3. CONFIGURATION
IM 2493AAA-1
4
CONFIGURING THE 2493 POWER SERIES
Plus
METER
The new triple-display POWER SERIES
Plus
can be configured for voltage and
current inputs from instrument transformers, as well as analog outputs, RS-485
network address and a rolling average display.
All set-up functions can be performed using the four push-buttons on the front
panel see below) or via RS-485 communications. You can also use the buttons
to display the minimum and maximum readings and to change the display from
phase to phase.
This button
starts all
operations.
When
viewing or
changing
settings it is
used to
back out of
a mode.
This button,
when
changing
settings, it
moves
between
settings or
between
digits.
This button
will
increment
the value
being
changed.
It is also
used to
display Max
readings.
This button,
when
changing
settings, is
used to
select a
mode, save
it, and then
move to the
next mode
in the
sequence.
It is also
used to
display Min
readings.
All button operations are begun with the Mode button.
To see the Min or Max, push the Mode button and then the button of the reading
you want to see – Min or Max. The values will display for ten (10) seconds
before reverting to the normal display. If you want to reset the values, push the
Min or Max button again before the 10 seconds has expired.
To view the configuration settings, press Mode twice (Mode – Mode) and then
press Set. The first setting – the Current Transformer (CT) ratio - will be
displayed.. To see the other settings, press Next. You can scroll through all the
settings by pressing Next. To go back to normal operations, press Mode. To
change the setting being shown, press Set. See the specific sections on the
following pages for details on how to change the settings. Once a setting is