background image

IM 05F01D02-02E (2)

This manual describes key entries for operating the indicator. If you cannot remember how to carry out an operation during
setting, press the 

S E T / E N T

 key for more than 3 seconds. This brings you to the display (operating display) that appears at

power-on.

Contents

1.

Setting Alarm Setpoints

2.

Troubleshooting

NOTE

Do not use the instrument generating strong magnetic field such as radio equipment and the like near the indicator.
This may cause the fluctuation of the PV value.

1. Setting Alarm Setpoints

The following operating procedure describes an example of setting
a value of 160.0 in the alarm-1 setpoint parameter.  Before setting
the alarm setpoint, check the alarm type.  To change the alarm type,
see “4. Changing Alarm Type”  in   

Initial Settings User's

Manual  

.

Press the            key once to display the parameter 
“A1”.

Bring the operating display into view (display 
appears at power on).

Press the            key once to register the setpoint.

You can take the same steps for alarm-2 setpoint 
(A2), alarm-3 setpoint (A3), and alarm-4 setpoint 
(A4) that are displayed after this.

1.

3.

Press the       or       key to display the required 
setpoint.

4.

5.

Press the            key for more than 3 seconds. 
This returns you to the display shown at power-on 
(figure below).

Press the            key for more than 3 seconds to call 
up the menu “OP.PA”.

2.

6.

S E T / E N T

S E T / E N T

S E T / E N T

S E T / E N T

P V

AL1

2

3

4

S E T / E N T

P V

AL1

2

3

4

S E T / E N T

P V

AL1

2

3

4

S E T / E N T

P V

AL1

2

3

4

S E T / E N T

P V

AL1

2

3

4

S E T / E N T

P V

AL1

2

3

4

S E T / E N T

Displays PV.

Displays PV.

Displays 

parameter 

“A1”.

Displays menu 

“OP.PA”.

Blinks during 

change.

User’s
Manual

Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual

   Operations

IM 05F01D02-02E

2. Troubleshooting

Troubleshooting Flow

If the operating display does not appear after turning on the indicator's power, try to solve the problem by following the
procedure below.  If the problem seems to be complex, contact the vendor from which you purchased the instrument.

Ask the vendor for repair.

Find the cause.

Totally 

inoperable?

Yes

Yes

Yes

No

No

No

Is key 

operation 

faulty?

Yes

No

Yes

Check wiring on the 
power supply 
terminals.

Check the key lock 
setting.

Is display 

faulty?

Yes

No

Turn off power, and 
then turn it on 
again.

Is I/O 

signal faulty?

Yes

No

Check the 
instrument’s I/O 
specifications.

Check the supply 
voltage.

Check the specifications 
of I/O counterpart for 
wrong polarity.

Check the 
communication-related 
parameters.

Check the specifications 
of communication 
counterpart.

Check 
communication wiring.

Is 

communication 

link faulty?

No

Does the code 

include a communication 

option?

Yes

Normal?

Is 

key lock 

enabled?

Check the 
instrument's suffix 
code.

Yes

No

Correct?

Correct 

errors.

Disable 

key lock.

No communication 

capability.

 Is the instrument 

defective?

IMPORTANT

Take note of the parameter settings when asking the vendor for repair.

Errors at Power On

The following table shows errors that may be detected by the fault diagnosis function when the power is turned on.

(E000)

(E002)

(E001)

(E400)

Error indication 

(on PV display unit) 

Description 

of error 

Remedy

Faulty RAM

Faulty ROM

System data error 

PV decimal point blinks. 

Faulty calibration 
value 

PV

Control 

output 

Alarm 

output 

Retransmission 

output 

Communi-

cation

None

OFF

0% or less

Stopped

0%

0% or less 
or OFF

0%

Normal 
action 

Faulty 
Contact us 
for repair. 

Normal action 
(out of 
accuracy) 

Normal action 
(out of 
accuracy) 

Normal action 
(out of 
accuracy) 

Normal action 
(out of 
accuracy) 

Parameter error 

0%

Preset value OFF

0%

Check and set
the parameters,
as they have 
been set to the 
limited values.

Possible Errors during Operation

The following shows possible errors occurring during operations.

Retransmis-

sion output 

Commu-

nication

(-OVER)

(OVER) or 

Error indication
(on PV display 
unit)

Displays “RJC”
and PV
alternately

Faulty 
Contact us for repair.

Faulty 
Contact us for repair.

Check wires and 
sensor.

Description
of error

RJC error 

EEPROM
error 

A/DC error

PV burnout 
error 

PV

Measured with RJC=OFF

Normal action

105%

Dependent on the BSL
parameter Up-scale: 105%
Down-scale: -5%

Control
output

Normal
action

Normal
action

Preset
value

Preset
value

Alarm
output

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Remedy

Normal
action

Normal
action

Normal
action

Normal
action

Check process.

SP decimal pont
blinks (on 
setpoint display 
unit).

PV value blinks.

Check wires and 
communication parameters,
and make resetting.
Recovery at normal receipt

Excessive PV 
Out of -5 to
105%

Faulty 
communi-
cation line 

-5% or 105%

Normal action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

Normal
action

All indications off

Faulty if power off/on does
not reset start the unit. 
Contact us for repair.

All indications off

Check for abnormal  power.

Runaway (due
to defective
power or
noise) 

Power off

None

None

0% or less
or OFF

0%

OFF

OFF

0% or 
less

0%

Stopped 

Stopped 

(B.OUT)

(E300)

If a Power Failure Occurs during Operation

Momentary power failures shorter than 20 ms

The indicator is not affected at all and continues normal operation.

Momentary power failures of 20 ms or longer

• The alarm function of the indicator continues to work normally.  (Alarms with the stand-by feature temporarily return to

their stand-by state, however.)

• Setting parameters that have already been configured retain their settings.

4th Edition: Jan 31, 2005

Alarm output terminals

Factory-set defaults 

Alarm-1 (terminal numbers            )............PV high limit alarm 
Alarm-2 (terminal numbers            )............PV low limit alarm 
Alarm-3 (terminal numbers            )............PV high limit alarm 
Alarm-4 (terminal numbers                 ).......PV low limit alarm

-

6

7

-

5

7

-

4

7

-

-

1

2

3

Отзывы: