5.3  Settings Related to Alarm Output 

Set the following parameters when output-2 is specified for alarm 

output. 

5.3.1  Alarm Setpoints 

  Set the alarm setpoints of alarm-1 and alarm-2 in 

[E03: SET 

POINT1]

 and 

[E04: SET POINT2]

 numerically. 

 •

Setting range: A range of 0 to 100% of input range 

 •

Setting resolution: 0.1% 

5.3.2  Direction of Alarm Action 

  Select the direction of alarm-1 action and that of alarm-2 

action from among HIGH ALM (high-limit alarm) and LOW 

ALM (low-limit alarm) and set each in 

[E05: ALM1 ACTION]

 

(direction of alarm-1 action) or 

[E06: ALM2 ACTION]

 

(direction of alarm-2 action). 

 •

To activate alarm status when input signal ≥ alarm setpoint, 

select HIGH ALM. 

 •

To activate alarm status when input signal ≤ alarm setpoint, 

select LOW ALM. 

5.3.3  Hysteresis 

  Set alarm-1 and alarm-2 hysteresis, in 

[E09: HYSTERESIS1]

 

and 

[E10: HYSTERESIS2]

.  Hysteresis is a value added to the 

alarm setpoint in order for an alarm status to be released (to 

normal) after the alarm status has been activated. The alarm 

status will be released in the following conditions, depending 

on the direction of alarm action. 

*  When HIGH ALM (high-limit alarm) is set: Alarm is released 

when input signal < (alarm setpoint - hysteresis). 

*  When LOW ALM (low-limit alarm) is set: Alarm is released 

when input signal > (alarm se hysteresis). 

 •

Setting range: A range of 0 to 100% of input range 

 •

Setting resolution: 0.1% 

5.3.4  Alarm ON Delay and Alarm OFF Delay 

  Set alarm-1 and alarm-2 ON delays in 

[E11: ON DELAY1]

 and 

[E12: ON DELAY2]

 and then alarm-1 and alarm-2 OFF delays 

in 

[E13: OFF DELAY1]

 and 

[E14: OFF DELAY2]

  An alarm ON delay is a delay time from the establishment of 

alarm condition to alarm output; an alarm OFF delay is a delay 

time from the establishment of return-to-normal condition to 

output. 

 •

Setting range: 0 to 999 seconds 

 •

Setting resolution: 1 second (Note that about 0.2 second 

will be added to set time to prevent erroneous operation.) 

  For example, when an alarm ON delay is set to 1 second, 

alarm output is generated if alarm status continues for 

more than 1 second after the input value exceeds the 

alarm setpoint. Further, when an alarm OFF delay is set 

to 2 seconds, alarm output is released if normal condition 

continues for more than 2 seconds after the input value has 

returned to normal from the alarm status.

5.3.5  Direction of Relay Action 

  Set the direction of relay energizing in alarm-1 normal 

condition and alarm-2 normal condition by selecting from 

among NRM DE-ENERGIZED (de-energized under normal 

condition) and NRM ENERGIZED (energized under normal 

condition) in 

[E15: RL1 ACTION]

 and 

[E16: RL2 ACTION]

 

and set them. 

6.  DESCRIPTION OF ALARM ACTIONS 

This chapter describes examples of alarm actions under the 

following conditions. 

Item

Alarm 1

Alarm 2

Parameter

Setpoint Parameter

Setpoint

Direction of alarm 

action

E05: ALM1 ACTION

High-limit 

alarm

E06: ALM2 ACTION Low-limit 

alarm

Alarm setting

E03: SET POINT1

80%

E04 : SET POINT2

15%

Hysteresis

E09: HYSTERESIS1 10%

E10 : HYSTERESIS2 5%

Alarm ON delay

E11: ON DELAY1

1 sec

E12 : ON DELAY2

3 sec

Alarm OFF delay

E13: OFF DELAY1

2 sec

E14 : OFF DELAY2

4 sec

Description of  

alarm actions

The alarm is output if the 

condition where the input value 

is 80% or more of high-limit 

alarm continues for 1 second 

or more.

After the alarm is output, when 

the condition where the input 

value is less than 70% of 

high-limit alarm continues for 

2 seconds or more, the status 

returns to normal.

The alarm is output if the 

condition where the input value 

is 15% or less of low-limit 

alarm continues for 3 seconds 

or more.

After the alarm is output, when 

the condition where the input 

value is more than 20% of 

low-limit alarm continues for 

4 seconds or more, the status 

returns to normal.

Figure 6.1

Alarm-1 action

Alarm-2 action

Normal

Normal

Normal

Normal

Alarm

Alarm

[

]

0

20

15

40

60

80

100

1 s.

2 s.

3 s.

4 s.

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time s.

[1]

[2]

[3]

[4]

Alarm-1 

ON delay

Alarm-2 

ON delay

Alarm-2 

OFF delay

Alarm-1 

OFF delay

Alarm conditions established

Alarm conditions

established

Normal conditions

established

Normal conditions established

High-limit alarm ON

Low-limit alarm ON

High-limit alarm OFF

Low-limit alarm OFF

[1] Alarm status does not continue for more than 1 second after the 

alarm conditions are established at alarm 1.

[2] Normal status does not continue for more than 2 seconds after 

the normal conditions are established at alarm 1.

[3] Alarm status does not continue for more than 3 seconds after the 

alarm conditions are established at alarm 2.

[4] Normal status does not continue for more than 4 seconds after 

the normal conditions are established at alarm 2.

4

IM 77J01A07-01E

5th Edition