<5. Parameters>
5-3
IM 05F01D02-41E
1st Edition : May 31,2000-00
■
Setup Parameters
●
Alarm/Communication Related Parameters
Alarm-1 type
Alarm-2 type
Alarm-3 type
Alarm-4 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 delay timer
0.0 to 100.0% of PV input range span
Hysteresis can be set in the alarm setpoint.
Setting hysteresis prevents relays from chattering.
An alarm is output when the delay timer expires
after the alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm-
1 type “AL1” is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
2 type “AL2” is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
3 type “AL3” is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
4 type “AL4” is 1, 2, 9, 10, 11, 12, 19, and 20)
(AL1)
(AL2)
(AL3)
(AL4)
(HY1)
(HY2)
(HY3)
(HY4)
(DY1)
(DY2)
(DY3)
(DY4)
Parameter
Symbol
Name of Parameter
OFF (0)
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
9: PV high limit (de-energized, no stand-by action)
10: PV low limit (de-energized, no stand-by action)
11: PV high limit (energized, stand-by action)
12: PV low limit (energized, stand-by action)
19: PV high limit (de-energized, stand-by action)
20: PV low limit (de-energized, stand-by action)
21: Fault diagnosis output
Turns on in case of input burnout, A/D converter
failure, or reference junction compensation
(RJC) failure.
22: FAIL output
Turns off in case of program failure, ROM failure,
RAM failure, or power failure. This output is on
during normal operation. If it turns off, the
retransmission output is set to 0%, the alarm
output is set to OFF, and the indicator stops.
See “List of Alarm Types” for details on how these Alarm
Type parameters behave.
Time
Timer setpoint
Open
(Off)
Closed (On)
Open
(Off)
Open
Closed
Open
External contact
Blinking
Protocol selection
Baud rate
0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
0: PC link communication
1: PC link communication (with sum check)
2: Ladder communication
7: MODBUS (ASCII)
8: MODBUS (RTU)
(P.SL)
(BPS)
Point of on-off action
(Alarm setpoint)
PV value
Output
On
Off
Hysteresis
Hysteresis setting for PV high limit alarm
1
2
1
2
0.5% of PV
input range span
Output alarms
0.5%
0.00
0
4
Setting Range and Description
Initial Value
User Setting