5. CHANGING SETTINGS
IM 2493AAA-1
9
“ErrL” (Too Low) when you try to advance to the secondary. The ratio of the
Primary and Secondary must be between 1.000 and 5000. You will get “ErrH” or
ErrL” if you try to advance to Confirm mode with an incorrect ratio.
If you try to save a ratio value that exceeds the precision of the unit, that value
will be automatically rounded off. For example, setting the CT to a ratio of 5.367
to 5 results in a value of 1.0734. The unit will round this to 1.073, and in the
future display the ratio as 5.365 to 5. Setting the secondary to 1 will always
avoid this.
Changing the rolling average setting
The rolling average causes the displayed value to be an average of the number
of samples to which this parameter is set. Increasing this setting will reduce digit
bounce, but will slow the display response time. The analog output response time
is not affected by this setting.
When you reach the Average setting, press Set and the first digit will begin
blinking.
To increment the value of the digit, press Inc. Once a digit has reached 9 (nine),
it will then go to 0 (zero). To move to the second digit press Next. To return to
the first digit press Next again. When you have set the desired value, press Set.
Both digits will blink, showing you are now in Confirm mode. If the value is
correct press Set one more time to save the value and move on to the Address
setting. Pressing Mode at any time before this will restore the old setting.
The average can be set to any value from 0 to 29.