
IM 05F01D02-03E (2)
2. Lists of Parameters
■
Operating Parameters
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User setting
Alarm 1-setpoint
Alarm 2-setpoint
Alarm 3-setpoint
Alarm 4-setpoint
PV alarm: -100.0 to 100.0% of PV input range
PV high limit
alarm:
100.0% of
PV input range
PV low limit
alarm:
0.0% of
PV input range
PV input filter
OFF, 1 to 120 second
Used when the PV input fluctuates.
OFF
PV input bias
-100.0% to 100.0% of PV input range span
Used to correct the PV input value.
0.0% of PV
input range
span
(A1)
(A2)
(A3)
(A4)
(FL)
(BS)
PV peak value
Displays the maximum value of PV input during operation.
This parameter is not to be set.
PV bottom value
Displays the minimum value of PV input during operation.
This parameter is not to be set.
(PEAK)
(BOTM)
■
Setup Parameters
●
Alarm/Communication-related Parameters
Alarm-1 type
Alarm-2 type
Alarm-3 type
Alarm-4 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 delay timer
0.0 to 100.0% of PV input range span
Hysteresis can be set in the alarm setpoint.
Setting hysteresis prevents relays from
chattering.
An alarm is output when the delay timer expires
after the alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm-
1 type “AL1” is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
2 type “AL2” is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
3 type “AL3” is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
4 type “AL4” is 1, 2, 9, 10, 11, 12, 19, and 20)
(AL1)
(AL2)
(AL3)
(AL4)
(HY1)
(HY2)
(HY3)
(HY4)
(DY1)
(DY2)
(DY3)
(DY4)
Parameter
Symbol
Name of Parameter
Setting Range and Description
User setting
OFF
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
9: PV high limit (de-energized, no stand-by action)
10: PV low limit (de-energized, no stand-by action)
11: PV high limit (energized, stand-by action)
12: PV low limit (energized, stand-by action)
19: PV high limit (de-energized, stand-by action)
20: PV low limit (de-energized, stand-by action)
21: Fault diagnosis output
Turns on in case of input burnout, A/D
converter failure, or reference junction
compensation (RJC) failure.
22: FAIL output
Turns off in case of program failure, ROM
failure, RAM failure, or power failure. This
output is on during normal operation. If it
turns off, the retransmission output is set to
0%, the alarm output is set to OFF, and the
indicator stops.
See “List of Alarm Types” on the right side of this
manual for details on how these Alarm Type
parameters behave.
Point of on-off action
(Alarm setpoint)
PV value
Output
On
Off
Hysteresis
Protocol selection
Baud rate
0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
Parity 0:
None
1: Even
2: Odd
Stop bit
1, 2
Data length
Address
1 to 99
However, the maximum number of stations
connectable is 31.
Minimum response
time
0 to 10 (
⫻
10 ms)
0: PC link communication
1: PC link communication (with checksum)
2: Ladder communication
7: MODBUS (ASCII)
8: MODBUS (RTU)
(P.SL)
(BPS)
(PRI)
(STP)
(DLN)
(ADR)
(RP.T)
1
2
1
2
0.5% of PV
input range span
0.00
Initial Value
0
4
1
1
8
1
0
(TEST)
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu.
Caution: Do not change the setpoint of the TEST parameter, otherwise the indicator will be disabled.
7, 8
Fixed at 7, when the P.SL parameter is set to
MODBUS (ASCII).
Fixed at 8, when the P.SL parameter is set to
MODBUS (RTU) or Ladder Communication.
Hysteresis setting for PV high limit alarm
Time
Hysteresis
Alarm setpoint
Alarm output
Delay timer
PV
on
off
Delay timer
*
Parameters relating to PV should all be set in real numbers.
For example, use temperature values to define alarm setpoints for
temperature input.
*
The “User Setting” column in the table below is provided for the customer to record setpoints.
●
Input-/Output-related Parameters
-1999 to 9999, however SL < SH
Set the read-out scale of voltage-mode PV input.
OFF
PV input unit
°
C: degree Celsius
°
F: Fahrenheit
°
C
Max. value of PV input
range
Min. value of PV input
range
Max. value of
instrument
input range
Min. value of
instrument
input range
Set the PV input range, however RL < RH
-Temperature input
Set the range of temperature that is actually indicated.
- Voltage input
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually
indicated should be set using the parameters
Maximum Value of PV Input Scale (SH) and Minimum
Value of PV Input Scale (SL).
PV input decimal point
position (displayed
at voltage input)
Max. value of PV input
scale
(displayed at voltage input)
Min. value of PV input
scale
(displayed at voltage input)
Selection of PV input
burnout action
Presence/absence of
PV input reference
junction compensation
0 to 3
Set the position of the decimal point of voltage-
mode PV input.
0: No decimal place
1: One decimal place
2, 3: Two, three decimal places
1
100.0
0.0
OFF
1: Up scale
2: Down scale
1
OFF, ON
ON
(IN)
(UNIT)
(RH)
(RL)
(SDP)
(SH)
(SL)
(BSL)
(RJC)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User Setting
PV input type (PV INPUT
terminals)
- - terminals
13
12
11
OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56
See Instrument Input Range Codes in
Initial
Settings User’s Manual
.
Retransmission output
type
OFF: Does not work.
1: PV
4: Loop power supply for sensor (15 V)
1
Max. value of
retransmission output
scale
Min. value of
retransmission output
scale
RET=1: RTL + 1 digit to 100.0% of PV
input range
RET=1: 0.0% of PV input range to
RTH - 1 digit
100.0% of
PV input range
0.0% of
PV input range
(RTH)
(RTL)
(RET)
DI function selection
1
(DIS)
SELECT display-1
registration
SELECT display-2
registration
SELECT display-3
registration
SELECT display-4
registration
OFF
OFF, 201 to 1015
For example, registering “231” for C.S1 allows you to
change alarm-1 setpoint in operating display.
Numbers for registering alarm SP parameter for
operating display:
Alarm-1 setpoint: 231 Alarm-2 setpoint: 232
Alarm-3 setpoint: 233 Alarm-4 setpoint: 234
(C.S1)
(C.S2)
(C.S3)
(C.S4)
Password setting
0: Password not set
1 to 9999
0
(PWD)
Key lock
OFF
(LOCK)
OFF: No key lock
1: Change to any parameter prohibited
Prohibits any operating parameter or setup
parameter from being changed. The setpoint
of the LOCK parameter itself can be changed,
however.
2: Change to and display of operating parameters
prohibited
Turns off the display for setting operating
parameters, thus prohibiting any change to
the parameter settings.
(Press the SET/ENT key for more than
3 seconds to show the password check
display.)
OFF: The external contact input is disabled.
1: Resets the values of the PEAK and BOTM
operating parameters to an off-to-on transition
of the DI1 input.
■
List of Alarm Types
The table below shows the alarm types and alarm actions.
In the table, codes 1, 2, 9, and 10 are not provided with stand-by actions, while codes 11, 12, 19, and 20 are provided with
stand-by actions.
Alarm action
Alarm action
Alarm type code
Alarm type code
Alarm type
“Open/close” shows status of relay contact,
and “lit” and “unlit” shows status of lamp
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
Alarm type
No alarm
OFF
PV high limit
PV low limit
1
11
2
12
De-energized
on PV high limit
De-energized
on PV low limit
9
19
10
20
22
21
“Open/close” shows status of relay contact,
and “lit” and “unlit” shows status of lamp
Fault diagnosis output (Note1)
FAIL output (Note2)
Alarm setpoint
Closed (lit)
Hysteresis
PV
Open (unlit)
Closed (lit)
Hysteresis
Open (unlit)
Alarm setpoint
PV
PV
Open (lit)
Alarm setpoint
Hysteresis
Closed
(unlit)
Alarm setpoint
Hysteresis
PV
Open (lit)
Closed
(unlit)
Note1: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
Note2: FAIL output
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns
off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
Treated
as normal
⬚
C
Power-on
Time
The alarm output does not
turn on in this region even
if the PV value is below the
low limit of the alarm setpoint.
Low limit of
alarm setpoint
Normal
Abnormal
The alarm
output turns on.
Stand-by Action
It is effective in the following cases where;
- the power is turned on
- the alarm type is changed
●
Behavior of the PV High-limit Alarm Parameter (Alarm Type Code: 1)
Alarm
setpoint
Alarm hysteresis
Alarm
contact output
Off
Off
On
PV value
■
Useful Operating Display (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to
change settings easily. A maximum of four displays can be registered.
Setting method:
Set the parameter numbers (D register numbers) you wish to register for
setup parameters C.S1 to C.S4.
●
Numbers for Registration with SELECT Display
Operating Parameter
Registration Number
Alarm-1 setpoint (A1)
Alarm-2 setpoint (A2)
Alarm-3 setpoint (A3)
Alarm-4 setpoint (A4)
231
232
233
234
Bias (BS)
243
Filter (FL)
244
Setup Parameter
Registration Number
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
919
920
921
922
S E T / E N T
key
S E T / E N T
key
PV display
Ordinary operating
displays (example)
Alarm-1 setting
display (example)
Useful
operating display
(SELECT display)
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T