<2. Initial Settings>
2-5
IM 05F01D02-41E
■
Instrument Input Range Codes
Input
Type
Instrument Input
Range Code
Instrument
Input Range
Measurement Accuracy
OFF
1
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
2
K
J
4
5
T
6
⫾
0.1% of instrument range
⫾
1 digit for temperatures
equal to or higher than 0
°
C
⫾
0.2% of instrument range
⫾
1 digit for temperatures
below 0
°
C
⫾
0.1% of instrument range
⫾
1 digit for temperatures
equal to or higher than 0
°
C
⫾
0.2% of instrument range
⫾
1 digit for temperatures
below 0
°
C
B
7
⫾
0.15% of instrument range
⫾
1 digit for temperatures
equal to or higher than 400
°
C
⫾
5% of instrument range
⫾
1 digit for temperatures
below 400
°
C
S
8
R
9
⫾
0.15% of instrument range
⫾
1 digit
N
10
⫾
0.1% of instrument range
⫾
1 digit
⫾
0.25% of instrument range
⫾
1 digit for temperatures
below 0
°
C
E
11
L(DIN)
12
13
U(DIN)
14
W
15
⫾
0.2% of instrument range
⫾
1 digit
Platinel 2
16
⫾
0.1% of instrument range
⫾
1 digit
PR20-40
17
⫾
0.5% of instrument range
⫾
1 digit for temperatures
equal to or higher than 800
°
C
No guarantee of accuracy for temperatures below 800
°
C
Thermocouple
Unspecified
W97Re3-
W75Re25
18
⫾
0.2% of instrument range
⫾
1 digit
30
⫾
0.1% of instrument range
⫾
1 digit (Note 1) (Note 2)
JPt100
31
⫾
0.2% of instrument range
⫾
1 digit (Note 1)
35
36
⫾
0.1% of instrument range
⫾
1 digit (Note 1) (Note 2)
RTD
Pt100
37
⫾
0.2% of instrument range
⫾
1 digit (Note 1)
0.4 to 2 V
40
Standard
signal
1 to 5 V
41
0 to 2 V
50
0 to 10 V
51
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
55
-10.00 to 20.00 mV
DC voltage
0 to 100 mV
56
0.0 to 100.0 mV
⫾
0.1% of instrument range
⫾
1 digit
The read-out range can be scaled between -1999 and
9999.
3
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
-200 to 1370
⬚
C
-300 to 2500
⬚
F
-199.9 to 999.9
⬚
C
0 to 2300
⬚
F
-199.9 to 500.0
⬚
C
-199.9 to 999.9
⬚
F
-199.9 to 999.9
⬚
C
-300 to 2300
⬚
F
-199.9 to 400.0
⬚
C
-300 to 750
⬚
F
0.0 to 400.0
⬚
C
-199.9 to 750.0
⬚
F
0 to 1800
⬚
C
32 to 3300
⬚
F
0 to 1700
⬚
C
32 to 3100
⬚
F
0 to 1700
⬚
C
32 to 3100
⬚
F
-200 to 1300
⬚
C
-300 to 2400
⬚
F
-199.9 to 999.9
⬚
C
-300 to 1800
⬚
F
-199.9 to 900.0
⬚
C
-300 to 1300
⬚
F
-199.9 to 400.0
⬚
C
-300 to 750
⬚
F
0.0 to 400.0
⬚
C
-199.9 to 750.0
⬚
F
0 to 2300
⬚
C
32 to 4200
⬚
F
0 to 1390
⬚
C
32 to 2500
⬚
F
0 to 1900
⬚
C
32 to 3400
⬚
F
0 to 2000
⬚
C
32 to 3600
⬚
F
-199.9 to 500.0
⬚
C
-199.9 to 999.9
⬚
F
-150.0 to 150.0
⬚
C
-199.9 to 300.0
⬚
F
-199.9 to 850.0
⬚
C
-300 to 1560
⬚
F
-199.9 to 500.0
⬚
C
-199.9 to 999.9
⬚
F
-150.0 to 150.0
⬚
C
-199.9 to 300.0
⬚
F
*
Performance in the standard condition (at 23
⫾
2
⬚
C, 55
⫾
10%RH, and 50/60 Hz power frequency.
Note 1: The accuracy is
⫾
0.3
⬚
C of instrument range
⫾
1 digit for a temperature range from 0
⬚
C to 100
⬚
C.
Note 2: The accuracy is
⫾
0.5
⬚
C of instrument range
⫾
1 digit for a temperature range from -100
⬚
C to 200
⬚
C.
*
To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250
⍀
resistor. This
resistor is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)