.

HLD lamp is lit in HOLD mode.

Press the SET/ENTER key.

The parameter HOLD (Pause/cancel release 

of program operation) is displayed (during 

program operation.) 

Other operating procedures for disabling the hold mode:

(1) Press the RUN key for 1 second during hold-mode operation. In this case, the 

controller resumes program operation.

(2) Execute the “Advance“ function during hold-mode operation. In this case, the 

segment is advanced.

8.  Changing Program Setpoints when in Hold Mode

The following operating procedures changes a program setpoint of soak segment 

during Hold-mode operation.

The program operation is started when releasing the Hold after changing the pro-

gram setpoint.

1.

2.

Set program operation in hold mode.

3.

4.

Blinks during the change.

Blinks during the change.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Up/Down arrow keys to display the required setpoint.

9.  Executing “Advance” Function

“Advance” can be performed during program operation using any of the following: (1) 

MODE key, (2) Parameter, (3) Contact input, and (4) Communication.

The following shows an example of switching using the MODE key.

When executing the “Advance” function during hold-mode operation, the hold mode is disabled.

1.

2.

3.

4.

The segment is advanced.

Press the SET/ENTER key.

Show the Operation Display.

Press the MODE key.

The ADV (Advance of segment) is displayed (during 

program operation.)

10.  Switching to Local-mode (LOCAL) Operation

Switching to local-mode can be performed using any of the following: 

(1) MODE key (user function key), (2) Parameter, (3) Contact input, and (4) Communication.

The following shows an example of switching using the MODE key.

1.

2.

3.

4.

“LSP” is displayed when 

in local-mode operation.

Press the SET/ENTER key.

Show the Operation Display.

Press the MODE key several times.

The LOC (local operation) is displayed.

■ Remedies if Power Failure Occurs 

during Operations

•  Instantaneous power failure within 20 ms.

 

A power failure is not detected. Normal 

operation continues.

•  Power failure for less than about 5 seconds, 

or for about 5 seconds or more.

 

Affects the "settings" and "operation sta-

tus."

  For details, see User's Manual.

NOTE

Write down the settings of parameters for a 

repair request.

■ For the Errors at Power On 

and the Errors during Op-

eration, see “Parameters” 

in this manual.

1.

2.

3.

4.

“LSP” is displayed when 

in local-mode operation.

Press the SET/ENTER key.

Show the Operation Display.

Press the MODE key several times.

The LOC (local operation) is displayed.

11.  Changing Setpoints during Local-mode Operation

The following operating procedures changes setpoints during local-mode operation.

1.

2.

3.

4.

“LSP” is displayed when in local-mode operation.

Press the SET/ENTER key.

Press the SET/ENTER key.

Blinks during the change.

Blinks during the change.

Press the Up/Down arrow keys to display the required setpoint.

■ Troubleshooting Flow

If the Operation Display does not appear after turning on the controller’s power, check the procedures in the following flowchart.

If a problem appears to be complicated, contact our sales representatives.

Is the controller

defective?

Contact us for repair. Problem solved.

No communication

capability

Completely

inactive?

Yes

Yes

Yes

No

No

No

Key

operation

failure?

Yes

No

Yes

Check wiring of the

power terminals.

Check the key lock

setting.

Display

failure?

*

Yes

No

Turn off power, and

then turn it on again.

I/O signal

failure?

Yes

No

Check the 

supply voltage.

Check the 

specifications and polarity

 of connected devices .

Check the communication-

related parameters.

Check the specifications

of communication 

devices.

Check the

communication wiring.

Communication

failure?

No

With

communi-

cation?

Yes

Yes

Normal?

Is the 

key locked?

Check the specifications

of the controller.

Yes

No

Correct?

Correct the error(s).

Cancel the setting.

Check the I/O specifications

of the controller.

* The LCD (a liquid crystal display) is used for 

   a display portion of this product.

   The LCD has a characteristic that the display action 

   becomes late at the low temperature.

   Additionally, the luminance and contrast degradation

   are caused due to aged deterioration.

   However, the control function is not affected.

12. Troubleshooting

Содержание UP35A

Страница 1: ...AP option is specified 4 program patterns 40 program segments max 20 segments per pattern provided with retransmission output or 15 V DC loop power supply 3 DIs and 3 DOs Type 1 Basic control 0 Standa...

Страница 2: ...dards JIS IEC DIN ITS 90 for TC and RTD Contact Input Specifications Number of inputs See the table of Model and Suffix Codes Input type No voltage contact input or transistor contact input Input cont...

Страница 3: ...xiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay failure always insert a CR filter for use with alt...

Страница 4: ...t 1 output PV event 1 output Common Common Common UP 104 105 106 107 108 109 PV PV input TC input RTD input Voltage mV V input A Current mA input B b Equipped as standard 202 203 201 202 203 202 203 2...

Страница 5: ...PID control Other setup Operation NO NO NO YES YES YES Set the other parameters as needed Programming Set the program pattern PID tuning Input setup Output setup Installation and wiring Power ON Contr...

Страница 6: ...ess the Right arrow key until ALRM menu appears Press the SET ENTER key 4 5 Press the SET ENTER key The parameter AL1 alarm 1 type is displayed The last digit of the setpoint blinks Press the Up Down...

Страница 7: ...row keys to move between digits Change the setpoint using the Up Down arrow keys to increase and decrease the value and the Left Right arrow keys to move between digits Press the Down arrow key until...

Страница 8: ...22 Segment write error The total number of segments exceeded 20 40 when the option AP is specified ERR23 Segment insert error New segment cannot be inserted because the number of segments in a pattern...

Страница 9: ...ld down the PARAMETER key for 3 seconds to display MODE menu Press the SET ENTER key The parameter HOLD Pause cancel release of program operation is displayed during program operation Press the Down a...

Страница 10: ...rogram operation is displayed during program operation Other operating procedures for disabling the hold mode 1 Press the RUN key for 1 second during hold mode operation In this case the controller re...

Страница 11: ...17 Cooling side OUT high limit 18 Cooling side OUT low limit Add 100 for de energized For example when the PV high limit is de energized the setting is 101 OFF See Pro gram ming in this manual STD to...

Страница 12: ...PARAMETER or PARA key and Left arrow key simultaneously for 3 sec DISPLAY or DISP key PARAMETER or PARA key SET ENTER key Move to the Operation Parameter Setting Display Hold down the PARAMETER or PA...

Страница 13: ...Net Communication Setting Parameter E3 terminal Area Menu symbol DNET Parameter symbol Name of Parameter Setting Range Initial value User setting Display level BR Baud rate 125K 125k bps 250K 250k bps...

Страница 14: ...AR 0020 for operation parameter error only Operation parameter error Operation parameter data is corrupted Initialized to user default value PAR 0040 for program pattern error only Program pattern err...