Appendx 2 Event Acton Confguraton Examples
Example 1: To Start/Stop Memory Samplng by Usng the Remote Control
Functon (/R1 Opton)
We will configure the MV so that it starts or stops memory sampling when a signal is
applied to remote control input terminal 2. We will use event action number 1.
• Dsplay and Settngs
Press
MENU
and then select
Menu
tab >
Tmer, Event acton
>
Event acton
.
<Operaton>
If you turn ON the input to remote control input terminal 2, the MV will start memory
sampling (if it isn’t already). If you turn OFF the input, the MV will stop memory sampling.
Example 2: To Wrte a Message When an Alarm Occurs
We will configure the MV so that it will write the message “Channel 1 Alarm” to group 1
when an alarm occurs on channel 1. We will use event action number 2.
• Dsplay and Settngs
Press
MENU
and then select
Menu
tab >
Tmer, Event acton
>
Event acton
.
<Other Settngs>
• Assign an alarm to channel 1, and configure the MV so that alarm events are sent to
internal switch 3.
• Register “Channel 1 Alarm” to message number 4.
For alarm configuration instructions, see section 3.7.
For message registration instructions, see section 6.4.